background image

Installation and operation manual

4

FXSQ20~125M7V1B

VRV System air conditioner

4PW15110-1

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Refer to 

Table 1

for the dimensions of flare nut spaces and the

appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)

Table 1

When connecting the flare nut, coat the flare both inside and
outside with ether oil or ester oil and initially tighten by hand 3 or
4 turns before tightening firmly.

Check the pipe connector for gas leaks, then insulate it.

D

RAIN PIPING WORK

Rig the drain piping as shown in the figure and take measures
against condensation. Improperly rigged piping could lead to leaks
and eventually wet furniture and belongings.

1

Install the drain pipes.

-

Keep piping as short as possible and slope it downwards so 
that air may not remain trapped inside the pipe.

-

Keep pipe size equal to or greater than that of the connecting 
pipe (vinyl pipe of 25 mm nominal diameter and 32 mm outer 
diameter).

-

Use the supplied drain hose and metal clamp. Tighten the 
clamp firmly.

Insulate the drain hose inside the building.

If the drain hose cannot be sufficiently set on a slope, fit the
hose with drain raising piping (field supply).

HOW TO PERFORM PIPING 

(See figure 8)

Connect the drain hose to the drain raising pipes, and insulate
them.

Connect the drain hose to the drain pipe on the indoor unit, and
tighten it with the metal clamp.

-

To ensure a downward slope of 1:100, install hanging bars 
every 1 to 1.5 m.

-

If unifying multiple drain pipes, install the pipes as shown in 

figure 9

.

2

After piping work is finished, check if drainage flows smoothly.

-

Open the water inlet lid, add approximately 1 l of water 
gradually and check the drainage flow. 

(See figure 10)

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

Pipe

gauge

Tightening torque

Flare dimension 

A (mm)

Flare shape

Ø6.4

14.2~17.2 N•m 

(144~176 kgf•cm)

8.7~9.1

Ø9.5

32.7~39.9 N•m 

(333~407 kgf•cm)

12.8~13.2

Ø12.7

49.5~60.3 N•m 

(504~616 kgf•cm)

16.2~16.6

Ø15.9

61.8~75.4 N•m 

(630~770 kgf•cm)

19.3~19.7

Coat here with ether oil 
or ester oil

1

Liquid pipe

2

Gas pipe

3

Insulation for fitting of liquid 
line (supplied with the unit)

4

Insulation for fitting of gas 
line (supplied with the unit)

5

Clamps (use 2 clamps per 
insulation)

2

3

1

4

R=0.4~0.8

45

° ±

2

90

°±

4

A

5

3

1

2

4

1

Hanging bar

1

Metal clamp

2

Drain hose

3

White tape (field 
supply)

1

Ceiling slab

2

Hanging bar

3

Adjustable range

4

Drain hose (supplied with the unit)

5

Metal clamp (supplied with the unit)

6

Drain raising pipe (field supply)

Installation

A

Rear suction installation

275

When canvas duct is installed

350-530

When air inlet panel is directly installed

275

1

Multiple drain piping

1

Water inlet

2

Portable pump

3

Water inlet lid

4

Bucket (adding water from water inlet)

5

Drain outlet for maintenance (with rubber drain plug)

6

Refrigerant pipes

1-1.5 m

1

2

1

3

Summary of Contents for FXSQ100M7V1B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXSQ20M7V1B FXSQ25M7V1B FXSQ32M7V1B FXSQ40M7V1B FXSQ50M7V1B FXSQ63M7V1B FXSQ80M7V1B FXSQ100M7V1B FXSQ125M7V1B System air conditioner ...

Page 2: ...2 2 5 6 7 4 3 4 4 1 3 2 4 5 5 5 2 1 2 3 6a 6a 2 3 1 4 680 85 6b 6b 1 3 2 4 6 5 50 200 45 680 6c 6c 1 5 2 3 7 4 680 65 3 3 1 4 3 4 2 800 630 B A 145 7c 7c 4 2 2 3 1 460 180 350 A 8 8 1 1 5m 0 625mm 2 6 1 5 4 A 3 9 9 1 100mm 7a 7a 1 3 2 2 1 3 10 10 3 2 1 6 5 4 ...

Page 3: ... 4 2 1 13 13 2 2 1 14 14 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 4 5 3 1 16 16 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 20 20 S M S S M 1 2 3 19 19 1 2 5 6 3 4 7 8 9 15 15 21 21 SETTING 2 1 4 3 11c 11c 5 4 1 3 2 18 18 F2 T1 T2 FO...

Page 4: ...r följande standard er eller andra normgivande dokument under förutsättning att användning sker i överensstämmelse med våra instruktioner respektive utstyr er i overensstemmelse med følgende standard er eller andre normgivende dokument er under forutssetning av at disse brukes i henhold til våre instrukser vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen...

Page 5: ...er pattern for installation Do not install accessories on the casing directly Drilling holes in the casing may damage electrical wires and consequently cause fire Accessories Check if the following accessories are included with your unit Screws for fixing panels are attached to the air inlet panel Optional accessories There are two types of remote controllers wired and wireless Select a remote contr...

Page 6: ...choose one of the possibilities as listed further Standard rear suction See figure 6a Installation with rear duct and duct service opening See figure 6b Installation with rear duct no duct service opening See figure 6c Tick when checked Is the indoor unit fixed firmly The unit may drop vibrate or make noise Is the gas leak test finished It may result in insufficient cooling Is the unit fully insulated Co...

Page 7: ...13 3 Tighten the upper nut 4 Fix the paper pattern for installation The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details Attach the paper pattern for installation to the unit with the attached screws as shown in figure 17 The paper pattern for installation is marked for 3 types of ceiling openings Read the notations carefully wh...

Page 8: ...nd insulate them Connect the drain hose to the drain pipe on the indoor unit and tighten it with the metal clamp To ensure a downward slope of 1 100 install hanging bars every 1 to 1 5 m If unifying multiple drain pipes install the pipes as shown in figure 9 2 After piping work is finished check if drainage flows smoothly Open the water inlet lid add approximately 1 l of water gradually and check the...

Page 9: ...hed the system may cause a malfunction Electrical characteristics MCA Min circuit Amps A MFA Max Fuse Amps A KW Fan Motor Rated Output kW FLA Full Load Amps A Specifications for field supplied fuses and wire Allowable length of transmission wiring between indoor and outdoor units and between the indoor unit and the remote controller is as follows 1 Outdoor unit indoor unit max 1000 m total wiring le...

Page 10: ...er to the Installation manual of the remote controller supplied with the remote controller 6 Never connect the power supply wiring to the terminal board for transmission wiring This mistake could damage the entire system 7 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that they do ...

Page 11: ...hen set the first code No to 1 Then set second code position No to 01 for forced off and to 02 for on off operation forced off at factory set See figure 21 Centralized control For centralized control it is necessary to designate the group No For details refer to the manual of each optional controller for centralized control INSTALLATION OF THE DECORATION PANEL Refer to the installation manual attach...

Page 12: ...he shade 4 Fix the air filter Align the two hanger brackets and push the two clips in their place pull the cloth if necessary Confirm that four hangers are fixed 5 Shut the air inlet grille Only for bottom suction Refer to item no 1 6 After turning on the power press FILTER SIGN RESET button The TIME TO CLEAN AIR FILTER display is turned off Caution Only a qualified service person is allowed to perfor...

Page 13: ... the unit turn on the main power switch at least 6 hours before operation What to do when stopping the system for a long period Turn on FAN OPERATION for half a day and dry the unit Refer to the operation manual of the outdoor unit Cut off the power supply When the main power switch is turned on some wattage is being consumed even if the system is not operating The remote controller display is tur...

Page 14: ...H ADAPTOR FOR WIRING RyC RyF MAGNETIC RELAY RyH MAGNETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTOR X18A CONNECTOR WIRING ADAPTOR FOR ELECTRICAL APPENDICES FIELD WIRING BLK BLACK TERMINAL BLU BLUE CONNECTOR ORG ORANGE WIRE CLAMP PNK PINK PROTECTIVE EARTH SCREW RED RED WHT WHITE YLW YELLOW RECEIVER...

Page 15: ...NOTES NOTES ...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN15110 1 ...

Reviews: