background image

 

3

Standard rear suction 

(See figure 6a)

Installation with rear duct and duct service opening 

(See 

figure 6b)

Installation with rear duct, no duct service opening 

(See 

figure 6c)

Mounting the air inlet panel with a canvas connection 

(See 

figure 7a)

Mounting the air inlet panel directly 

(See figure 7b)

Bottom suction 

(See figure 7c)

2

The fan speed for this indoor unit is preset to provide standard
external static pressure.

3

Install the suspension bolts.
(Use M10 size bolt for the suspension bolt.) Use anchors for
existing ceilings, and a sunken insert, sunken anchors or other
field supplied parts for new ceilings to reinforce the ceiling in
order to bear the weight of the unit.

Installation example 

(See figure 3)

Indoor unit installation

When installing optional accessories (except for the air inlet panel),
read also the installation manual of the optional accessories.
Depending on the field conditions, it may be easier to install optional
accessories before the indoor unit is installed.

1

Install the indoor unit temporarily.
- Attach the hanger bracket to the suspension bolt. Be sure to 

fix it securely by using a nut and washer from the upper and 
lower sides of the hanger bracket. 

(See figure 4)

2

Check if the unit is horizontally levelled.
- Do not install the unit tilted. The indoor unit is equipped with a 

built-in drain pump and float switch. (If the unit is tilted 
against condensate flow, the float switch may malfunction 
and cause water to drip.)

- Check if the unit is levelled at all four corners with a water 

level or a water-filled vinyl tube as shown in 

figure 9

.

3

Tighten the upper nut.

Installing the duct

Connect the duct supplied in the field.

Air inlet side

- Attach the duct and intake-side flange (field supply).
- Connect the flange to the main unit with accessory screws 

(7).

- Wrap the intake-side flange and duct connection area with 

aluminum tape or something similar to prevent air escaping.

1

Ceiling surface

2

Ceiling opening

3

Service access panel (optional accessory)

4

Air filter

5

Air inlet duct

6

Duct service opening

7

Interchangeable plate

NOTE

Before installation of the unit (in case of installation
with duct, but no duct service opening): modify the
position of the air filters.

1

Remove the air filter(s) at the 
outside of the unit

2

Remove the interchangeable 
plate

3

Install the air filter(s) from the 
inside of the unit

4

Reinstall the interchangeable 
plate

NOTE

When installing an air inlet duct, select fixing screws
that shall stick out maximum 5 mm at the inside of the
flange to protect the air filter from damage during
maintenance of the filter.

1

Air inlet duct

2

Inside of the flange

3

Fixing screw

1

Ceiling surface

2

Ceiling opening

3

Air inlet panel (Optional accessory)

4

Indoor unit (Back side)

5

Canvas connection for air inlet panel (Optional accessory)

Model

A (mm)

50

1460

63

1610

NOTE

The unit can be used with bottom suction by replacing
the interchangeable plate by the air filter holding plate.

1

2

4

3

1

2

3

5 mm

1

Air filter holding plate with air filter(s)

2

Interchangeable plate

NOTE

For other installation than standard installation, contact
your Daikin dealer for details.

1

Anchor

2

Ceiling slab

3

Long nut or turn-buckle

4

Suspension bolt

5

Indoor unit

NOTE

All the above parts are field supplied.

For other installation than standard installation,
contact your dealer for details.

1

Nut (field supply)

2

Washer for hanger bracket (supplied with the unit)

3

Tighten (double nut)

1

Water level

2

Vinyl tube

When attaching a duct to the intake side, be sure to attach
an air filter inside the air passage on the intake side. (Use
an air filter whose dust collecting efficiency is at least 50%
in a gravimetric technique.)
The included filter is not used when the intake duct is
attached.

Summary of Contents for FXTQ50A2VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXTQ50A2VEB FXTQ63A2VEB System air conditioners...

Page 2: ...1 2 4 5 3 6a 7c 6b 6c 8 9 10 11 2 1 3 5 4 5 2 1 1 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 6 3 5 6 4 2 1 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4...

Page 3: ...como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como esta...

Page 4: ...of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install accessories on the casing directly Drilling holes in the casing may da...

Page 5: ...tance between wireless remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible...

Page 6: ...accessory screws 7 Wrap the intake side flange and duct connection area with aluminum tape or something similar to prevent air escaping 1 Ceiling surface 2 Ceiling opening 3 Service access panel opti...

Page 7: ...lacement or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preve...

Page 8: ...ge of outdoor unit R additional refrigerant charge according to liquid piping diameter length and outdoor unit specific amount defined in outdoor unit manual P additional refrigerant charge due to use...

Page 9: ...pump mounted in this unit is the high lift type The characteristic of this pump is that the higher the pump is the lower the drainage sound becomes Therefore a drain pump height of 300mm is recommend...

Page 10: ...turned back on again Refer to the installation manual delivered with the outdoor unit for the size of power supply electric wire connected to the outdoor unit the capacity of the earth leakage breaker...

Page 11: ...or transmission wiring This mistake could damage the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the termi...

Page 12: ...hermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote...

Page 13: ...ure to turn on the outdoor unit before performing the test operation on the outdoor unit If any other error display occurs on the display of the remote controller refer to Test operation on page 11 an...

Page 14: ...mpossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneously as shown and then pull them downward Wire...

Page 15: ...ve any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel disp...

Page 16: ...ONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING X33A CONNECTOR FOR WIRING X35A CONNECTOR POWER SUPPLY FOR WIRING X38A CONNECTOR FOR WIRING FIELD WIRING BLK BLACK PNK PINK CONNECTOR...

Page 17: ......

Page 18: ......

Page 19: ...F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 P1 P2 F1 F2 T1 T2 1 3 6 2 1 2 5 6 3 4...

Page 20: ...4P410034 1 2015 05 Copyright 2015 Daikin...

Reviews: