Daikin FXSN71A2VEB Installation And Operation Manual Download Page 14

11 Unit installation

Installation and operation manual

14

FXSN50~112A2VEB

CO

 Conveni-Pack: indoor unit

4P602815-1F – 2021.07

Example: 

Total refrigerant charge in the system is 45 kg and room

volume  is  300  m

3

.  45/300=0.15,  which  is  >QLMV  (0.074)  and

<QLAV (0.18), therefore install at least 1 appropriate measure in the
room.

A (kg)

B (m³)

0

0

100 150

50

200 250

300

350

450

550

400

500

600 650 700 750 800 850 900 950 1000

5

10

15

20

25

30

35

40

45

50

55

60

65

70

  

c

b

a

QLMV

QLAV

  11‒2 Example graph for calculation

A

Refrigerant charge

B

Room volume

a

2 appropriate measures required

b

1 appropriate measure required

c

No measure required

For occupancies on the lowest underground floor of the
building

If the total refrigerant charge
(kg) divided by the room
volume

(a)

 (m

3

) is…

…the number of appropriate
measures must be at least…

<RCL

0

>RCL and ≤QLMV

1

>QLMV and <QLAV

2

>QLAV

Value CANNOT be exceeded!

(a)

For occupied spaces with a floor area exceeding 250 m

2

, use

250 m

2

 as the floor area for determination of the room volume

(

Example: 

 even if the room area is 300 m

2

 and the room height

is 2.5 m, calculate the room volume as 250 m

2

×2.5 m=625 m

3

)

Example: 

Total refrigerant change in the system is 45 kg and room

volume is 300 m

3

. 45/300=0.15, which is >RCL (0.072) and <QLAV

(0.18), therefore install at least 2 appropriate measures in the room.

A (kg)

B (m³)

0

0

100 150

50

200 250

300

350

450

550

400

500

600 650 700 750 800 850 900 950 1000

5

10

15

20

25

30

35

40

45

50

55

60

65

70

  

d

b

a

RCL

QLAV

QLMV

c

  11‒3 Example graph for calculation

A

Refrigerant charge limit

B

Room volume

a

Installation is not allowed

b

2 appropriate measures required

c

1 appropriate measure required

d

No measure required

INFORMATION

Even if there is no refrigerating system on the lowest floor,
where  the  largest  system  charge  (kg)  in  the  building
divided by total volume of the lowest floor (m

3

) exceed the

value  for  QLMV,  provide  a  mechanical  ventilation  in
accordance with EN 378-3:2016.

11.2

Mounting the indoor unit

11.2.1

Guidelines when installing the indoor unit

INFORMATION

Optional  equipment.

  When  installing  optional  equipment,

also read the installation manual of the optional equipment.
Depending  on  the  field  conditions,  it  might  be  easier  to
install the optional equipment first.

Installation options

INFORMATION

The unit can be used with bottom suction by replacing the
interchangeable plate by the air filter holding plate.

b

a

a

a

Air filter holding plate with air filter(s)

b

Interchangeable plate

Ceiling  strength.

  Check  whether  the  ceiling  is  strong  enough  to

support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.

▪ For existing ceilings, use anchors.

▪ For  new  ceilings,  use  sunken  inserts,  sunken  anchors  or  other

field supplied parts.

b

a

c

e

d

a

Anchor

b

Ceiling slab

c

Long nut or turn-buckle

d

Suspension bolt

e

Indoor unit

Suspension  bolts.

  Use  M10  suspension  bolts  for  installation.

Attach  the  hanger  bracket  to  the  suspension  bolt.  Fix  it  securely
using  a  nut  and  washer  from  the  upper  and  lower  sides  of  the
hanger bracket.

Summary of Contents for FXSN71A2VEB

Page 1: ...Installation and operation manual CO Conveni Pack indoor unit English Installation and operation manual CO Conveni Pack indoor unit FXSN50A2VEB FXSN71A2VEB FXSN112A2VEB...

Page 2: ...fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi...

Page 3: ...9 13 2 To connect the electrical wiring to the indoor unit 19 13 3 To connect appropriate measures for appliances filled with CO 20 14 Commissioning 20 14 1 Checklist before commissioning 20 14 2 To p...

Page 4: ...f valve from liquid pipe to gas pipe When the safety shut off valves close and no measures are installed increased pressure may damage the liquid piping Installing the ducting see 11 2 2 Guidelines wh...

Page 5: ...ning use of the appliance in a safe way and understand the hazards involved Children SHALL NOT play with the appliance Cleaning and user maintenance SHALL NOT be made by children without supervision W...

Page 6: ...y if equipment with burner is used together with the system CAUTION Do NOT operate the system when using a room fumigation type insecticide Chemicals could collect in the unit and endanger the health...

Page 7: ...ubleshooting see 8 Troubleshooting 410 WARNING Stop operation and shut OFF the power if anything unusual occurs burning smells etc Leaving the unit running under such circumstances may cause breakage...

Page 8: ...umidity is beyond these conditions safety devices may be put in action and the air conditioner may not operate 6 2 About operation modes INFORMATION Depending on the installed system some operation mo...

Page 9: ...ilter suction grille air outlet and outside panels WARNING NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit...

Page 10: ...interface only for Madoka with buzzer see option list or from another safety alarm in combination with a CO2 refrigerant leak detector field supply Actions required by the user 1 Ventilate the room an...

Page 11: ...terface operation lamp or display blinks Check if the air filter is clogged see 7 2 2 To clean the air filter 49 Check if air inlet or outlet of outdoor or indoor unit is not blocked by obstacles Remo...

Page 12: ...rd WARNING Make sure to install all necessary countermeasures in case of refrigerant leakage according to standard EN378 see 11 1 2 Additional installation site requirements for CO refrigerant 413 Mak...

Page 13: ...safety alarm in combination with a CO2 refrigerant leak detector a safety alarm alone is NOT considered an appropriate measure where occupants are restricted in their movements CO2 refrigerant leak de...

Page 14: ...5 20 25 30 35 40 45 50 55 60 65 70 d b a RCL QLAV QLMV c 11 3 Example graph for calculation A Refrigerant charge limit B Room volume a Installation is not allowed b 2 appropriate measures required c 1...

Page 15: ...the drain pan or the air filter If the metal duct passes through a metal lath wire lath or metal plate of the wooden structure separate the duct and wall electrically Install the outlet grille in a po...

Page 16: ...iameter field supply d Hanging bars field supply Combining drain pipes You can combine drain pipes Make sure to use drain pipes and T joints with the correct gauge for the operating capacity of the un...

Page 17: ...the reference guide or the service manual of the user interface 2 Gradually pour approximately 1 l of water through the water inlet and check for leaks see When installation of the system is not yet...

Page 18: ...ending on its location in the system Use K65 unions and fittings approved for a working pressure of 120 bar or 90 bar depending on its location in the system ONLY brazing is allowed for connection of...

Page 19: ...wiring and power supply wiring may cross but may NOT run parallel 1 Remove the service cover 2 User interface cable Route the cable through the frame connect the cable to the terminal block symbols P1...

Page 20: ...T1 T2 3 If the CO2 refrigerant leak detector is installed enable the function for refrigerant leak detection as described in 15 1 Field setting 421 P1P2 F1 F2 T1 T2 P1P2 P1P2 P1P2 F1 F2 T1 T2 P1P2 F1...

Page 21: ...ion To set bottom suction or rear suction installation If you have an installation with Then 1 M SW C1 C2 Rear suction 13 23 11 01 Bottom suction 02 To set automatic airflow adjustment The automatic a...

Page 22: ...nit Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by in the part code Symbol Meaning Symbol Meaning Circuit breaker Protective earth Con...

Page 23: ...ant leak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge a...

Page 24: ...4P602815 1F 2021 07 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: