![background image](http://html1.mh-extra.com/html/daikin/fxsq-pave/fxsq-pave_engineering-data_2460174062.webp)
FXSQ-PAVE EDFMT391737
60
3P432203-4B
15
(3) Make settings to adjust the air volume automatically.
After setting the operating mode to “Fan”, set the air con-
ditioner to
setting mode with the operation of the air
conditioner stopped. Select Mode No. [21] (11 in the case
of batch settings), select FIRST CODE No. “7”, and set the
SECOND CODE No. to “03”.
Return to the “Basic screen” (“Normal mode” if a wireless
remote controller is used), and press the ON/OFF button.
The operation lamp is lit, and the indoor unit will go into fan
operation for air volume automatic adjustments (at which
time, do not adjust the opening of the air outlet or inlet).
The air volume adjustments will automatically terminate
approximately 1 to 15 minutes after the indoor unit comes
into operation, and the operation lamp will be OFF and the
indoor unit will come to a stop.
Table 7
Mode No.
FIRST
CODE
No.
Setting
content
SECOND CODE No.
01
02
03
11 (21)
7
Air volume
adjust-
ment
OFF
Air volume
adjust-
ment
completion
Air volume
adjust-
ment start
(4) After the air conditioner comes to a stop, be sure to check
with Mode No. [21] per indoor unit that the above SECOND
CODE No. is “02”. If the operation of the air conditioner
does not stop automatically or the SECOND CODE No. is
not set to “02”, repeat the setting procedure from (3).
CAUTION
•
If
airfl
ow pathway changes, such as duct and air outlet
changes, are made after air volume adjustments, be sure to
make “Air volume automatic adjustment” again.
•
If
airfl
ow pathway changes, such as duct and air outlet
changes, are made after
11. TEST OPERATION or air
conditioner relocation, contact your dealer.
(b) Select external static pressure with the remote controller.
Check with Mode No. [21] per indoor unit that the SECOND CODE
No. for the above “Air volume adjustment” is set to “01” (OFF).
(The SECOND CODE No. is factory set to “01” (OFF).)
Change the SECOND CODE No. by referring to the table below
according to the external static pressure of the duct to be
connected.
Table 8
In case of 20-125 class
External static
pressure
Mode No.
FIRST
CODE No.
SECOND
CODE No.
30Pa (*1)
13(23)
6
03
40Pa (*1)
04
50Pa
05
60Pa
06
70Pa
07
80Pa
08
90Pa
09
100Pa
10
110Pa
11
120Pa
12
130Pa
13
140Pa
14
150Pa
15
(*1) The FXSQ50-125 class cannot be set to 30Pa or 40Pa.
10. FIELD SETTING
CAUTION
Before carrying out
field
setting, check the items mentioned in
(1) Items to be checked after the installation work is
completed on page 3.
•
Check if all the installation and piping works for the air
conditioner are completed.
•
Check that the outside panel and piping cover of the indoor
and outdoor units are closed.
< FIELD SETTING >
After turning on the power supply, carry out
field
setting
from the remote controller according to the installation
state.
•
Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.”
and “SECOND CODE No.”.
The settings shown by
in the following tables indicate
those when shipped from the factory.
•
The method of setting procedure and operation is shown in
the installation manual attached to the remote controller.
(Note) Though setting of “Mode No.” is carried out as a group,
if you intend to carry out individual setting by each
indoor unit or
confi
rmation after setting, carry out
setting with the Mode No. shown in the paren thesis ( ).
•
Ask your customer to keep the manual attached to the remote
controller together with the operation manual.
•
Do not carry out settings other than those shown in the table.
•
Settings are performed by selecting “Mode No.”, “FIRST
CODE No.”, and “SECOND CODE No.”.
10-1 Settings for external static pressure
•
Make settings in either method (a) or method (b).
(a) Make settings with Air volume automatic adjustment
function.
“Air volume automatic adjustment” function: The air volume
is adjusted to the rated air volume automatically.
CAUTION
•
Be sure to check that the external static pressure is within
the
specification
range before making settings. The external
static pressure will not be automatically adjusted and air
volume
insufficiency
or water leakage may result if the
external static pressure is outside the range. (Refer to the
technical document for the setting range of external static
pressure.)
(1) Check that the electrical wiring and duct work have been
completed.
(If the closing damper is set midway, be sure to check that
the damper is opened. Furthermore, check that the air
passage on the suction side is provided with an air
filter
(field
supply)).
(2) If air conditioner has more than one air outlet and air inlet,
be sure to make adjustments so that the air volume ratio of
each air outlet and the corresponding air inlet will conform
to the designed air volume ratio.
In that case, set the operating mode to “Fan”. (In the case
of changing the air volume, press the fan speed button on
the remote controller and change the current selection to
“High”, “Medium”, or “Low”.)
In case of 140 class
External static
pressure
Mode No.
FIRST
CODE No.
SECOND
CODE No.
50Pa
13(23)
6
05
60Pa
06
70Pa
07
80Pa
08
90Pa
09
100Pa
10
110Pa
11
120Pa
12
130Pa
13
140Pa
14
Summary of Contents for FXSQ-PAVE
Page 1: ...FXSQ PAVE EDFMT391737 201709 Engineering Data 50 60 Hz...
Page 2: ......
Page 10: ...FXSQ PAVE EDFMT391737 8 3 Dimensions FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE 3D095725B Unit mm...
Page 11: ...FXSQ PAVE EDFMT391737 9 FXSQ40PAVE 3D095726B Unit mm...
Page 12: ...FXSQ PAVE EDFMT391737 10 FXSQ50PAVE 3D096164B Unit mm...
Page 13: ...FXSQ PAVE EDFMT391737 11 FXSQ63PAVE FXSQ80PAVE 3D095426D Unit mm...
Page 14: ...FXSQ PAVE EDFMT391737 12 FXSQ100PAVE FXSQ125PAVE 3D095427D Unit mm...
Page 15: ...FXSQ PAVE EDFMT391737 13 FXSQ140PAVE 3D095727C Unit mm...
Page 22: ...FXSQ PAVE EDFMT391737 20 9 Fan Performances FXSQ20PAVE FXSQ25PAVE 3D095855A...
Page 23: ...FXSQ PAVE EDFMT391737 21 FXSQ32PAVE 3D095856A...
Page 24: ...FXSQ PAVE EDFMT391737 22 FXSQ40PAVE 3D095857A...
Page 25: ...FXSQ PAVE EDFMT391737 23 FXSQ50PAVE 3D095858A...
Page 26: ...FXSQ PAVE EDFMT391737 24 FXSQ63PAVE 3D095859A...
Page 27: ...FXSQ PAVE EDFMT391737 25 FXSQ80PAVE 3D095860A...
Page 28: ...FXSQ PAVE EDFMT391737 26 FXSQ100PAVE 3D095861A...
Page 29: ...FXSQ PAVE EDFMT391737 27 FXSQ125PAVE 3D095862A...
Page 30: ...FXSQ PAVE EDFMT391737 28 FXSQ140PAVE 3D095863A...
Page 32: ...FXSQ PAVE EDFMT391737 30 FXSQ32PAVE 3D095847A...
Page 33: ...FXSQ PAVE EDFMT391737 31 FXSQ40PAVE 3D095848A...
Page 34: ...FXSQ PAVE EDFMT391737 32 FXSQ50PAVE 3D095849A...
Page 35: ...FXSQ PAVE EDFMT391737 33 FXSQ63PAVE 3D095850A...
Page 36: ...FXSQ PAVE EDFMT391737 34 FXSQ80PAVE 3D095851A...
Page 37: ...FXSQ PAVE EDFMT391737 35 FXSQ100PAVE 3D095852A...
Page 38: ...FXSQ PAVE EDFMT391737 36 FXSQ125PAVE 3D095853A...
Page 39: ...FXSQ PAVE EDFMT391737 37 FXSQ140PAVE 3D095854A...
Page 40: ...FXSQ PAVE EDFMT391737 38 11 Sound Levels FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE 4D095804B 4D095805B...
Page 41: ...FXSQ PAVE EDFMT391737 39 FXSQ40PAVE FXSQ50PAVE 4D095806B 4D095807B...
Page 42: ...FXSQ PAVE EDFMT391737 40 FXSQ63PAVE FXSQ80PAVE 4D095808B 4D095809B...
Page 43: ...FXSQ PAVE EDFMT391737 41 FXSQ100PAVE FXSQ125PAVE 4D095810B 4D095811B...
Page 44: ...FXSQ PAVE EDFMT391737 42 FXSQ140PAVE 4D095812B...
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......