background image

 

FXLQ20~6 FXNQ20~63P2VEB
VRV System air conditioners
4P323720-1 – 2012.06

Installation and operation manual

6

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

Do not use anti-oxidants when brazing the pipe joints. Residue
can clog pipes and break equipment.

Do not use flux when brazing copper-to-copper refrigerant
piping. Use phosphor copper brazing filler alloy (BCuP) which
does not require flux.

Flux has an extremely harmful influence on refrigerant piping
systems. For instance, if chlorine based flux is used, it will cause
pipe corrosion or, in particular, if the flux contains fluorine, it will
deteriorate the refrigerant oil.

Use R410A only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R410A installations to
withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
Vacuum pump:
Use a 2-stage vacuum pump with a non-return valve
Make sure the pump oil does not flow oppositely into the system
while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa
(5 Torr, –755 mm Hg).

Drain piping work

Rig the drain pipe as shown below. Improperly rigged piping could
lead to leaks and eventually wet furniture and belongings.

1

Carry out the drain piping
Connect the drain hose (accessory part) using the attached
hose and parts, as shown in the figure below.

2

If converging multiple drain pipes, install according to the
procedure shown below. Use a slope downwards at a gradient of
at least 1/100.

Select converging drain pipes with a size that is suitable for the
operating capacity of the unit.

3

After piping work is finished, check if drainage flows smoothly.
Pour approximately 1 liter of water slowly in the air outlet and
check drainage flow.

4

Be sure to insulate all indoor pipes.

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

1

2

3

4

5

6

6

1

Drip pan

2

Drain hose (accessory part)

3

Metal clamp (accessory part)

4

3/4" drain pipe

5

Cut to a suitable length 

6

Slope

Drain piping connections

Do not connect the drain piping directly to sewage
pipes that smell of ammonia. The ammonia in the
sewage might enter the indoor unit through the drain
pipes and corrode the heat exchanger.

Keep in mind that the drain pipe will become blocked
if water remains in the drain pipe.

2

3

5

4

6

1

/1

00

Piping process inside unit

1/100

Summary of Contents for FXLQ20P2VEB

Page 1: ...NSTALLATION AND OPERATION MANUAL FXLQ20P2VEB FXLQ25P2VEB FXLQ32P2VEB FXLQ40P2VEB FXLQ50P2VEB FXLQ63P2VEB FXNQ20P2VEB FXNQ25P2VEB FXNQ32P2VEB FXNQ40P2VEB FXNQ50P2VEB FXNQ63P2VEB System air conditioners...

Page 2: ...D OUT D F1 F2 F1 F2 Control box L N L N P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 4 2 L N L N L N L N 2 1 2 3 7 9 8 10 4 5 6 L N IN D OUT D F1...

Page 3: ...B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo c...

Page 4: ...d below Places with mineral oil or filled with oil vapour or spray like in kitchens Plastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corr...

Page 5: ...class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures Keep indoor unit outdoor unit power supply wiring a...

Page 6: ...otating the discharge grille NOTE Make sure no short circuit of air is caused when placing the unit directly under a windowsill 100 100 1000 20 A B C C A 1750 B 1750 C B b 20 20 C A A B C B Model 20 2...

Page 7: ...alling over either fasten to the wall using the holes provided or fasten to the floor with a field supplied floor fastener Wallmounted installation 1 Positioning of holes for fastening to the wall Uni...

Page 8: ...ghtening torque Overtightening may damage the flare and cause leaks When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand be...

Page 9: ...ure from mixing into the system Vacuum pump Use a 2 stage vacuum pump with a non return valve Make sure the pump oil does not flow oppositely into the system while the pump is not working Use a vacuum...

Page 10: ...to the table below When attaching the control box lid make sure not to pinch any wires and make sure that the wiring does not come in contact with the piping and sharp edges After all wiring connectio...

Page 11: ...0 6 16 0 025 0 5 50 0 6 16 0 035 0 5 63 0 6 16 0 035 0 5 MCA Minimum Circuit Amps A MFA Maximum Fuse Amps A FLA Full Load Amps A NOTE For details refer to Electrical data in the technical data book P...

Page 12: ...operation 1 Wire specifications and how to perform wiring Connect input from outside to terminals T1 and T2 of the terminal board remote controller to transmission wiring 2 Actuation The following ta...

Page 13: ...t been finished Error code Meaning There is a short circuit at the forced off terminals T1 T2 U4 or UH The power on the outdoor unit is off The outdoor unit has not been wired for power supply Incorre...

Page 14: ...the air filter make sure to attach it Turn on the main power supply switch The control panel display lights up when the power is turned on To protect the unit turn on the main power switch at least 6...

Page 15: ...TIONAL ACCESSORY X18A CONNECTOR WIRING ADAPTOR FOR ELECTRICAL APPENDICES WIRED REMOTE CONTROLLER R1T THERMISTOR AIR SS1 SELECTOR SWITCH MAIN SUB TERMINAL BLOCK BLK BLACK PNK PINK CONNECTOR BLU BLUE RE...

Page 16: ...Copyright 2012 Daikin 4P323720 1 2012 06...

Reviews: