background image

 

Installation and operation manual

7

FXSQ20~125M8V3B

VRV System air conditioners

4PW25083-1C

PRECAUTIONS

A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.

For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.

Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.

F

IELD

 

SETTING

Field setting must be made on the remote controller in function of the
installation condition.

Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".

For setting and operation, refer to the "Field settings" in the
installation manual of the remote controller.

Summary of field settings

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB".

MAIN/SUB CHANGEOVER

Insert a wedge-head screwdriver into the recess between the
upper and lower part of the remote controller and, working from
the 2 positions, pry off the upper part. 

(See figure 15)

(The remote controller PC board is attached to the upper part of
the remote controller.)

Turn the main/sub changeover switch on one of the two remote
controller PC boards to "S". 

(See figure 20)

(Leave the switch of the other remote controller set to "M".)

Computerised control (forced off and on/off operation)

1

Wire specifications and how to perform wiring

-

Connect input from outside to terminals T1 and T2 of the 
terminal board (remote controller to transmission wiring).

(See figure 18)

2

Actuation

-

The following table explains "forced off" and "on/off 
operations" in response to input A.

3

How to select forced off and on/off operation

-

Turn the power on and then use the remote controller to 
select operation.

-

Set the remote controller to the field set mode. For details, 
refer to the chapter "How to set in the field", in the remote 
controller manual.

-

When in the field set mode, select mode No. 12, then set the 
first code No. to "1". Then set second code (position) No. to 
"01" for forced off and to "02" for on/off operation. (forced off 
at factory set.) 

(See figure 21)

Centralized control

For centralized control, it is necessary to designate the group No. For
details, refer to the manual of each optional controller for centralized
control.

I

NSTALLATION

 

OF

 

THE

 

DECORATION

 

PANEL

Refer to the installation manual attached to the decoration panel.

After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel.

Mode 

No.

(Note 1)

First 

code 

No.

Description of setting

Second code No. (Note 2)

01

02

03

04

10 

(20)

0

Filter contamination 
- Heavy/Light
= Setting to define 
time between 2 filter 
cleaning display 
indications. (When 
contamination is 
high, setting can be 
changed to half the 
time inbetween 2 
filter cleaning 
display indications.)

Ultra-long-
life filter

Light

±10,000 hrs.

Hea

vy

±5,000 hrs.

Long-life 
filter

±2,500 hrs.

±1,250 hrs.

Standard 
filter

±200 hrs.

±100 hrs.

2

Thermostat sensor selection

Use both the 
unit sensor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. 
(See note 5+6)

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 5+6)

Use remote 
controller 
sensor only. 
(See note 5+6)

3

Setting for display of time 
between 2 filter cleaning display 
indications

Display

Do not display

6

Thermostat sensor in group 
control

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 6)

Use both the 
unit senor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. (See 
note 4+5+6)

12 

(22)

0

Output signal X1-X2 of the 
optional KRP1B PCB kit

Thermostat-on + 
compressor run

Operation

Mal-
function

1

ON/OFF input from outside 
(T1/T2 input) = Setting when 
forced ON/OFF is to be 
operated from outside.

Forced OFF

ON/OFF
operation

3

Fan setting during thermostat 
OFF at heating operation

LL

Set speed

OFF 
(See note 3)

4

Differential automatic 
changeover

0°C

1°C

2°C

3°C
(See 
note 7)

5

Auto-restart after power failure

Disabled

Enabled

9

Fixed cool/heat master

Disabled

Enabled

13 

(23)

6

Setting the external static 
pressure 
(To be set in function of the 
connected duct resistance)

Normal

High static 
pressure

Low static 
pressure

15 

(25)

3

Drain pump ope 
humidifier interlock

Equipped

Not equipped

Note 1 : Setting is carried out in the group mode, however, if the mode number inside parentheses is selected, 

indoor units can also be set individually.

Note 2 : Factory settings of the Second code No. are marked in grey backgrounds.
Note 3 : Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Note 4 : If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.
Note 5 : If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01, 

10-2-02 or 10-2-03 have priority.

Note 6 : If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group 

connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have 
priority.

Note 7 : More settings for Differential automatic change over temperatures are:

Second code No.

05

4°C

06

5°C

07

6°C

08

7°C

1

Remote controller PC board

2

Factory setting

3

Only one remote controller needs to be changed

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75-1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum 
applicable load of 15 V DC, 10 mA

1

Input A

Forced off

on/off operation

Input "on" stops operation 

input off 

 on: turns on the unit 

(impossible by remote controllers)

Input "off" enables control 

input on 

 off: turns off the unit by remote 

controller

1

Second code No.

2

Mode No.

3

First code No.

4

Field set mode

Summary of Contents for FXSQ100M8V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXSQ20M8V3B FXSQ25M8V3B FXSQ32M8V3B FXSQ40M8V3B FXSQ50M8V3B FXSQ63M8V3B FXSQ80M8V3B FXSQ100M8V3B FXSQ125M8V3B System air conditioners...

Page 2: ...2 5 6 7 4 3 4 4 1 3 2 4 5 5 5 2 1 2 3 6a 6a 2 3 1 4 680 85 6b 6b 1 3 2 4 6 5 50 200 45 680 6c 6c 1 5 2 3 7 4 680 65 3 3 1 4 3 4 2 800 630 B A 145 7c 7c 4 2 2 3 1 460 180 350 A 8 8 1 1 5m 0 625mm 2 6...

Page 3: ...e z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 s...

Page 4: ...air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the installation site use the supplied paper...

Page 5: ...nerated even if 1 meter is kept 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If there is a risk reinforce the ceiling bef...

Page 6: ...The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details Attach the paper pattern for installation to the unit with the attached scre...

Page 7: ...ee figure 8 Connect the drain hose to the drain raising pipes and insulate them Connect the drain hose to the drain pipe on the indoor unit and tighten it with the metal clamp To ensure a downward slo...

Page 8: ...matched the system may cause a malfunction Electrical characteristics MCA Min circuit Amps A MFA Max Fuse Amps A KW Fan Motor Rated Output kW FLA Full Load Amps A Specifications for field supplied fus...

Page 9: ...he remote controller 6 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 7 Use only specified wires and tightly connect wi...

Page 10: ...to define time between 2 filter cleaning display indications When contamination is high setting can be changed to half the time inbetween 2 filter cleaning display indications Ultra long life filter L...

Page 11: ...esent unhook the chains 2 Remove the air filters Remove the air filters by pulling their cloth upward rear suction or backward bottom suction 3 Clean the air filter Use vacuum cleaner A or wash the ai...

Page 12: ...fter cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel display lights when the power is turned on To protect the unit turn on the main power switch...

Page 13: ...H ADAPTOR FOR WIRING RyC RyF MAGNETIC RELAY RyH MAGNETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTO...

Page 14: ...NOTES NOTES...

Page 15: ...4 2 1 13 13 2 2 1 14 14 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 4 5 3 1 16 16 IN D OUT D F1 F2 F1...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25083 1C...

Reviews: