![background image](http://html1.mh-extra.com/html/daikin/fxlq-p/fxlq-p_technical-data-manual_2459762012.webp)
• Indoor Unit • FXLQ-P
5
• VRV Systems • FXLQ-P
10
5
Capacity tables
5 - 3
Capacity Correction Factor
20°CDB
23°CDB
26°CDB
27°CDB
28°CDB
30°CDB
32°CDB
14°CWB
16°CWB
18°CWB
19°CWB
20°CWB
22°CWB
24°CWB
20
TC ratio
0,527
0,540
0,601
0,638
0,671
0,727
0,768
SHF ratio
1,205
1,300
1,249
1,196
1,157
1,101
1,063
25
TC ratio
0,527
0,542
0,604
0,642
0,675
0,730
0,771
SHF ratio
1,206
1,301
1,247
1,194
1,155
1,099
1,063
32
TC ratio
0,525
0,538
0,600
0,637
0,669
0,725
0,769
SHF ratio
1,212
1,308
1,249
1,197
1,158
1,100
1,061
40
TC ratio
0,533
0,553
0,610
0,648
0,681
0,731
0,771
SHF ratio
1,184
1,274
1,238
1,187
1,150
1,100
1,070
50
TC ratio
0,530
0,545
0,601
0,639
0,672
0,727
0,768
SHF ratio
1,194
1,288
1,247
1,195
1,156
1,101
1,064
63
TC ratio
0,535
0,553
0,608
0,646
0,678
0,729
0,769
SHF ratio
1,179
1,269
1,238
1,188
1,151
1,103
1,075
FXLQ-P
4TW27232-9
Capacity correction factor Te = 11°C