background image

FXSQ20~125M8V3B
VRV System air conditioners
4PW25083-1C

Installation and operation manual

2

For the following items, take special care during 
construction and check after installation is finished

Notes to the installer

Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the system
and show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.

I

MPORTANT

 

INFORMATION

 

REGARDING

 

THE

 

REFRIGERANT

 

USED

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

(1)

 GWP = global warming potential

Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.

S

ELECTING

 

INSTALLATION

 

SITE

(See 

figure 1

 and 

figure 2

)

1

Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.

-

Where optimum air distribution can be ensured.

-

Where nothing blocks air passage.

-

Where condensate water can be properly drained.

-

Where the false ceiling is not noticeably on an incline.

-

Where sufficient clearance for maintenance and service can 
be ensured.

-

Where piping between indoor and outdoor units is possible 
within the allowable limit. (Refer to the installation manual of 
the outdoor unit.)

-

This is a class A product. In a domestic environment this 
product may cause radio interference in which case the user 
may be required to take adequate measures.

-

Keep indoor unit, outdoor unit, power supply wiring and 
transmission wiring at least 1 meter away from televisions 
and radios. This is to prevent image interference and noise in 
those electrical appliances. (Noise may be generated 
depending on the conditions under which the electric wave is 
generated, even if 1 meter is kept.)

2

Use suspension bolts for installation. Check whether the ceiling
is strong enough to support the weight of the indoor unit. If there
is a risk, reinforce the ceiling before installing the unit.

P

REPARATIONS

 

BEFORE

 

INSTALLATION

1

Relation of ceiling opening to unit and suspension bolt position.

(See figure 3)

For installation, choose one of the possibilities as listed further.

Standard rear suction 

(See figure 6a)

Installation with rear duct and duct service opening 

(See 

figure 6b)

Installation with rear duct, no duct service opening 

(See 

figure 6c)

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 
name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 
outdoor units?

It may result in insufficient cooling.

Are refrigerant piping length and additional refrigerant charge 
noted down?

The refrigerant charge in the system might not be clear.

Are the air filters fixed properly (when installing with rear duct)?

Maintenance of the air filters can be impossible.

1

Service space 

300

2

Drain pipe

3

Power supply wiring port

4

Transmission wiring port

5

Maintenance drain outlet

6

Gas pipe

7

Liquid pipe

Model

A

B

FXSQ20~32

550

600

50

700

750

FXSQ63

1000

1050

FXSQ80~125

1400

1450

1

Indoor unit

2

Pipe

3

Suspension bolt pitch (x4)

4

Suspension bolt pitch distance

1

Ceiling surface

2

Ceiling opening

3

Service access panel (optional accessory)

4

Air filter

5

Air inlet duct

6

Duct service opening

7

Interchangeable plate

NOTE

Before installation of the unit (in case of installation
with duct, but no duct service opening): modify the
position of the air filters.

Summary of Contents for FXSQ100M8V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXSQ20M8V3B FXSQ25M8V3B FXSQ32M8V3B FXSQ40M8V3B FXSQ50M8V3B FXSQ63M8V3B FXSQ80M8V3B FXSQ100M8V3B FXSQ125M8V3B System air conditioners...

Page 2: ...2 5 6 7 4 3 4 4 1 3 2 4 5 5 5 2 1 2 3 6a 6a 2 3 1 4 680 85 6b 6b 1 3 2 4 6 5 50 200 45 680 6c 6c 1 5 2 3 7 4 680 65 3 3 1 4 3 4 2 800 630 B A 145 7c 7c 4 2 2 3 1 460 180 350 A 8 8 1 1 5m 0 625mm 2 6...

Page 3: ...e z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 s...

Page 4: ...air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the installation site use the supplied paper...

Page 5: ...nerated even if 1 meter is kept 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the indoor unit If there is a risk reinforce the ceiling bef...

Page 6: ...The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details Attach the paper pattern for installation to the unit with the attached scre...

Page 7: ...ee figure 8 Connect the drain hose to the drain raising pipes and insulate them Connect the drain hose to the drain pipe on the indoor unit and tighten it with the metal clamp To ensure a downward slo...

Page 8: ...matched the system may cause a malfunction Electrical characteristics MCA Min circuit Amps A MFA Max Fuse Amps A KW Fan Motor Rated Output kW FLA Full Load Amps A Specifications for field supplied fus...

Page 9: ...he remote controller 6 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 7 Use only specified wires and tightly connect wi...

Page 10: ...to define time between 2 filter cleaning display indications When contamination is high setting can be changed to half the time inbetween 2 filter cleaning display indications Ultra long life filter L...

Page 11: ...esent unhook the chains 2 Remove the air filters Remove the air filters by pulling their cloth upward rear suction or backward bottom suction 3 Clean the air filter Use vacuum cleaner A or wash the ai...

Page 12: ...fter cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel display lights when the power is turned on To protect the unit turn on the main power switch...

Page 13: ...H ADAPTOR FOR WIRING RyC RyF MAGNETIC RELAY RyH MAGNETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTO...

Page 14: ...NOTES NOTES...

Page 15: ...4 2 1 13 13 2 2 1 14 14 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 4 5 3 1 16 16 IN D OUT D F1 F2 F1...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25083 1C...