Specifications for field supplied fuses and wire

Allowable length of transmission wiring between indoor and outdoor
units, and between the indoor unit and the remote controller is as
follows:

1.

Outdoor unit - indoor unit: max. 1000 m (total wiring length:
2000 m)

2.

Indoor unit - remote controller: max 500 m

Wiring example and how to set the remote 
controller

How to connect wiring

Remove the switch box cover as shown in 

figure 12

, and make the

connections.

Precautions

1.

Observe the notes mentioned below when wiring to the power
supply terminal board.
• Use a round crimp-style terminal for insulation sleeve for

connection to the terminal block for wiring the units. When
none are available, follow the instructions below.

• Do not connect wires of different gauge to the same power

supply terminal. (Looseness in the connection may cause
overheating.)

• When connecting wires of the same gauge, connect them

according to the figure.

Use the specified electric wire. Connect the wire securely to
the terminal. Lock the wire down without applying excessive
force to the terminal. Use torques according to the table below.

• When attaching the control box lid, make sure not to pinch

any wires.

• After all wiring connections are done, fill in any gaps in the

casing wiring holes with putty or insulation material (field
supply) thus to prevent small animals or dirt from entering the
unit from outside and causing short circuits in the control box.

2.

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

3.

Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.

4.

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

5.

Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire
system.

6.

Use only specified wires and tightly connect wires to the terminals.
Be careful that wires do not place external stress on the terminals.
Keep wiring in neat order so that they do not obstruct other
equipment such as popping open the switch box cover. Make sure
the cover closes tight. Incomplete connections could result in
overheating, and in the worse case, electric shock or fire.

Keep total current of crossover wiring between indoor units less than
12 A. Branch the line outside the terminal block of the unit in
accordance with the electrical equipment standards, when using two
power wiring of a gauge greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or greater
degree of insulation as power supply wiring itself.

Wiring example

Fit the power supply wiring of each unit with a switch and fuse as
shown in 

figure 16

.

Complete system example (3 systems)

When using 1 remote controller for 1 indoor unit (Normal operation)

(See figure 15)

For group control or use with 2 remote controllers 

(See figure 17)

When including BS unit 

(See figure 13)

Power supply wiring

Model

Field fuses

Wire

Size

15~140

16 A

H05VV-U3G

Local codes

Model

Wire

Size

15~140

Sheathed wire (2)

0.75-1.25 mm

2

NOTE

For details, refer to 

"Wiring example" on page 7

.

1

Switch box cover

2

Switch box low voltage wiring inlet

3

Switch box high voltage wiring inlet

4

Wiring diagram

5

Switch box

Tightening torque (N•m)

Terminal block for remote controller

0.79~0.97

Terminal block for power supply

1.18~1.44

1

2

3

1

Round crimp-style terminal

2

Attach insulation sleeve

3

Wiring

NOTE

The customer has the ability to select the remote
controller thermistor.

1

Power supply

2

Main switch

3

Power supply wiring

4

Transmission wiring

5

Switch

6

Fuse

7

BS unit REYQ only

8

Indoor unit

9

Remote controller

1

Outdoor unit

2

Indoor unit

3

Remote controller (optional accessories)

4

Most downstream indoor unit

5

For use with 2 remote controllers

6

BS unit

NOTE

It is not necessary to designate an indoor unit address
when using group control. The address is
automatically set when the power is activated.

Summary of Contents for FXSQ15A2VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXSQ15A2VEB FXSQ20A2VEB FXSQ25A2VEB FXSQ32A2VEB FXSQ40A2VEB FXSQ50A2VEB FXSQ63A2VEB FXSQ80A2VEB FXSQ100A2VEB FXSQ125A2VEB FXSQ140A2VEB System air conditioners...

Page 2: ...1 2 4 5 3 6a 7c 6b 6c 8 9 10 11 2 1 3 5 4 5 2 1 1 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 6 3 5 6 4 2 1 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4...

Page 3: ...or B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo...

Page 4: ...e air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install accessories on the casing directly Drilling...

Page 5: ...mote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible away from fluorescent lig...

Page 6: ...7 Wrap the intake side flange and duct connection area with aluminum tape or something similar to prevent air escaping 1 Ceiling surface 2 Ceiling opening 3 Service access panel optional accessory 4 A...

Page 7: ...or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing nor...

Page 8: ...n this unit is the high lift type The characteristic of this pump is that the higher the pump is the lower the drainage sound becomes Therefore a drain pump height of 300mm is recommended Testing of d...

Page 9: ...installation manual delivered with the outdoor unit for the size of power supply electric wire connected to the outdoor unit the capacity of the earth leakage breaker and fuse and for wiring instruct...

Page 10: ...r transmission wiring This mistake could damage the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the termin...

Page 11: ...hermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote...

Page 12: ...outdoor unit Check the defective point Using the remote controller Check on an indoor unit if the second code of mode No 21 is set to 01 factory setting Change the second code according to the extern...

Page 13: ...mpossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneously as shown and then pull them downward Wire...

Page 14: ...ve any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel disp...

Page 15: ...ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING X33A CONNECTOR FOR WIRING X35A CONNECTOR POWER SUPPLY FOR WIRING X38A CONNECTOR FOR WIRING FIELD WIRING BLK BLACK PNK PINK CONNECTOR BLU BLUE RED RED S...

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ...F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 P1 P2 F1 F2 T1 T2 1 3 6 2 1 2 5 6 3 4...

Page 20: ...4P399436 1A 2015 02 Copyright 2014 Daikin...

Reviews: