Daikin FXSN71A2VEB Installation And Operation Manual Download Page 9

7 Maintenance and service

Installation and operation manual

9

FXSN50~112A2VEB
CO

 Conveni-Pack: indoor unit

4P602815-1F – 2021.07

6.2.2

Special heating operation modes

Operation

Description

Defrost

To prevent a loss of heating capacity due to frost
accumulation in the outdoor unit, the system will
automatically switch to defrost operation.

During defrost operation, the indoor unit fan will
stop operation, and the following icon will appear on
the home screen:

In order to protect the system, cold air may come
from the indoor unit when the defrost operation
starts on the outdoor unit side.

The system will resume normal operation after
approximately 6 to 8 minutes.

Hot start

During hot start, the indoor unit fan will stop
operation, and the following icon will appear on the
home screen:

6.3

To operate the system

INFORMATION

For setting of the operation mode or other settings, see the
reference guide or operation manual of the user interface.

7

Maintenance and service

7.1

Precautions for maintenance and
service

WARNING: 

  System  contains  refrigerant

under very high pressure.

The system MUST be serviced by qualified persons ONLY.

NOTICE

Maintenance  MUST  be  done  by  an  authorised  installer  or
service agent.

We  recommend  performing  maintenance  at  least  once  a
year. However, applicable legislation might require shorter
maintenance intervals.

CAUTION

Do  NOT  insert  fingers,  rods  or  other  objects  into  the  air
inlet or outlet. When the fan is rotating at high speed, it will
cause injury.

NOTICE

NEVER  inspect  or  service  the  unit  by  yourself.  Ask  a
qualified service person to perform this work. However, as
end  user,  you  may  clean  the  air  filter,  suction  grille,  air
outlet and outside panels.

WARNING

NEVER  replace  a  fuse  with  a  fuse  of  a  wrong  ampere
ratings  or  other  wires  when  a  fuse  blows  out.  Use  of  wire
or copper wire may cause the unit to break down or cause
a fire.

CAUTION

After  a  long  use,  check  the  unit  stand  and  fitting  for
damage. If damaged, the unit may fall and result in injury.

CAUTION

Before  accessing  terminal  devices,  make  sure  to  interrupt
all power supply.

DANGER: RISK OF ELECTROCUTION

To  clean  the  air  conditioner  or  air  filter,  be  sure  to  stop
operation  and  turn  all  power  supplies  OFF.  Otherwise,  an
electrical shock and injury may result.

WARNING

Be careful with ladders when working in high places.

7.2

Cleaning the air filter and air outlet

7.2.1

To clean the air outlet

WARNING

Do  NOT  let  the  indoor  unit  get  wet. 

Possible

consequence: 

Electrical shock or fire.

NOTICE

▪ Do  NOT  use  gasoline,  benzene,  thinner  polishing

powder  or  liquid  insecticide. 

Possible  consequence:

Discoloration and deformation.

▪ Do  NOT  use  water  or  air  of  50°C  or  higher. 

Possible

consequence: 

Discoloration and deformation.

Clean with a soft cloth. If it is difficult to remove stains, use water or
a neutral detergent.

7.2.2

To clean the air filter

When to clean the air filter:

▪ Rule  of  thumb:  Clean  every  6  months.  If  the  air  in  the  room  is

extremely contaminated, increase the cleaning frequency.

▪ Depending  on  the  settings,  the  user  interface  can  display  the

"Time  to  clean  filter" 

notification.  Clean  the  air  filter  when  the

notification is displayed.

▪ If  the  dirt  becomes  impossible  to  clean,  change  the  air  filter

(= optional equipment).

How to clean the air filter:

NOTICE

Do  NOT  use  water  of  50°C  or  higher. 

Possible

consequence: 

Discoloration and deformation.

1

Remove  the  air  filter.

  Pull  its  cloth  upward  (in  case  of  rear

suction) or backward (in case of bottom suction).

rear suction

bottom suction

Summary of Contents for FXSN71A2VEB

Page 1: ...Installation and operation manual CO Conveni Pack indoor unit English Installation and operation manual CO Conveni Pack indoor unit FXSN50A2VEB FXSN71A2VEB FXSN112A2VEB...

Page 2: ...fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi...

Page 3: ...9 13 2 To connect the electrical wiring to the indoor unit 19 13 3 To connect appropriate measures for appliances filled with CO 20 14 Commissioning 20 14 1 Checklist before commissioning 20 14 2 To p...

Page 4: ...f valve from liquid pipe to gas pipe When the safety shut off valves close and no measures are installed increased pressure may damage the liquid piping Installing the ducting see 11 2 2 Guidelines wh...

Page 5: ...ning use of the appliance in a safe way and understand the hazards involved Children SHALL NOT play with the appliance Cleaning and user maintenance SHALL NOT be made by children without supervision W...

Page 6: ...y if equipment with burner is used together with the system CAUTION Do NOT operate the system when using a room fumigation type insecticide Chemicals could collect in the unit and endanger the health...

Page 7: ...ubleshooting see 8 Troubleshooting 410 WARNING Stop operation and shut OFF the power if anything unusual occurs burning smells etc Leaving the unit running under such circumstances may cause breakage...

Page 8: ...umidity is beyond these conditions safety devices may be put in action and the air conditioner may not operate 6 2 About operation modes INFORMATION Depending on the installed system some operation mo...

Page 9: ...ilter suction grille air outlet and outside panels WARNING NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit...

Page 10: ...interface only for Madoka with buzzer see option list or from another safety alarm in combination with a CO2 refrigerant leak detector field supply Actions required by the user 1 Ventilate the room an...

Page 11: ...terface operation lamp or display blinks Check if the air filter is clogged see 7 2 2 To clean the air filter 49 Check if air inlet or outlet of outdoor or indoor unit is not blocked by obstacles Remo...

Page 12: ...rd WARNING Make sure to install all necessary countermeasures in case of refrigerant leakage according to standard EN378 see 11 1 2 Additional installation site requirements for CO refrigerant 413 Mak...

Page 13: ...safety alarm in combination with a CO2 refrigerant leak detector a safety alarm alone is NOT considered an appropriate measure where occupants are restricted in their movements CO2 refrigerant leak de...

Page 14: ...5 20 25 30 35 40 45 50 55 60 65 70 d b a RCL QLAV QLMV c 11 3 Example graph for calculation A Refrigerant charge limit B Room volume a Installation is not allowed b 2 appropriate measures required c 1...

Page 15: ...the drain pan or the air filter If the metal duct passes through a metal lath wire lath or metal plate of the wooden structure separate the duct and wall electrically Install the outlet grille in a po...

Page 16: ...iameter field supply d Hanging bars field supply Combining drain pipes You can combine drain pipes Make sure to use drain pipes and T joints with the correct gauge for the operating capacity of the un...

Page 17: ...the reference guide or the service manual of the user interface 2 Gradually pour approximately 1 l of water through the water inlet and check for leaks see When installation of the system is not yet...

Page 18: ...ending on its location in the system Use K65 unions and fittings approved for a working pressure of 120 bar or 90 bar depending on its location in the system ONLY brazing is allowed for connection of...

Page 19: ...wiring and power supply wiring may cross but may NOT run parallel 1 Remove the service cover 2 User interface cable Route the cable through the frame connect the cable to the terminal block symbols P1...

Page 20: ...T1 T2 3 If the CO2 refrigerant leak detector is installed enable the function for refrigerant leak detection as described in 15 1 Field setting 421 P1P2 F1 F2 T1 T2 P1P2 P1P2 P1P2 F1 F2 T1 T2 P1P2 F1...

Page 21: ...ion To set bottom suction or rear suction installation If you have an installation with Then 1 M SW C1 C2 Rear suction 13 23 11 01 Bottom suction 02 To set automatic airflow adjustment The automatic a...

Page 22: ...nit Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by in the part code Symbol Meaning Symbol Meaning Circuit breaker Protective earth Con...

Page 23: ...ant leak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge a...

Page 24: ...4P602815 1F 2021 07 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: