• Indoor Units • CONCEALED CEILING UNIT • FXSQ-P7VEB
1
Specifications
1-2 ELECTRICAL SPECIFICATIONS (50HZ)
FXSQ20P7VEB
FXSQ25P7VEB
FXSQ32P7VEB
FXSQ40P7VEB
FXSQ50P7VEB
Power Supply
Name
VE
Frequency
Hz
50
Voltage
V
220-240
Current
Minimum circuit amps (MCA)
A
0.4
0.4
0.4
1.2
1.2
Maximum fuse amps (MFA)
A
16
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-2 ELECTRICAL SPECIFICATIONS (50HZ)
FXSQ63P7VEB
FXSQ80P7VEB
FXSQ100P7VEB
FXSQ125P7VEB
Power Supply
Name
VE
Frequency
Hz
50
Voltage
V
220-240
Current
Minimum circuit amps (MCA)
A
1.1
1.3
1.6
2.1
Maximum fuse amps (MFA)
A
16
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 ELECTRICAL SPECIFICATIONS (60HZ)
FXSQ20P7VEB
FXSQ25P7VEB
FXSQ32P7VEB
FXSQ40P7VEB
FXSQ50P7VEB
Power Supply
Name
VE
Frequency
Hz
60
Voltage
V
220
Current
Minimum circuit amps (MCA)
A
0.4
0.4
0.4
1.2
1.2
Maximum fuse amps (MFA)
A
16
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 ELECTRICAL SPECIFICATIONS (60HZ)
FXSQ63P7VEB
FXSQ80P7VEB
FXSQ100P7VEB
FXSQ125P7VEB
Power Supply
Name
VE
Frequency
Hz
60
Voltage
V
220
Current
Minimum circuit amps (MCA)
A
1.1
1.3
1.6
2.1
Maximum fuse amps (MFA)
A
16
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker