background image

FXSQ-PAVE EDFMT391737

60

3P432203-4B

15 

(3)  Make settings to adjust the air volume automatically. 

After setting the operating mode to “Fan”, set the air con-
ditioner to 

 setting mode with the operation of the air

conditioner stopped. Select Mode No. [21] (11 in the case 
of batch settings), select FIRST CODE No. “7”, and set the 
SECOND CODE No. to “03”. 

Return to the “Basic screen” (“Normal mode” if a wireless 

remote controller is used), and press the ON/OFF button. 

The operation lamp is lit, and the indoor unit will go into fan 

operation for air volume automatic adjustments (at which 

time, do not adjust the opening of the air outlet or inlet). 

The air volume adjustments will automatically terminate 

approximately 1 to 15 minutes after the indoor unit comes 

into operation, and the operation lamp will be OFF and the 

indoor unit will come to a stop.

Table 7

Mode No.

FIRST 
CODE 

No.

Setting 

content

SECOND CODE No.

01

02

03

11 (21)

7

Air volume 

adjust-

ment

OFF

Air volume 

adjust-

ment 

completion

Air volume 

adjust-

ment start

(4)  After the air conditioner comes to a stop, be sure to check 

with Mode No. [21] per indoor unit that the above SECOND 
CODE No. is “02”. If the operation of the air conditioner 
does not stop automatically or the SECOND CODE No. is 
not set to “02”, repeat the setting procedure from (3).

 CAUTION

• 

If 

airfl

ow pathway changes, such as duct and air outlet 

changes, are made after air volume adjustments, be sure to 
make “Air volume automatic adjustment” again.

• 

If 

airfl

ow pathway changes, such as duct and air outlet 

changes, are made after 

11. TEST OPERATION or air 

conditioner relocation, contact your dealer.

(b) Select external static pressure with the remote controller.

Check with Mode No. [21] per indoor unit that the SECOND CODE 

No. for the above “Air volume adjustment” is set to “01” (OFF). 

(The SECOND CODE No. is factory set to “01” (OFF).) 

Change the SECOND CODE No. by referring to the table below 

according to the external static pressure of the duct to be 

connected.
Table 8
In case of 20-125 class

External static 

pressure

Mode No.

FIRST  

CODE No.

SECOND 

CODE No.

30Pa (*1)

13(23)

6

03

40Pa (*1)

04

50Pa

05

60Pa

06

70Pa

07

80Pa

08

90Pa

09

100Pa

10

110Pa

11

120Pa

12

130Pa

13

140Pa

14

150Pa

15

(*1) The FXSQ50-125 class cannot be set to 30Pa or 40Pa.

10. FIELD SETTING

 CAUTION

Before carrying out 

field

 setting, check the items mentioned in  

(1) Items to be checked after the installation work is 

completed on page 3.

• 

Check if all the installation and piping works for the air 
conditioner are completed.

• 

Check that the outside panel and piping cover of the indoor 
and outdoor units  are closed.

< FIELD SETTING >

After turning on the power supply, carry out 

field

 setting 

from the remote controller according to the installation 

state.

• 

Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.” 
and “SECOND CODE No.”. 
The settings shown by 

 in the following tables indicate 

those when shipped from the factory.

• 

The method of setting procedure and operation is shown in 
the installation manual attached to the remote controller.
(Note)  Though setting of “Mode No.” is carried out as a group, 

if you intend to carry out individual setting by each 
indoor  unit  or 

confi

rmation  after  setting,  carry  out 

setting with the Mode No. shown in the paren thesis ( ). 

  Ask your customer to keep the manual attached to the remote 

controller together with the operation manual.

• 

Do not carry out settings other than those shown in the table.

• 

Settings are performed by selecting “Mode No.”, “FIRST 
CODE No.”, and “SECOND CODE No.”.

10-1 Settings for external static pressure

• 

Make settings in either method (a) or method (b).
(a) Make settings with Air volume automatic adjustment 

function.
“Air volume automatic adjustment” function: The air volume 
is adjusted to the rated air volume automatically.

 CAUTION

• 

Be sure to check that the external static pressure is within 
the 

specification

 range before making settings. The external 

static pressure will not be automatically adjusted and air 
volume 

insufficiency

 or water leakage may result if the 

external static pressure is outside the range. (Refer to the 
technical document for the setting range of external static 
pressure.)

(1)  Check that the electrical wiring and duct work have been 

completed.  
(If the closing damper is set midway, be sure to check that 
the damper is opened. Furthermore, check that the air 
passage on the suction side is provided with an air 

filter 

(field

 supply)).

(2)  If air conditioner has more than one air outlet and air inlet, 

be sure to make adjustments so that the air volume ratio of 
each air outlet and the corresponding air inlet will conform 
to the designed air volume ratio. 
In that case, set the operating mode to “Fan”. (In the case 
of changing the air volume, press the fan speed button on 
the remote controller and change the current selection to 
“High”, “Medium”, or “Low”.)

In case of 140 class

External static 

pressure

Mode No.

FIRST  

CODE No.

SECOND 

CODE No.

50Pa

13(23)

6

05

60Pa

06

70Pa

07

80Pa

08

90Pa

09

100Pa

10

110Pa

11

120Pa

12

130Pa

13

140Pa

14

Summary of Contents for FXSQ-PAVE

Page 1: ...FXSQ PAVE EDFMT391737 201709 Engineering Data 50 60 Hz...

Page 2: ......

Page 3: ...Safety Devices Setting 17 8 Capacity Tables 18 8 1 Cooling Capacity for Te Auto 18 8 2 Cooling Capacity for Te 6 C 18 8 3 Cooling Capacity for Te 9 C 19 8 4 Heating Capacity 19 9 Fan Performances 20 1...

Page 4: ...5 40 50 62 5 80 100 125 140 FXSQ 20PAVE 25PAVE 32PAVE 40PAVE 50PAVE 63PAVE 80PAVE 100PAVE 125PAVE 140PAVE FXSQ for Thailand 20PAVS 25PAVS 32PAVS 40PAVS 50PAVS 63PAVS 80PAVS 100PAVS 125PAVS 140PAVS FXS...

Page 5: ...expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange Operati...

Page 6: ...ion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange Operation man...

Page 7: ...xpansion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange Operatio...

Page 8: ...c expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange Opera...

Page 9: ...tronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange...

Page 10: ...FXSQ PAVE EDFMT391737 8 3 Dimensions FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE 3D095725B Unit mm...

Page 11: ...FXSQ PAVE EDFMT391737 9 FXSQ40PAVE 3D095726B Unit mm...

Page 12: ...FXSQ PAVE EDFMT391737 10 FXSQ50PAVE 3D096164B Unit mm...

Page 13: ...FXSQ PAVE EDFMT391737 11 FXSQ63PAVE FXSQ80PAVE 3D095426D Unit mm...

Page 14: ...FXSQ PAVE EDFMT391737 12 FXSQ100PAVE FXSQ125PAVE 3D095427D Unit mm...

Page 15: ...FXSQ PAVE EDFMT391737 13 FXSQ140PAVE 3D095727C Unit mm...

Page 16: ...PAVE FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE 12...

Page 17: ...FXSQ PAVE EDFMT391737 15 5 Wiring Diagrams FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE 3D092752C...

Page 18: ...FXSQ PAVE EDFMT391737 16 6 Electric Characteristics FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE 4D105290...

Page 19: ...V 6 3 A Drain pump thermal fuse C Model FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE Printed circuit board fuse 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A Printed circuit board fuse Fan drive...

Page 20: ...length Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 1...

Page 21: ...8 TC Total capacity kW SHC Sensible heat capacity kW Notes 1 These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the sel...

Page 22: ...FXSQ PAVE EDFMT391737 20 9 Fan Performances FXSQ20PAVE FXSQ25PAVE 3D095855A...

Page 23: ...FXSQ PAVE EDFMT391737 21 FXSQ32PAVE 3D095856A...

Page 24: ...FXSQ PAVE EDFMT391737 22 FXSQ40PAVE 3D095857A...

Page 25: ...FXSQ PAVE EDFMT391737 23 FXSQ50PAVE 3D095858A...

Page 26: ...FXSQ PAVE EDFMT391737 24 FXSQ63PAVE 3D095859A...

Page 27: ...FXSQ PAVE EDFMT391737 25 FXSQ80PAVE 3D095860A...

Page 28: ...FXSQ PAVE EDFMT391737 26 FXSQ100PAVE 3D095861A...

Page 29: ...FXSQ PAVE EDFMT391737 27 FXSQ125PAVE 3D095862A...

Page 30: ...FXSQ PAVE EDFMT391737 28 FXSQ140PAVE 3D095863A...

Page 31: ...FXSQ PAVE EDFMT391737 29 10 Airflow Auto Adjustment Characteristics FXSQ20PAVE FXSQ25PAVE 3D095846A...

Page 32: ...FXSQ PAVE EDFMT391737 30 FXSQ32PAVE 3D095847A...

Page 33: ...FXSQ PAVE EDFMT391737 31 FXSQ40PAVE 3D095848A...

Page 34: ...FXSQ PAVE EDFMT391737 32 FXSQ50PAVE 3D095849A...

Page 35: ...FXSQ PAVE EDFMT391737 33 FXSQ63PAVE 3D095850A...

Page 36: ...FXSQ PAVE EDFMT391737 34 FXSQ80PAVE 3D095851A...

Page 37: ...FXSQ PAVE EDFMT391737 35 FXSQ100PAVE 3D095852A...

Page 38: ...FXSQ PAVE EDFMT391737 36 FXSQ125PAVE 3D095853A...

Page 39: ...FXSQ PAVE EDFMT391737 37 FXSQ140PAVE 3D095854A...

Page 40: ...FXSQ PAVE EDFMT391737 38 11 Sound Levels FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE 4D095804B 4D095805B...

Page 41: ...FXSQ PAVE EDFMT391737 39 FXSQ40PAVE FXSQ50PAVE 4D095806B 4D095807B...

Page 42: ...FXSQ PAVE EDFMT391737 40 FXSQ63PAVE FXSQ80PAVE 4D095808B 4D095809B...

Page 43: ...FXSQ PAVE EDFMT391737 41 FXSQ100PAVE FXSQ125PAVE 4D095810B 4D095811B...

Page 44: ...FXSQ PAVE EDFMT391737 42 FXSQ140PAVE 4D095812B...

Page 45: ...FXSQ PAVE EDFMT391737 43 12 Centre of Gravity FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE 4D095814B Unit mm...

Page 46: ...chamber for rear suction Note 1 KDDFP63B80 Long life replacement filter Note 1 KAFP631B80 Service panel White KTBJ25K80W Fresh white KTBJ25K80F Brown KTBJ25K80T Air discharge adapter KDAP25A71A Shiel...

Page 47: ...roller Wireless Cooling Only BRC4C66 Note 4 Heat Pump BRC4C65 Note 4 Wired BRC1C62 Note 4 Navigation remote controller Wired remote controller BRC1E62 Note 4 5 Simplified remote controller Exposed typ...

Page 48: ...our local dealer regarding what to do in case of refrigerant leakage When the air conditioner is installed in a small room it is necessary to take proper measures so that the amount of any leaked refr...

Page 49: ...ng of soft material or protective plates together with a rope when lifting to avoid damage or scratches to the indoor unit Have the customer actually operate the air conditioner while looking at the o...

Page 50: ...ts or inlets of the indoor and outdoor units blocked with obstacles It may lead to capacity drop due to fan speed drop or malfunction of equipment Does not cool Does not heat Is the external static pr...

Page 51: ...type lamp is installed If you set the fan speed at thermostat OFF did you explain the set fan speed to the customer Have you handed the operation manual and the installation manual to the customer Ha...

Page 52: ...ng framework reinforcement may be required in order to keep the ceiling horizontal and prevent ceiling vibration after opening the ceiling holes For details consult your building and upholstery work c...

Page 53: ...3 Check the level of the unit Refer to Fig 8 4 Remove the washer clamp 9 used for preventing the washer for hanger 11 from dropping and tighten the up per side nut Hanger Bottom of product Level Viny...

Page 54: ...t into the clearance between the hanger and the washer for hanger 11 Unless the washers are properly attached the hanging bolts may come off from the hanger WARNING The indoor unit must be securely in...

Page 55: ...t drainage is ensured Select the piping diameter equal to or larger than except for riser that of the connection piping polyvi nyl chloride piping nominal diameter 25 mm outside diameter 32 mm Install...

Page 56: ...up grade so that air may not stagnate in the drain hose If air stagnates the drain may ow oppositely when the drain pump stops and generate abnormal sound unit mm Fig 16 Downward inclination of 1 100...

Page 57: ...ghtened Wrap the sealing material Large 6 so that the metal clamp 1 end side may be doubled Metal clamp 1 accessory Drain hose 2 accessory Sealing material Large 6 accessory Sealing material Large 6 a...

Page 58: ...Q80PAVE 1 8 15 0 230 1 5 FXSQ100PAVE 2 5 15 0 300 2 0 FXSQ125PAVE 2 8 15 0 300 2 2 FXSQ140PAVE 3 1 15 0 350 2 5 8 DUCT WORK Pay the utmost attention to the following items and conduct the ductwork Che...

Page 59: ...WARNING When wiring form the wirings orderly so that the control box lid can be securely fastened If the control box lid is not in place the wirings may come out or be sandwiched by the box and the li...

Page 60: ...uctions below and perform wiring in the control box F2 T2 P1 P2 F1 T1 Securely x the wiring to the provided wiring xture with the clamp 8 Terminal block X1M for power supply wiring and earth wiring Co...

Page 61: ...ted In case of ON OFF OPERATION Operation Stop 3 How to choose FORCED OFF or ON OFF OPERATION For choosing FORCED OFF or ON OFF OPERATION setting by remote controller is required Refer to 10 FIELD SET...

Page 62: ...is completed on page 3 Check if all the installation and piping works for the air conditioner are completed Check that the outside panel and piping cover of the indoor and outdoor units are closed FIE...

Page 63: ...power supply wiring to the outdoor unit is not carried out The transmission wiring and the remote controller wiring and FORCED OFF wiring are connected wrongly The transmission wiring is disconnected...

Page 64: ......

Page 65: ......

Page 66: ......

Page 67: ......

Page 68: ...parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation...

Reviews: