background image

 

5

When using FXTQ (high efficiency range) indoor units in combination
with VRV4 outdoor unit systems, please take into account the
following rules.

1

Combination table

FXTQ indoor units can only be used corresponding to below
combination table. 
FXTQ indoor units cannot be combined with any other indoor
unit type compatible with the outdoor unit.

2

Piping rules for the complete system

Following piping rules have to be respected:

3

Piping connections

General layout (2 possibilities)

1.  

2.  

A: Piping between outdoor unit and (first) refrigerant branch kit

Choose from the following table in accordance with the outdoor unit
total capacity type, connected downstream.

REYQ*T

RYYQ*T & RXYQ*T

B: Piping between refrigerant branch kits (or BS box)

Choose from the following table in accordance with the indoor unit
total capacity type, connected downstream. Do not let the connection
piping exceed the refrigerant piping size chosen by the general
system model name.

Selection of refrigerant branch kits: Refnet headers and Refnet joints

4

Additional refrigerant charge

When using FXTQ indoor units, additional refrigerant needs to be
charged to the system. 

Total system refrigerant charge = Z; Z = O + R + P

O: standard factory charge of outdoor unit
R: additional refrigerant charge according to liquid piping diameter/length and outdoor unit
specific amount defined in outdoor unit manual
P: additional refrigerant charge due to use of FXTQ indoor units
P = 

Σ

 T

1..4

T: additional charge for each indoor unit used (depending on type)

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

Outdoor unit 

FXTQ63

FXTQ50

RYYQ8T

-

4 x O

RYYQ10T

4 x O

-

RXYQ8T

-

4 x O

RXYQ10T

4 x O

-

REYQ8T

-

4 x O

REYQ10T

4 x O

-

Maximum piping length

Longest pipe (actual)

120m

After first branch

40m

Total piping length

300m

Maximum height difference

Indoor-Outdoor (outdoor lowest)

40m

Outdoor-Indoor (outdoor highest)

50m

Indoor-Indoor

15m

1

2

3

4

5

6

6

A

C

a1

a2

a2

ID1

ID2

ID3 

ID4

OU

ID1

ID2

ID3

ID4

8HP

FXTQ50

FXTQ50

FXTQ50

FXTQ50

10HP

FXTQ63

FXTQ63

FXTQ63

FXTQ63

Outdoor unit 

capacity type 

(HP)

Piping outer diameter size (mm)

Liquid pipe

Suction gas pipe

High pressure/

low pressure gas 

pipe

8

9.5

19.1

15.9

10

9.5

22.2

19.1

Outdoor unit 

capacity type 

(HP)

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

8

19.1

9.5

10

22.2

9.5

8/10HP

Liquid

Suction 

gas

HP/LP 

gas

RXYQ

9,5

22,2

-

RYYQ

REYQ

19,1

Refnet joints

Refnet headers

a1

a2

b

8HP

KHRQ22M29T9

or

KHRQ23M29T9

KHRQ22M29T9

or

KHRQ23M29T9

KHRQ22M64H

or

KHRQ23M64H

10HP

KHRQ22M29T9

or

KHRQ23M29T9

KHRQ22M29T9

or

KHRQ23M29T9

KHRQ22M64H

or

KHRQ23M64H

A

C

b

ID1

ID2

ID3

ID4

OU

Summary of Contents for FXTQ50A2VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXTQ50A2VEB FXTQ63A2VEB System air conditioners...

Page 2: ...1 2 4 5 3 6a 7c 6b 6c 8 9 10 11 2 1 3 5 4 5 2 1 1 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 6 3 5 6 4 2 1 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4...

Page 3: ...como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como esta...

Page 4: ...of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install accessories on the casing directly Drilling holes in the casing may da...

Page 5: ...tance between wireless remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible...

Page 6: ...accessory screws 7 Wrap the intake side flange and duct connection area with aluminum tape or something similar to prevent air escaping 1 Ceiling surface 2 Ceiling opening 3 Service access panel opti...

Page 7: ...lacement or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preve...

Page 8: ...ge of outdoor unit R additional refrigerant charge according to liquid piping diameter length and outdoor unit specific amount defined in outdoor unit manual P additional refrigerant charge due to use...

Page 9: ...pump mounted in this unit is the high lift type The characteristic of this pump is that the higher the pump is the lower the drainage sound becomes Therefore a drain pump height of 300mm is recommend...

Page 10: ...turned back on again Refer to the installation manual delivered with the outdoor unit for the size of power supply electric wire connected to the outdoor unit the capacity of the earth leakage breaker...

Page 11: ...or transmission wiring This mistake could damage the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the termi...

Page 12: ...hermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote...

Page 13: ...ure to turn on the outdoor unit before performing the test operation on the outdoor unit If any other error display occurs on the display of the remote controller refer to Test operation on page 11 an...

Page 14: ...mpossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneously as shown and then pull them downward Wire...

Page 15: ...ve any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel disp...

Page 16: ...ONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING X33A CONNECTOR FOR WIRING X35A CONNECTOR POWER SUPPLY FOR WIRING X38A CONNECTOR FOR WIRING FIELD WIRING BLK BLACK PNK PINK CONNECTOR...

Page 17: ......

Page 18: ......

Page 19: ...F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 P1 P2 F1 F2 T1 T2 1 3 6 2 1 2 5 6 3 4...

Page 20: ...4P410034 1 2015 05 Copyright 2015 Daikin...

Reviews: