background image

5 User interface

Installation and operation manual

8

FXSN50~112A2VEB

CO

 Conveni-Pack: indoor unit

4P602815-1F – 2021.07

a

b

e

e

d

c

f

h

i

j

k

h

l

i

j

k

l

g

a

Main outdoor unit (LRYEN10*)

b

Capacity up unit (LRNUN5*)

c

Communication box (BRR9B1V1)

d

Indoor unit for air conditioning

e

Indoor unit for refrigeration (showcase)

f

Indoor unit for refrigeration (blower coil)

g

Safety valve

h

CO

2

 control panel

i

CO

2

 detector

j

CO

2

 alarm

k

CO

2

 ventilator

l

Shut off valve

5

User interface

CAUTION

▪ NEVER touch the internal parts of the controller.

▪ Do NOT remove the front panel. Some parts inside are

dangerous  to  touch  and  appliance  problems  may
happen.  For  checking  and  adjusting  the  internal  parts,
contact your dealer.

This operation manual offers a non-exhaustive overview of the main
functions of the system.

For  more  information  about  the  user  interface,  see  the  operation
manual of the installed user interface.

6

Operation

6.1

Operation range

Use the system in the following temperature and humidity ranges for
safe and effective operation.

Cooling and drying

Heating

Outdoor unit

–5~43°C DB

–20~16°C WB

Cooling and drying

Heating

Indoor unit

14~24°C WB

15~27°C DB

Indoor humidity

≤80%

(a)

(a)

To avoid condensation and water dripping out of the unit. If the
temperature or the humidity is beyond these conditions, safety
devices may be put in action and the air conditioner may not
operate.

6.2

About operation modes

INFORMATION

Depending on the installed system, some operation modes
will not be available.

▪ The  air  flow  rate  may  adjust  itself  depending  on  the  room

temperature  or  the  fan  may  stop  immediately.  This  is  not  a
malfunction.

▪ If the main power supply is turned off during operation, operation

will restart automatically after the power turns back on again.

Setpoint.

  Target  temperature  for  the  Cooling,  Heating,  and  Auto

operation modes.

Setback.

 A function that keeps the room temperature in a specific

range  when  the  system  is  turned  off  (by  the  user,  the  schedule
function, or the OFF timer).

6.2.1

Basic operation modes

The indoor unit can operate in various operation modes.

Icon

Operation mode

Cooling.

 In this mode, cooling will be activated as

required by the setpoint, or by Setback operation.

Heating.

 In this mode, heating will be activated as

required by the setpoint, or by Setback operation.

Fan only.

 In this mode, air circulates without heating

or cooling.

Dry.

 In this mode, the air humidity will be lowered with

a minimal temperature decrease.

The temperature and fan speed are controlled
automatically and cannot be controlled by the
controller.

Dry operation will not function if the room temperature
is too low.

Auto.

 In Auto mode, the indoor unit automatically

switches between heating and cooling mode, as
required by the setpoint.

Summary of Contents for FXSN71A2VEB

Page 1: ...Installation and operation manual CO Conveni Pack indoor unit English Installation and operation manual CO Conveni Pack indoor unit FXSN50A2VEB FXSN71A2VEB FXSN112A2VEB...

Page 2: ...fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi...

Page 3: ...9 13 2 To connect the electrical wiring to the indoor unit 19 13 3 To connect appropriate measures for appliances filled with CO 20 14 Commissioning 20 14 1 Checklist before commissioning 20 14 2 To p...

Page 4: ...f valve from liquid pipe to gas pipe When the safety shut off valves close and no measures are installed increased pressure may damage the liquid piping Installing the ducting see 11 2 2 Guidelines wh...

Page 5: ...ning use of the appliance in a safe way and understand the hazards involved Children SHALL NOT play with the appliance Cleaning and user maintenance SHALL NOT be made by children without supervision W...

Page 6: ...y if equipment with burner is used together with the system CAUTION Do NOT operate the system when using a room fumigation type insecticide Chemicals could collect in the unit and endanger the health...

Page 7: ...ubleshooting see 8 Troubleshooting 410 WARNING Stop operation and shut OFF the power if anything unusual occurs burning smells etc Leaving the unit running under such circumstances may cause breakage...

Page 8: ...umidity is beyond these conditions safety devices may be put in action and the air conditioner may not operate 6 2 About operation modes INFORMATION Depending on the installed system some operation mo...

Page 9: ...ilter suction grille air outlet and outside panels WARNING NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit...

Page 10: ...interface only for Madoka with buzzer see option list or from another safety alarm in combination with a CO2 refrigerant leak detector field supply Actions required by the user 1 Ventilate the room an...

Page 11: ...terface operation lamp or display blinks Check if the air filter is clogged see 7 2 2 To clean the air filter 49 Check if air inlet or outlet of outdoor or indoor unit is not blocked by obstacles Remo...

Page 12: ...rd WARNING Make sure to install all necessary countermeasures in case of refrigerant leakage according to standard EN378 see 11 1 2 Additional installation site requirements for CO refrigerant 413 Mak...

Page 13: ...safety alarm in combination with a CO2 refrigerant leak detector a safety alarm alone is NOT considered an appropriate measure where occupants are restricted in their movements CO2 refrigerant leak de...

Page 14: ...5 20 25 30 35 40 45 50 55 60 65 70 d b a RCL QLAV QLMV c 11 3 Example graph for calculation A Refrigerant charge limit B Room volume a Installation is not allowed b 2 appropriate measures required c 1...

Page 15: ...the drain pan or the air filter If the metal duct passes through a metal lath wire lath or metal plate of the wooden structure separate the duct and wall electrically Install the outlet grille in a po...

Page 16: ...iameter field supply d Hanging bars field supply Combining drain pipes You can combine drain pipes Make sure to use drain pipes and T joints with the correct gauge for the operating capacity of the un...

Page 17: ...the reference guide or the service manual of the user interface 2 Gradually pour approximately 1 l of water through the water inlet and check for leaks see When installation of the system is not yet...

Page 18: ...ending on its location in the system Use K65 unions and fittings approved for a working pressure of 120 bar or 90 bar depending on its location in the system ONLY brazing is allowed for connection of...

Page 19: ...wiring and power supply wiring may cross but may NOT run parallel 1 Remove the service cover 2 User interface cable Route the cable through the frame connect the cable to the terminal block symbols P1...

Page 20: ...T1 T2 3 If the CO2 refrigerant leak detector is installed enable the function for refrigerant leak detection as described in 15 1 Field setting 421 P1P2 F1 F2 T1 T2 P1P2 P1P2 P1P2 F1 F2 T1 T2 P1P2 F1...

Page 21: ...ion To set bottom suction or rear suction installation If you have an installation with Then 1 M SW C1 C2 Rear suction 13 23 11 01 Bottom suction 02 To set automatic airflow adjustment The automatic a...

Page 22: ...nit Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by in the part code Symbol Meaning Symbol Meaning Circuit breaker Protective earth Con...

Page 23: ...ant leak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge a...

Page 24: ...4P602815 1F 2021 07 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: