background image

 

2

Optional accessories

There are two types of remote controllers: wired and wireless.
Select a remote controller according to customer request and
install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.

When installing bottom suction: air inlet panel and canvas
connection for the air inlet panel.

For the following items, take special care during 
construction and check after installation is finished

Notes to the installer

Read this manual carefully to ensure correct installation. Be sure
to instruct the customer how to properly operate the system and
show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.

Important information regarding the 
refrigerant used

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

(1)

 GWP = global warming potential

Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.

Selecting installation site

(See 

figure 1

 and 

figure 2

)

1

Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.
- Where optimum air distribution can be ensured.
- Where nothing blocks air passage.
- Where condensate water can be properly drained.
- Where the false ceiling is not noticeably on an incline.
- Where sufficient clearance for maintenance and service can 

be ensured.

- Where there is no risk of flammable gas leaking.
- The equipment is not intended for use in a potentially 

explosive atmosphere.

- Where piping between indoor and outdoor units is possible 

within the allowable limit. (Refer to the installation manual of 
the outdoor unit.)

- Keep indoor unit, outdoor unit, power supply wiring and 

transmission wiring at least 1 meter away from televisions 
and radios. This is to prevent image interference and noise in 
those electrical appliances. (Noise may be generated 
depending on the conditions under which the electric wave is 
generated, even if 1 meter is kept.)

- When installing the wireless remote controller kit, the 

distance between wireless remote controller and indoor unit 
might be shorter if there are fluorescent lights who are 
electrically started in the room. The indoor unit must be 
installed as far as possible away from fluorescent lights.

- Do not place objects that are susceptible to moisture directly 

beneath the indoor or outdoor units. Under certain conditions, 
condensation on the main unit or refrigerant pipes, air filter 
dirt or drain blockage may cause dripping, resulting in fouling 
or failure of the object concerned.

2

Ensure that a protective guard is installed on air suction and air
outlet side to prevent that the fan blades or heat exchanger be
touched.
The protection must comply with relevant European and national
regulations.

3

Use suspension bolts for installation. Check whether the ceiling
is strong enough to support the weight of the indoor unit. If there
is a risk, reinforce the ceiling before installing the unit.

Preparations before installation

1

Relation of ceiling opening to unit and suspension bolt position.

(See figure 5)

For installation, choose one of the possibilities as listed further.

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling or heating.

Is the unit fully insulated and checked for air leaks?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 
name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 
outdoor units?

It may result in insufficient cooling or heating.

Are refrigerant piping length and additional refrigerant charge 
noted down?

The refrigerant charge in the system might not be clear.

Are the air filters fixed properly (when installing with rear duct)?

Maintenance of the air filters can be impossible.

Is the external static pressure set?

It may result in insufficient cooling or heating.

1

Service space

2

Drain pipe

3

Power supply wiring port

4

Transmission wiring port

5

Maintenance drain outlet

6

Gas pipe

7

Liquid pipe

Model

A (mm)

B (mm)

50

1400

1438

63

1550

1588

1

Indoor unit

2

Pipe

3

Suspension bolt pitch (x4)

4

Suspension bolt pitch distance

Summary of Contents for FXTQ50A2VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXTQ50A2VEB FXTQ63A2VEB System air conditioners...

Page 2: ...1 2 4 5 3 6a 7c 6b 6c 8 9 10 11 2 1 3 5 4 5 2 1 1 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 6 3 5 6 4 2 1 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4...

Page 3: ...como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como esta...

Page 4: ...of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install accessories on the casing directly Drilling holes in the casing may da...

Page 5: ...tance between wireless remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible...

Page 6: ...accessory screws 7 Wrap the intake side flange and duct connection area with aluminum tape or something similar to prevent air escaping 1 Ceiling surface 2 Ceiling opening 3 Service access panel opti...

Page 7: ...lacement or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preve...

Page 8: ...ge of outdoor unit R additional refrigerant charge according to liquid piping diameter length and outdoor unit specific amount defined in outdoor unit manual P additional refrigerant charge due to use...

Page 9: ...pump mounted in this unit is the high lift type The characteristic of this pump is that the higher the pump is the lower the drainage sound becomes Therefore a drain pump height of 300mm is recommend...

Page 10: ...turned back on again Refer to the installation manual delivered with the outdoor unit for the size of power supply electric wire connected to the outdoor unit the capacity of the earth leakage breaker...

Page 11: ...or transmission wiring This mistake could damage the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the termi...

Page 12: ...hermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote...

Page 13: ...ure to turn on the outdoor unit before performing the test operation on the outdoor unit If any other error display occurs on the display of the remote controller refer to Test operation on page 11 an...

Page 14: ...mpossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneously as shown and then pull them downward Wire...

Page 15: ...ve any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel disp...

Page 16: ...ONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING X33A CONNECTOR FOR WIRING X35A CONNECTOR POWER SUPPLY FOR WIRING X38A CONNECTOR FOR WIRING FIELD WIRING BLK BLACK PNK PINK CONNECTOR...

Page 17: ......

Page 18: ......

Page 19: ...F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 P1 P2 F1 F2 T1 T2 1 3 6 2 1 2 5 6 3 4...

Page 20: ...4P410034 1 2015 05 Copyright 2015 Daikin...

Reviews: