background image

 

9

External static pressure settings

Settings for external static pressure can be achieved in 2 ways:

Using the airflow automatic adjustment function

Airflow automatic adjustment is the volume of blow-off air that
has been automatically adjusted to the rated quantity.

1

Make sure the test run is done with a dry coil.
If the coil is not dry, run the unit for 2 hours with fan only to dry
the coil.

2

Check if the power supply wiring to the air conditioning unit is
completed along with the duct installation.
If a closing damper is installed in the air conditioning unit, make
sure that it is open.
Also check if the air filter is properly attached into the air
passage on the air suction side of the air conditioning unit.

3

If there is more than one air inlet and outlet, adjust the dampers
so that the airflow rate of each air inlet and outlet is conform with
the designed airflow rate. 
Make sure the air conditioning unit is in fan operation mode.
Press and set the airflow adjustment button on the remote
controller to change the airflow rate to H or L.

4

Setting the airflow automatic adjustment settings.
When the air conditioning unit is running in fan operation mode
perform the next steps:
- stop the air conditioning unit,
- go to field setting mode,
- select mode No. 21 (or 11 in case of group setting),
- set the first code No. to "7",
- set the second code No. to "03".
Return to normal operating mode after setting these settings and
press the ON/OFF operation button. The operation lamp will
light up and the air conditioning unit will start the fan operation
for airflow automatic adjustment.

After 1 to 8 minutes, the air conditioning unit stops operating
automatically when the fan operation for airflow automatic
adjustment has been carried out, the operation lamp will be off.

5

When the air conditioning unit has stopped, check on an indoor
unit if the second code No. of mode No. 21 is set to "02".
If the air conditioning unit does not stop operating or the second
code No. is not "02", repeat step 4.
If the outdoor unit is not turned on, the display on the remote
controller will show "

U4

" or "

UH

" (refer to 

"Test operation" on

page 10

). However, you can continue setting this function

because these messages are only applicable to outdoor units.
After setting this function, be sure to turn on the outdoor unit
before performing the test operation on the outdoor unit.
If any other error display occurs on the display of the remote
controller, refer to 

"Test operation" on page 10

 and the operation

manual of the outdoor unit. Check the defective point.

Using the remote controller

Check on an indoor unit if the second code of mode No. 21 is set to
"01" (= factory setting). Change the second code according to the
external static pressure of the duct to be connected as shown in
table 2.

Table 2

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB".

MAIN/SUB CHANGEOVER

Insert a wedge-head screwdriver into the recess between the
upper and lower part of the remote controller and, working from
the 2 positions, pry off the upper part. 

(See figure 18)

(The remote controller PC board is attached to the upper part of
the remote controller.)

Turn the main/sub changeover switch on one of the two remote
controller PC boards to "S". 

(See figure 19)

(Leave the switch of the other remote controller set to "M".)

Do not adjust the dampers during fan operation for
airflow automatic adjustment.

Mode 

No.

First 

code No.

Second 

code No.

Setting content

11 (21)

7

01

Airflow adjustment is OFF

02

Completion of airflow adjustment

03

Start of airflow adjustment

If the external static pressure higher than 100 Pa, do
not use airflow automatic adjustment function.

If there is no change after airflow adjustment in the
ventilation paths, be sure to perform setting the airflow
automatic adjustment again.

Contact your dealer if there is no change after
performing airflow adjustment in the ventilation paths,
after performing the test operation of the outdoor unit
or when the air conditioning unit is moved to another
location.

If booster fans, an outdoor air processing unit or HRV
via duct are used, do not use airflow automatic
adjustment control with a remote controller.

If the ventilation paths have been changed, perform
the setting of the airflow automatic adjustment again
as described above from step 3 onwards.

NOTE

The second code No. is set to "01" by default.

Mode 

No.

1st 

code 

No.

2nd 

code 

No.

External static pressure (Pa)

FXSQ

15

20

25

32

40

50

63

80

100 125 140

13 

(23)

6

01

30

30

30

30

30

30

30

40

40

50

50

02

-

-

-

-

-

-

-

-

-

-

-

03

30

30

30

30

30

30

30

-

-

-

-

04

40

40

40

40

40

40

40

40

40

-

-

05

50

50

50

50

50

50

50

50

50

50

50

06

60

60

60

60

60

60

60

60

60

60

60

07

70

70

70

70

70

70

70

70

70

70

70

08

80

80

80

80

80

80

80

80

80

80

80

09

90

90

90

90

90

90

90

90

90

90

90

10

100 100 100 100 100 100 100 100 100 100 100

11

110 110 110 110 110 110 110 110 110 110 110

12

120 120 120 120 120 120 120 120 120 120 120

13

130 130 130 130 130 130 130 130 130 130 130

14

140 140 140 140 140 140 140 140 140 140 140

15

150 150 150 150 150 150 150 150 150 150 150

1

Remote controller PC board

2

Factory setting

3

Only one remote controller needs to be changed

Summary of Contents for FXSQ15A2VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXSQ15A2VEB FXSQ20A2VEB FXSQ25A2VEB FXSQ32A2VEB FXSQ40A2VEB FXSQ50A2VEB FXSQ63A2VEB FXSQ80A2VEB FXSQ100A2VEB FXSQ125A2VEB FXSQ140A2VEB System air conditioners...

Page 2: ...1 2 4 5 3 6a 7c 6b 6c 8 9 10 11 2 1 3 5 4 5 2 1 1 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 6 3 5 6 4 2 1 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4...

Page 3: ...or B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo...

Page 4: ...e air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install accessories on the casing directly Drilling...

Page 5: ...mote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible away from fluorescent lig...

Page 6: ...7 Wrap the intake side flange and duct connection area with aluminum tape or something similar to prevent air escaping 1 Ceiling surface 2 Ceiling opening 3 Service access panel optional accessory 4 A...

Page 7: ...or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing nor...

Page 8: ...n this unit is the high lift type The characteristic of this pump is that the higher the pump is the lower the drainage sound becomes Therefore a drain pump height of 300mm is recommended Testing of d...

Page 9: ...installation manual delivered with the outdoor unit for the size of power supply electric wire connected to the outdoor unit the capacity of the earth leakage breaker and fuse and for wiring instruct...

Page 10: ...r transmission wiring This mistake could damage the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the termin...

Page 11: ...hermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote...

Page 12: ...outdoor unit Check the defective point Using the remote controller Check on an indoor unit if the second code of mode No 21 is set to 01 factory setting Change the second code according to the extern...

Page 13: ...mpossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneously as shown and then pull them downward Wire...

Page 14: ...ve any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel disp...

Page 15: ...ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING X33A CONNECTOR FOR WIRING X35A CONNECTOR POWER SUPPLY FOR WIRING X38A CONNECTOR FOR WIRING FIELD WIRING BLK BLACK PNK PINK CONNECTOR BLU BLUE RED RED S...

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ...F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 P1 P2 F1 F2 T1 T2 1 3 6 2 1 2 5 6 3 4...

Page 20: ...4P399436 1A 2015 02 Copyright 2014 Daikin...

Reviews: