background image

FXSQ-PAVE EDFMT391737

50

3P432203-4B

5

Control box

20 or more

Ceiling

Inspection port

A

Inspection 

port 1

(450×450)

Inspection 

port 3

Control box

Control box

800

800

Arrow A-1

Arrow A-2

Inspection port 2

(Indoor unit size 

+ 300 or more)

(Indoor unit 

size or more)

200mm  or less

D=B+300 or more

B

< In the case of (1)-2, 3 >

Fig. 4

Table 1 

(unit [mm])

Model

B

C

D

20·25·32 class

550

588

850

40 class

700

738

1000

50·63·80 class

1000

1038

1300

100·125 class

1400

1438

1700

140 class

1550

1588

1850

(2)  Mount canvas ducts to the air outlet and inlet so that 

the vibration of the indoor unit will not be transmit-

ted to the ducts or ceiling. Furthermore, attach sound 

absorbing material (thermal insulation material) to the 

duct inner walls and anti-vibration rubber to the hang-

ing bolts (refer to 8. DUCT WORK).

(3)  The indoor unit is set to standard external static pres-

sure.

• 

If external static pressure is higher or lower than the 
standard set value, the remote controller may be used to 
make on-site setting change in the external static pres-
sure.  
Refer to 

10. FIELD SETTING.

(4)  Open installation holes  

(in the case of installation onto the existing ceiling).

• 

Open the installation holes on the ceiling of the instal-
lation location, and work on the refrigerant piping, drain 
piping, remote controller wiring (unless a wireless re-
mote controller is used), and wiring between the indoor 
and outdoor units to the piping connection port and 
wiring connection port of the indoor unit (refer to each 
piping and wiring procedure items).

• 

Ceiling framework reinforcement may be required in 
order to keep the ceiling horizontal and prevent ceiling 
vibration after opening the ceiling holes. For details, 
consult your building and upholstery work contractors.

(5)  Install the hanging bolts.

• 

Use M8 or M10 bolts for hanging the indoor unit. 
Use hole-in-anchors for the existing bolts and embed-
ded inserts or foundation bolts for new bolts, and

the

indoor unit 

 to the building so that it may withstand

the mass of the unit. 

(2)  Use hanging bolts for installation.

Investigate if the installation place can withstand the mass 
of the indoor unit and, if necessary, hang the indoor unit 
with bolts after it is reinforced by beams etc.

4.  PREPARATION BEFORE INSTALLATION

(1)  Check the relation of location between the ceiling 

opening and the indoor unit hanging bolts. (unit [mm])

• 

Provide one of the following service spaces for the 
maintenance and inspection of the control box and 
drain pump or for other services.

1.  Inspection ports 1 and 2 (450 × 450) (Fig. 3-1) and 

a minimum space of 300 mm at the bottom of the 
product (Fig. 3).

2.  Inspection port 1 (450 × 450) on the control box side 

and inspection port 2 on the bottom of the product. 
(Fig. 4, arrow A-1)

3.  Inspection port 3 on the bottom of the product and on 

the bottom side of the control box. (Fig. 4, arrow A-2)

Control box

300 or more

Ceilin

I

g

nspection port

< In the case of (1)-1 >

Fig. 3

Control box

800

200 or less

500

B

C

(Hanging bolt pitch

)

Hanging bolts (× 4)

630

Air outlet

Bottom of 

indoor unit

* Inspection port 2 is not required 

if the bottom space under the product 

is accessible for work.

Air inlet

(Hanging bolt pitch)

Inspection port 1

(450×450)

Inspection port 2*

(450×450)
(For drain pan 

removal and 

component replacement)

Fig. 3-1

Summary of Contents for FXSQ-PAVE

Page 1: ...FXSQ PAVE EDFMT391737 201709 Engineering Data 50 60 Hz...

Page 2: ......

Page 3: ...Safety Devices Setting 17 8 Capacity Tables 18 8 1 Cooling Capacity for Te Auto 18 8 2 Cooling Capacity for Te 6 C 18 8 3 Cooling Capacity for Te 9 C 19 8 4 Heating Capacity 19 9 Fan Performances 20 1...

Page 4: ...5 40 50 62 5 80 100 125 140 FXSQ 20PAVE 25PAVE 32PAVE 40PAVE 50PAVE 63PAVE 80PAVE 100PAVE 125PAVE 140PAVE FXSQ for Thailand 20PAVS 25PAVS 32PAVS 40PAVS 50PAVS 63PAVS 80PAVS 100PAVS 125PAVS 140PAVS FXS...

Page 5: ...expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange Operati...

Page 6: ...ion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange Operation man...

Page 7: ...xpansion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange Operatio...

Page 8: ...c expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange Opera...

Page 9: ...tronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange...

Page 10: ...FXSQ PAVE EDFMT391737 8 3 Dimensions FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE 3D095725B Unit mm...

Page 11: ...FXSQ PAVE EDFMT391737 9 FXSQ40PAVE 3D095726B Unit mm...

Page 12: ...FXSQ PAVE EDFMT391737 10 FXSQ50PAVE 3D096164B Unit mm...

Page 13: ...FXSQ PAVE EDFMT391737 11 FXSQ63PAVE FXSQ80PAVE 3D095426D Unit mm...

Page 14: ...FXSQ PAVE EDFMT391737 12 FXSQ100PAVE FXSQ125PAVE 3D095427D Unit mm...

Page 15: ...FXSQ PAVE EDFMT391737 13 FXSQ140PAVE 3D095727C Unit mm...

Page 16: ...PAVE FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE 12...

Page 17: ...FXSQ PAVE EDFMT391737 15 5 Wiring Diagrams FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE 3D092752C...

Page 18: ...FXSQ PAVE EDFMT391737 16 6 Electric Characteristics FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE 4D105290...

Page 19: ...V 6 3 A Drain pump thermal fuse C Model FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE Printed circuit board fuse 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A Printed circuit board fuse Fan drive...

Page 20: ...length Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 1...

Page 21: ...8 TC Total capacity kW SHC Sensible heat capacity kW Notes 1 These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the sel...

Page 22: ...FXSQ PAVE EDFMT391737 20 9 Fan Performances FXSQ20PAVE FXSQ25PAVE 3D095855A...

Page 23: ...FXSQ PAVE EDFMT391737 21 FXSQ32PAVE 3D095856A...

Page 24: ...FXSQ PAVE EDFMT391737 22 FXSQ40PAVE 3D095857A...

Page 25: ...FXSQ PAVE EDFMT391737 23 FXSQ50PAVE 3D095858A...

Page 26: ...FXSQ PAVE EDFMT391737 24 FXSQ63PAVE 3D095859A...

Page 27: ...FXSQ PAVE EDFMT391737 25 FXSQ80PAVE 3D095860A...

Page 28: ...FXSQ PAVE EDFMT391737 26 FXSQ100PAVE 3D095861A...

Page 29: ...FXSQ PAVE EDFMT391737 27 FXSQ125PAVE 3D095862A...

Page 30: ...FXSQ PAVE EDFMT391737 28 FXSQ140PAVE 3D095863A...

Page 31: ...FXSQ PAVE EDFMT391737 29 10 Airflow Auto Adjustment Characteristics FXSQ20PAVE FXSQ25PAVE 3D095846A...

Page 32: ...FXSQ PAVE EDFMT391737 30 FXSQ32PAVE 3D095847A...

Page 33: ...FXSQ PAVE EDFMT391737 31 FXSQ40PAVE 3D095848A...

Page 34: ...FXSQ PAVE EDFMT391737 32 FXSQ50PAVE 3D095849A...

Page 35: ...FXSQ PAVE EDFMT391737 33 FXSQ63PAVE 3D095850A...

Page 36: ...FXSQ PAVE EDFMT391737 34 FXSQ80PAVE 3D095851A...

Page 37: ...FXSQ PAVE EDFMT391737 35 FXSQ100PAVE 3D095852A...

Page 38: ...FXSQ PAVE EDFMT391737 36 FXSQ125PAVE 3D095853A...

Page 39: ...FXSQ PAVE EDFMT391737 37 FXSQ140PAVE 3D095854A...

Page 40: ...FXSQ PAVE EDFMT391737 38 11 Sound Levels FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE 4D095804B 4D095805B...

Page 41: ...FXSQ PAVE EDFMT391737 39 FXSQ40PAVE FXSQ50PAVE 4D095806B 4D095807B...

Page 42: ...FXSQ PAVE EDFMT391737 40 FXSQ63PAVE FXSQ80PAVE 4D095808B 4D095809B...

Page 43: ...FXSQ PAVE EDFMT391737 41 FXSQ100PAVE FXSQ125PAVE 4D095810B 4D095811B...

Page 44: ...FXSQ PAVE EDFMT391737 42 FXSQ140PAVE 4D095812B...

Page 45: ...FXSQ PAVE EDFMT391737 43 12 Centre of Gravity FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE 4D095814B Unit mm...

Page 46: ...chamber for rear suction Note 1 KDDFP63B80 Long life replacement filter Note 1 KAFP631B80 Service panel White KTBJ25K80W Fresh white KTBJ25K80F Brown KTBJ25K80T Air discharge adapter KDAP25A71A Shiel...

Page 47: ...roller Wireless Cooling Only BRC4C66 Note 4 Heat Pump BRC4C65 Note 4 Wired BRC1C62 Note 4 Navigation remote controller Wired remote controller BRC1E62 Note 4 5 Simplified remote controller Exposed typ...

Page 48: ...our local dealer regarding what to do in case of refrigerant leakage When the air conditioner is installed in a small room it is necessary to take proper measures so that the amount of any leaked refr...

Page 49: ...ng of soft material or protective plates together with a rope when lifting to avoid damage or scratches to the indoor unit Have the customer actually operate the air conditioner while looking at the o...

Page 50: ...ts or inlets of the indoor and outdoor units blocked with obstacles It may lead to capacity drop due to fan speed drop or malfunction of equipment Does not cool Does not heat Is the external static pr...

Page 51: ...type lamp is installed If you set the fan speed at thermostat OFF did you explain the set fan speed to the customer Have you handed the operation manual and the installation manual to the customer Ha...

Page 52: ...ng framework reinforcement may be required in order to keep the ceiling horizontal and prevent ceiling vibration after opening the ceiling holes For details consult your building and upholstery work c...

Page 53: ...3 Check the level of the unit Refer to Fig 8 4 Remove the washer clamp 9 used for preventing the washer for hanger 11 from dropping and tighten the up per side nut Hanger Bottom of product Level Viny...

Page 54: ...t into the clearance between the hanger and the washer for hanger 11 Unless the washers are properly attached the hanging bolts may come off from the hanger WARNING The indoor unit must be securely in...

Page 55: ...t drainage is ensured Select the piping diameter equal to or larger than except for riser that of the connection piping polyvi nyl chloride piping nominal diameter 25 mm outside diameter 32 mm Install...

Page 56: ...up grade so that air may not stagnate in the drain hose If air stagnates the drain may ow oppositely when the drain pump stops and generate abnormal sound unit mm Fig 16 Downward inclination of 1 100...

Page 57: ...ghtened Wrap the sealing material Large 6 so that the metal clamp 1 end side may be doubled Metal clamp 1 accessory Drain hose 2 accessory Sealing material Large 6 accessory Sealing material Large 6 a...

Page 58: ...Q80PAVE 1 8 15 0 230 1 5 FXSQ100PAVE 2 5 15 0 300 2 0 FXSQ125PAVE 2 8 15 0 300 2 2 FXSQ140PAVE 3 1 15 0 350 2 5 8 DUCT WORK Pay the utmost attention to the following items and conduct the ductwork Che...

Page 59: ...WARNING When wiring form the wirings orderly so that the control box lid can be securely fastened If the control box lid is not in place the wirings may come out or be sandwiched by the box and the li...

Page 60: ...uctions below and perform wiring in the control box F2 T2 P1 P2 F1 T1 Securely x the wiring to the provided wiring xture with the clamp 8 Terminal block X1M for power supply wiring and earth wiring Co...

Page 61: ...ted In case of ON OFF OPERATION Operation Stop 3 How to choose FORCED OFF or ON OFF OPERATION For choosing FORCED OFF or ON OFF OPERATION setting by remote controller is required Refer to 10 FIELD SET...

Page 62: ...is completed on page 3 Check if all the installation and piping works for the air conditioner are completed Check that the outside panel and piping cover of the indoor and outdoor units are closed FIE...

Page 63: ...power supply wiring to the outdoor unit is not carried out The transmission wiring and the remote controller wiring and FORCED OFF wiring are connected wrongly The transmission wiring is disconnected...

Page 64: ......

Page 65: ......

Page 66: ......

Page 67: ......

Page 68: ...parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation...

Reviews: