FXSQ20~125M7V1B
VRV System air conditioner
4PW15110-1

Installation and operation manual

3

Bottom suction 

(See figure 7a)

Mounting the air inlet panel with a canvas connection 

(See

figure 7b)

Mounting the air inlet panel directly 

(See figure 7c)

This is to protect the air filter from damage during maintenance of the
filter.

For other installation than standard installation, contact your Daikin
dealer for details.

2

The fan speed for this indoor unit is preset to provide standard
external static pressure.

If higher or lower external static pressure is required, reset the external
static pressure by repositioning the adaptors of the PC-board.
Refer to 

"Setting of static pressure changeover connector" on

page 6

.

3

Install the suspension bolts.

(Use M10 size bolt for the suspension bolt.) Use anchors for
existing ceilings, and a sunken insert, sunken anchors or other
field supplied parts for new ceilings to reinforce the ceiling in
order to bear the weight of the unit.

Installation example 

(See figure 4)

I

NDOOR UNIT INSTALLATION

When installing optional accessories (except for the air inlet panel),
read also the installation manual of the optional accessories.
Depending on the field conditions, it may be easier to install optional
accessories before the indoor unit is installed.

1

Install the indoor unit temporarily.

-

Attach the hanger bracket to the suspension bolt. Be sure to 
fix it securely by using a nut and washer from the upper and 
lower sides of the hanger bracket. 

(See figure 5)

2

Check if the unit is horizontally levelled.

-

Do not install the unit tilted. The indoor unit is equipped with a 
built-in drain pump and float switch. (If the unit is tilted 
against condensate flow, the float switch may malfunction 
and cause water to drip.)

-

Check if the unit is levelled at all four corners with a water 
level or a water-filled vinyl tube as shown in 

figure 13

.

3

Tighten the upper nut.

4

Fix the paper pattern for installation.

-

The paper pattern for installation corresponds with the 
measurements of the ceiling opening. Consult the builder for 
details.

-

Attach the paper pattern for installation to the unit with the 
attached screws as shown in 

figure 17

.

The paper pattern for installation is marked for 3 types of 
ceiling openings. Read the notations carefully when 
installing.

R

EFRIGERANT PIPING WORK

For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.

Before rigging tubes, check which type of refrigerant is used. 

Use a pipe cutter and flare suitable for the used refrigerant.

Apply ether oil or ester oil around the flare portions before
connecting.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

The outdoor unit is charged with refrigerant.

NOTE

The unit can be used with bottom suction by replacing
the interchangeable plate by the air filter holding plate.

1

Air filter holding plate with air filter(s)

2

Interchangeable plate

3

Small bottom plate

1

Ceiling surface

2

Ceiling opening

3

Air inlet panel (Optional accessory)

4

Indoor unit (Back side)

5

Canvas connection for air inlet panel (Optional accessory)

Model

A

FXSQ20•25•32

610

FXSQ40•50

760

FXSQ63

1060

FXSQ80•100•125

1460

NOTE

When installing an air inlet duct, select fixing screws
that shall stick out maximum 5 mm at the inside of the
flange.

1

Air inlet duct

2

Inside of the flange

3

Fixing screw

1

2

3

5 mm

1

Anchor

2

Ceiling slab

3

Long nut or turn-buckle

4

Suspension bolt

5

Indoor unit

NOTE

All the above parts are field supplied.

1

Nut (field supply)

2

Washer for hanger bracket (supplied with the unit)

3

Tighten (double nut)

1

Water level

2

Vinyl tube

1

Paper pattern for installation (supplied with the unit)

2

Screws for fixing the paper pattern for installation (supplied with 
the unit (6))

NOTE

All field piping must be provided by a licensed
refrigeration technician and must comply with the
relevant local and national codes.

Summary of Contents for FXSQ100M7V1B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXSQ20M7V1B FXSQ25M7V1B FXSQ32M7V1B FXSQ40M7V1B FXSQ50M7V1B FXSQ63M7V1B FXSQ80M7V1B FXSQ100M7V1B FXSQ125M7V1B System air conditioner ...

Page 2: ...2 2 5 6 7 4 3 4 4 1 3 2 4 5 5 5 2 1 2 3 6a 6a 2 3 1 4 680 85 6b 6b 1 3 2 4 6 5 50 200 45 680 6c 6c 1 5 2 3 7 4 680 65 3 3 1 4 3 4 2 800 630 B A 145 7c 7c 4 2 2 3 1 460 180 350 A 8 8 1 1 5m 0 625mm 2 6 1 5 4 A 3 9 9 1 100mm 7a 7a 1 3 2 2 1 3 10 10 3 2 1 6 5 4 ...

Page 3: ... 4 2 1 13 13 2 2 1 14 14 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 4 5 3 1 16 16 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 20 20 S M S S M 1 2 3 19 19 1 2 5 6 3 4 7 8 9 15 15 21 21 SETTING 2 1 4 3 11c 11c 5 4 1 3 2 18 18 F2 T1 T2 FO...

Page 4: ...r följande standard er eller andra normgivande dokument under förutsättning att användning sker i överensstämmelse med våra instruktioner respektive utstyr er i overensstemmelse med følgende standard er eller andre normgivende dokument er under forutssetning av at disse brukes i henhold til våre instrukser vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen...

Page 5: ...er pattern for installation Do not install accessories on the casing directly Drilling holes in the casing may damage electrical wires and consequently cause fire Accessories Check if the following accessories are included with your unit Screws for fixing panels are attached to the air inlet panel Optional accessories There are two types of remote controllers wired and wireless Select a remote contr...

Page 6: ...choose one of the possibilities as listed further Standard rear suction See figure 6a Installation with rear duct and duct service opening See figure 6b Installation with rear duct no duct service opening See figure 6c Tick when checked Is the indoor unit fixed firmly The unit may drop vibrate or make noise Is the gas leak test finished It may result in insufficient cooling Is the unit fully insulated Co...

Page 7: ...13 3 Tighten the upper nut 4 Fix the paper pattern for installation The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details Attach the paper pattern for installation to the unit with the attached screws as shown in figure 17 The paper pattern for installation is marked for 3 types of ceiling openings Read the notations carefully wh...

Page 8: ...nd insulate them Connect the drain hose to the drain pipe on the indoor unit and tighten it with the metal clamp To ensure a downward slope of 1 100 install hanging bars every 1 to 1 5 m If unifying multiple drain pipes install the pipes as shown in figure 9 2 After piping work is finished check if drainage flows smoothly Open the water inlet lid add approximately 1 l of water gradually and check the...

Page 9: ...hed the system may cause a malfunction Electrical characteristics MCA Min circuit Amps A MFA Max Fuse Amps A KW Fan Motor Rated Output kW FLA Full Load Amps A Specifications for field supplied fuses and wire Allowable length of transmission wiring between indoor and outdoor units and between the indoor unit and the remote controller is as follows 1 Outdoor unit indoor unit max 1000 m total wiring le...

Page 10: ...er to the Installation manual of the remote controller supplied with the remote controller 6 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 7 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that they do ...

Page 11: ...hen set the first code No to 1 Then set second code position No to 01 for forced off and to 02 for on off operation forced off at factory set See figure 21 Centralized control For centralized control it is necessary to designate the group No For details refer to the manual of each optional controller for centralized control INSTALLATION OF THE DECORATION PANEL Refer to the installation manual attach...

Page 12: ...he shade 4 Fix the air filter Align the two hanger brackets and push the two clips in their place pull the cloth if necessary Confirm that four hangers are fixed 5 Shut the air inlet grille Only for bottom suction Refer to item no 1 6 After turning on the power press FILTER SIGN RESET button The TIME TO CLEAN AIR FILTER display is turned off Caution Only a qualified service person is allowed to perfor...

Page 13: ... the unit turn on the main power switch at least 6 hours before operation What to do when stopping the system for a long period Turn on FAN OPERATION for half a day and dry the unit Refer to the operation manual of the outdoor unit Cut off the power supply When the main power switch is turned on some wattage is being consumed even if the system is not operating The remote controller display is tur...

Page 14: ...H ADAPTOR FOR WIRING RyC RyF MAGNETIC RELAY RyH MAGNETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTOR X18A CONNECTOR WIRING ADAPTOR FOR ELECTRICAL APPENDICES FIELD WIRING BLK BLACK TERMINAL BLU BLUE CONNECTOR ORG ORANGE WIRE CLAMP PNK PINK PROTECTIVE EARTH SCREW RED RED WHT WHITE YLW YELLOW RECEIVER...

Page 15: ...NOTES NOTES ...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN15110 1 ...

Reviews: