Installation and operation manual

3

FXSQ20~125M8V3B

VRV System air conditioners

4PW25083-1C

Bottom suction 

(See figure 7a)

Mounting the air inlet panel with a canvas connection 

(See 

figure 7b)

Mounting the air inlet panel directly 

(See figure 7c)

This is to protect the air filter from damage during maintenance of the
filter.

For other installation than standard installation, contact your Daikin
dealer for details.

2

The fan speed for this indoor unit is preset to provide standard
external static pressure.

If higher or lower external static pressure is required, reset the external
static pressure by repositioning the adaptors of the PC-board.
Refer to 

"Setting of static pressure changeover connector" on

page 6

.

3

Install the suspension bolts.

(Use M10 size bolt for the suspension bolt.) Use anchors for
existing ceilings, and a sunken insert, sunken anchors or other
field supplied parts for new ceilings to reinforce the ceiling in
order to bear the weight of the unit.

Installation example 

(See figure 4)

I

NDOOR

 

UNIT

 

INSTALLATION

When installing optional accessories (except for the air inlet panel),
read also the installation manual of the optional accessories.
Depending on the field conditions, it may be easier to install optional
accessories before the indoor unit is installed.

1

Install the indoor unit temporarily.

-

Attach the hanger bracket to the suspension bolt. Be sure to 
fix it securely by using a nut and washer from the upper and 
lower sides of the hanger bracket. 

(See figure 5)

2

Check if the unit is horizontally levelled.

-

Do not install the unit tilted. The indoor unit is equipped with a 
built-in drain pump and float switch. (If the unit is tilted 
against condensate flow, the float switch may malfunction 
and cause water to drip.)

-

Check if the unit is levelled at all four corners with a water 
level or a water-filled vinyl tube as shown in 

figure 13

.

3

Tighten the upper nut.

4

Fix the paper pattern for installation.

-

The paper pattern for installation corresponds with the 
measurements of the ceiling opening. Consult the builder for 
details.

-

Attach the paper pattern for installation to the unit with the 
attached screws as shown in 

figure 17

The paper pattern for installation is marked for 3 types of 
ceiling openings. Read the notations carefully when 
installing.

R

EFRIGERANT

 

PIPING

 

WORK

For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.

Before rigging tubes, check which type of refrigerant is used. 

Use a pipe cutter and flare suitable for the used refrigerant.

Apply ether oil or ester oil around the flare portions before
connecting.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

1

Remove the air filter(s) at the 
outside of the unit

2

Remove the interchangeable plate

3

Install the air filter(s) from the inside 
of the unit

4

Reinstall the interchangeable plate

NOTE

The unit can be used with bottom suction by replacing
the interchangeable plate by the air filter holding plate.

1

Air filter holding plate with air filter(s)

2

Interchangeable plate

3

Small bottom plate

1

Ceiling surface

2

Ceiling opening

3

Air inlet panel (Optional accessory)

4

Indoor unit (Back side)

5

Canvas connection for air inlet panel (Optional accessory)

Model

A

FXSQ20~32

610

50

760

FXSQ63

1060

FXSQ80~125

1460

NOTE

When installing an air inlet duct, select fixing screws
that shall stick out maximum 5 mm at the inside of the
flange.

1

Air inlet duct

2

Inside of the flange

3

Fixing screw

1

2

4

3

1

2

3

5 mm

1

Anchor

2

Ceiling slab

3

Long nut or turn-buckle

4

Suspension bolt

5

Indoor unit

NOTE

All the above parts are field supplied.

1

Nut (field supply)

2

Washer for hanger bracket (supplied with the unit)

3

Tighten (double nut)

1

Water level

2

Vinyl tube

1

Paper pattern for installation (supplied with the unit)

2

Screws for fixing the paper pattern for installation (supplied with 
the unit (6))

NOTE

All field piping must be provided by a licensed
refrigeration technician and must comply with the
relevant local and national codes.

Summary of Contents for FXSQ100M8V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXSQ20M8V3B FXSQ25M8V3B FXSQ32M8V3B FXSQ40M8V3B FXSQ50M8V3B FXSQ63M8V3B FXSQ80M8V3B FXSQ100M8V3B FXSQ125M8V3B System air conditioners...

Page 2: ...2 5 6 7 4 3 4 4 1 3 2 4 5 5 5 2 1 2 3 6a 6a 2 3 1 4 680 85 6b 6b 1 3 2 4 6 5 50 200 45 680 6c 6c 1 5 2 3 7 4 680 65 3 3 1 4 3 4 2 800 630 B A 145 7c 7c 4 2 2 3 1 460 180 350 A 8 8 1 1 5m 0 625mm 2 6...

Page 3: ...e z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 s...

Page 4: ...air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the installation site use the supplied paper...

Page 5: ...nerated even if 1 meter is kept 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If there is a risk reinforce the ceiling bef...

Page 6: ...The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details Attach the paper pattern for installation to the unit with the attached scre...

Page 7: ...ee figure 8 Connect the drain hose to the drain raising pipes and insulate them Connect the drain hose to the drain pipe on the indoor unit and tighten it with the metal clamp To ensure a downward slo...

Page 8: ...matched the system may cause a malfunction Electrical characteristics MCA Min circuit Amps A MFA Max Fuse Amps A KW Fan Motor Rated Output kW FLA Full Load Amps A Specifications for field supplied fus...

Page 9: ...he remote controller 6 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 7 Use only specified wires and tightly connect wi...

Page 10: ...to define time between 2 filter cleaning display indications When contamination is high setting can be changed to half the time inbetween 2 filter cleaning display indications Ultra long life filter L...

Page 11: ...esent unhook the chains 2 Remove the air filters Remove the air filters by pulling their cloth upward rear suction or backward bottom suction 3 Clean the air filter Use vacuum cleaner A or wash the ai...

Page 12: ...fter cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel display lights when the power is turned on To protect the unit turn on the main power switch...

Page 13: ...H ADAPTOR FOR WIRING RyC RyF MAGNETIC RELAY RyH MAGNETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTO...

Page 14: ...NOTES NOTES...

Page 15: ...4 2 1 13 13 2 2 1 14 14 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 4 5 3 1 16 16 IN D OUT D F1 F2 F1...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25083 1C...

Reviews: