background image

• VRV

®

 Systems • Indoor Units

7

• Indoor Units • CONCEALED CEILING UNIT • FXSQ-P7VEB

3

Safety device settings

4

Options

Safety devices

20

25

32

40

50

63

80

100

125

FXSQ

PC Board Fuse

250V  3.15A

250V  3.15A

250V  3.15A

250V  3.15A

250V  3.15A

250V  3.15A

250V  3.15A

250V  3.15A

250V  3.15A

PC Board Fuse (Fan Driver)

250V  5A

250V  5A

250V  5A

250V  5A

250V  5A

250V  6.3A

250V  6.3A

250V  6.3A

250V  6.3A

Fan Motor Thermal Protector

°C

Drain Pump Fuse

°C

145

145

145

145

145

145

145

145

145

FXSQ20-125P

3TW31189-3A

Options

Operation Control

(*1): Electrical heater and humidifier are field supply. These parts should not be installed inside the equipment (refer to installation manual EKRP1B2A)
(*2): If installing an electrical heater, an option PCB for external heater (EKRP1B2) for each indoor unit is required.
(*3): An electrical heater can not be used for VRV system cooling only.
(*4): Mounting plate KRP4A96 is required for these options. Maximum 2 option PCB’s can be mounted.

Contents of accessory bag

Item

Type

FXSQ20,25,32

FXSQ40,50

FXSQ63,80

FXSQ100,125

Panel related

Decoration panel

BYBS32

BYBS45D

BYBS71D

BYBS125D

Air inlet and air discharge outlet related

Air discharge adapter for round duct

KDAJ25K36A

KDAJ25K56A

KDAJ25KA71A

KDAJ25KA140A

Item

Type

FXSQ20,25,32

FXSQ40,50

FXSQ63,80

FXSQ100,125

Remote Control

Wired Type

BRC1D528

Infrared type

HP

BRC4C65

CO

BRC4C66

Simplified remote control

BRC2C51

Remote control for hotel use

BRC3A61

Option BCB for external el. heater, humidifier and/or hour meter (*1), (*2), (*3), (*4)

EKRP1B2A

Wiring adapter for electrical appendices (1) (*2), (*4)

KRP2A51

Wiring adapter for electrical appendices (2) (*4)

KRP4A51

Remote sensor

KRCS01-1

Central remote control

DCS302CA51

Electrical box with earth terminal (3 blocks)

KJB311A

Unified ON/OFF control

DCS301BA51

Electrical box with earth terminal (2 blocks)

KJB212A

Schedule timer

DST301BA51

External adapter for outdoor unit (installation on indoor unit) (*4)

DTA104A61

Mounting plate for adapter PCB

KRP4A96

Description

Quantity

FXSQ20,25,32,40,50,60,71,100,125

Hexagon tapping screw (M5x16)

16

Round plain washer for wood

8

Installation and operation manual

1

Hose band

1

Insulation for joint (GAS)

1

Insulation for joint (LIQUID)

1

Drain hose

1

Drain hose sealing material

1

Sealing material

2

NOTES

Summary of Contents for FXSQ-P7VEB

Page 1: ...Concealed Ceiling Unit FXSQ P7VEB air conditioning systems technical data...

Page 2: ...Concealed Ceiling Unit FXSQ P7VEB technical data air conditioning systems...

Page 3: ...ety device settings 7 4 Options 7 5 Capacity tables 8 Cooling capacity tables 8 Heating capacity tables 10 6 Dimensional drawing centre of gravity 12 Dimensional drawing 12 Centre of gravity 14 7 Pipi...

Page 4: ...Face Area m 0 097 0 097 0 097 0 148 0 148 Nr of Stages 16 Empty Tubeplate Hole 12 Tube type Hi XSS 7 Fin Fin type Symmetric waffle louvre Treatment Hydrophilic Fan Type Sirocco fan Quantity 1 Cooling...

Page 5: ...TECHNICAL SPECIFICATIONS FXSQ63P7VEB FXSQ80P7VEB FXSQ100P7VEB FXSQ125P7VEB Capacity Cooling kW 7 1 9 0 11 2 14 0 Heating kW 8 0 10 0 12 5 16 0 Power Input 50Hz Cooling kW 142 163 247 303 Heating kW 1...

Page 6: ...1 BYBS125DJW1 BYBS125DJW1 BYBS125DJW1 Colour White 10Y9 0 5 Dimensions Height mm 55 Width mm 1 100 1 500 1 500 1 500 Depth mm 500 Weight kg 4 5 6 5 6 5 6 5 Drain up Height mm 625 Air Filter Resin net...

Page 7: ...range limits Maximum allowable voltage range variation between phases is 2 Select wire size based on the MCA Instead of a fuse use a circuit breaker 1 3 ELECTRICAL SPECIFICATIONS 60HZ FXSQ20P7VEB FXS...

Page 8: ...voltage supplied to the unit terminals is not below or above listed range limits 2 The maximum allowable voltage variation between phases is 2 3 Select a wire size based on the MCA 4 Instead of a fus...

Page 9: ...00 125 Panel related Decoration panel BYBS32 BYBS45D BYBS71D BYBS125D Air inlet and air discharge outlet related Air discharge adapter for round duct KDAJ25K36A KDAJ25K56A KDAJ25KA71A KDAJ25KA140A Ite...

Page 10: ...4 2 2 2 9 2 5 3 4 2 8 3 6 2 9 3 8 2 9 4 3 3 0 4 4 3 0 18 0 2 4 2 2 2 9 2 5 3 4 2 8 3 6 2 9 3 8 2 9 4 2 3 0 4 3 2 9 20 0 2 4 2 2 2 9 2 5 3 4 2 8 3 6 2 9 3 8 2 9 4 2 2 9 4 3 2 9 21 0 2 4 2 2 2 9 2 5 3 4...

Page 11: ...7 2 6 1 8 4 6 9 9 0 7 0 9 1 6 9 9 3 6 6 9 5 6 6 37 0 6 1 5 3 7 2 6 1 8 4 6 9 8 9 6 9 9 0 6 8 9 2 6 6 9 4 6 5 39 0 6 1 5 3 7 2 6 1 8 4 6 9 8 7 6 8 8 8 6 7 9 0 6 5 9 3 6 5 100 10 0 7 6 6 4 9 0 7 3 10 5...

Page 12: ...8 7 9 0 7 9 10 8 10 6 10 0 9 7 9 4 8 7 11 0 9 8 11 2 10 6 10 0 9 7 9 4 8 7 13 0 11 8 11 3 10 6 10 0 9 7 9 4 8 7 15 0 13 7 11 3 10 6 10 0 9 7 9 4 8 7 100 19 8 20 0 7 4 7 4 7 3 7 3 7 3 7 3 18 8 19 0 7...

Page 13: ...2 6 2 6 2 6 2 5 14 7 15 0 2 7 2 7 2 7 2 7 2 7 2 7 12 6 13 0 2 9 2 9 2 8 2 8 2 8 2 8 10 5 11 0 3 0 3 0 3 0 3 0 3 0 3 0 9 5 10 0 3 1 3 1 3 1 3 1 3 0 3 0 8 5 9 1 3 1 3 1 3 1 3 1 3 1 3 1 7 0 7 6 3 2 3 2...

Page 14: ...ion side 9 Air discharge side 10 Nameplate View A A Detail B Suspension bolt Service space Detail B 300 or more Service space Suspension position Suspension position FXSQ40 50P 3TW31214 1 NOTE 1 Refer...

Page 15: ...ide 9 Air discharge side 10 Nameplate View A A Detail B Suspension bolt Service space Detail B 350 or more Service space Suspension position Suspension position or more FXSQ100 125P 3TW31254 1 NOTE 1...

Page 16: ...CEILING UNIT FXSQ P7VEB VRV Systems Indoor Units 14 6 Dimensional drawing centre of gravity 6 2 Centre of gravity FXSQ20 125P 4TW31189 1A MODEL A B FXSQ20 32 220 550 FXSQ40 50 283 700 FXSQ63 80 441 10...

Page 17: ...gram FXSQ20 125P 3TW31185 1 Heat exchanger Liquid pipe connection port Gas pipe connection port Filter Filter Electronic expansion valve Refrigerant flow Cooling Heating Refrigerant pipe connection po...

Page 18: ...or optional accessory F2U Fuse T 5A 250V R2T Thermistor Liquid X28A Connector power supply for wiring F3U Fuse T 6 3A 250V R3T Thermistor gas X35A Connector adapter F4U Fuse T 6 3A 250V R5T Thermistor...

Page 19: ...res 0dB 20 Pa 5 Location of microphine Sound pressure level dB Octave band center frequency dB 1 5m Microphone Unit 2m 2m 1 5m 1m High tap Medium tap Low tap Discharge Suction FXSQ40 50P 3TW31217 2 No...

Page 20: ...ta is valid at free field condition 2 Data is valid at nominal operation condition 3 dBA A weighted sound power level A scale according to IEC 4 Reference acoustic pressures 0dB 20 Pa 5 Location of mi...

Page 21: ...m2 3 Measured according to ISO 3744 Sound pressure level dB Octave band center frequency dB High tap Medium tap Low tap FXSQ40 50P 3TW31217 1 Notes 1 dBA A weighted sound power level A scale according...

Page 22: ...dB High tap Medium tap Low tap FXSQ100P 3TW31257 1 Notes 1 dBA A weighted sound power level A scale according to IEC 2 Reference acoustic intensity 0dB 10E 6 W m2 3 Measured according to ISO 3744 Sou...

Page 23: ...r limit of ESP by airflow auto adjustment Lower limit of ESP External static pressure Pa External static pressure Pa H M L External static pressure Pa FXSQ32P 3TW31208 1 Fan characteristics 1 Fan char...

Page 24: ...r limit of ESP by airflow auto adjustment Lower limit of ESP External static pressure Pa External static pressure Pa External static pressure Pa H M L FXSQ63P 3TW31238 1 Fan characteristics 1 Fan char...

Page 25: ...r limit of ESP by airflowautoadjustment Lower limit of ESP External static pressure Pa External static pressure Pa H M L External static pressure Pa FXSQ100P 3TW31258 1 Fan characteristics 1 Fan chara...

Page 26: ...rate H Airflow m min NOTES 1 Fan characteristics as shown ar in fan only mode 2 ESP External static pressure Upper limit of ESP max ESP H max ESP M max ESP L max ESP Lower limit of ESP max ESP H std...

Page 27: ...uction Ceiling return Ceiling return Installation with duct Direct installation of inlet panel Wide variety of installation methods Easy modification from rear to bottom suction Drain pump up height N...

Page 28: ...ation with air inlet duct or less NOTES Nr Description 1 When installing the unit with rear suction a service opening is necessary for the maintenance of the air filters 2 When installing the unit wit...

Page 29: ...VRV Systems Indoor Units 27 Indoor Units CONCEALED CEILING UNIT FXSQ P7VEB 11 Installation 11 3 Switch box connection FXSQ20 125P 3TW31184 5 Emerg Common power supply Norm...

Page 30: ......

Page 31: ...ithout prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this publicat...

Reviews: