• Indoor Units • CONCEALED CEILING UNIT • FXSQ-P7VEB
• VRV
®
Systems • Indoor Units
4
1
Specifications
Motor
Speed (cooling)
High
rpm
975
1,161
1,060
1,218
Low
rpm
840
960
813
920
Speed (heating)
High
rpm
975
1,161
1,060
1,218
Low
rpm
840
960
813
920
Fan
Motor
Output (high)
W
350
Drive
Direct drive
Refrigerant
Name
R-410A
Sound level
Cooling
Sound power
(nominal)
dBA
59
63
61
66
Cooling
Sound Pressure
High
dBA
37
38
38
40
Low
dBA
30
32
32
33
Heating
Sound Pressure
High
dBA
37
38
38
40
Low
dBA
30
32
32
33
Piping connections
Liquid (OD)
Type
Flare connection
Diameter
mm
9.52
Gas
Type
Flare connection
Diameter
mm
15.9
Drain
Diameter
mm
VP25 (O.D. 32 / I.D. 25)
Heat Insulation
Both liquid and gas pipes
Decoration Panel
Model
BYBS71DJW1
BYBS125DJW1
BYBS125DJW1
BYBS125DJW1
Colour
White (10Y9/0,5)
Dimensions
Height
mm
55
Width
mm
1,100
1,500
1,500
1,500
Depth
mm
500
Weight
kg
4.5
6.5
6.5
6.5
Drain-up Height
mm
625
Air Filter
Resin net with mold resistance
Refrigerant control
Electronic expansion valve
Safety devices
PC board fuse
PC board fuse (fan driver)
Drain pump fuse
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature
: 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB,
6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
The sound pressure values are mentioned for a unit installed with rear suction
1-1 TECHNICAL SPECIFICATIONS
FXSQ63P7VEB
FXSQ80P7VEB
FXSQ100P7VEB
FXSQ125P7VEB