background image

15 Finishing the indoor unit installation

Installation and operation manual

20

FXHQ-A

VRV system air conditioner

3P668115-3E – 2022.11

15

Finishing the indoor unit
installation

NOTICE

Block  any  gaps  around  pipes  and  cables  with  sealing
material (accessory) to avoid dust from entering the indoor
unit.

15.1

To mount the suction grille and
decoration side panel

1

Install  securely  in  the  reverse  order.  Refer  to 

"To  open  the

indoor unit"

 [

4

 14].

2

When installing the suction grille, attach the strap of the suction
grille to the hook on the indoor unit.

INFORMATION

When closing the suction grille, make sure the straps of the
suction grille are not pinched anywhere.

a
c

d

e

c

b

a

b

b
f

a

Round hole

b

Hook

c

Strap

d

Indoor unit

e

Suction grille

f

Cross-shaped hole

16

Commissioning

NOTICE

General 

commissioning 

checklist.

 

Next 

to 

the

commissioning  instructions  in  this  chapter,  a  general
commissioning  checklist  is  also  available  on  the  Daikin
Business Portal (authentication required).

The  general  commissioning  checklist  is  complementary  to
the  instructions  in  this  chapter  and  can  be  used  as  a
guideline and reporting template during commissioning and
hand-over to the user.

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

16.1

Checklist before commissioning

1

After the installation of the unit, check the items listed below.

2

Close the unit.

3

Power up the unit.

You  have  read  the  complete  installation  and  operation
instructions described in the 

installer and user reference

guide

.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The 

drain  piping

  is  properly  installed  and  insulated,  and

drainage flows smoothly. Check for water leaks.

Possible consequence: 

condensate water might drip.

The 

refrigerant  pipes

  (gas  and  liquid)  are  installed

correctly and thermally insulated.

There are NO 

refrigerant leaks

.

There are NO 

missing phases

 or 

reversed phases

.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

16.2

To perform a test run

INFORMATION

▪ Perform the test run according to the instructions in the

outdoor unit manual.

▪ The test run is only completed if there is no malfunction

code displayed on the user interface or the outdoor unit
7‑segment display.

▪ See  the  service  manual  for  the  complete  list  of  error

codes and a detailed troubleshooting guideline for each
error.

NOTICE

Do NOT interrupt the test run.

17

Configuration

17.1

Field setting

Make  the  following  field  settings  so  that  they  correspond  with  the
actual installation setup and with the needs of the user:

▪ Ceiling height

▪ Air volume when thermostat control is OFF

▪ Time to clean air filter

▪ Thermostat sensor selection

▪ Thermostat sensor in group control

▪ Thermostat differential changeover (if remote sensor is used)

▪ Automatic changeover differential

▪ Auto-restart after power failure

▪ T1/T2 input setting

Summary of Contents for FXHQ32AVEB8

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXHQ32AVEB8 FXHQ63AVEB8 FXHQ100AVEB8...

Page 2: ...uojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za pred...

Page 3: ...used in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of B...

Page 4: ...ndard wiring components 18 14 2 To connect the electrical wiring to the indoor unit 18 15 Finishing the indoor unit installation 20 15 1 To mount the suction grille and decoration side panel 20 16 Com...

Page 5: ...s or circuit breakers Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping particularly on the high pressure side Do NOT use taped wires ex...

Page 6: ...alised treatment facility for reuse By ensuring waste batteries are disposed of correctly you will help to prevent potential negative consequences for the environment and human health 3 2 Instructions...

Page 7: ...CAUTION Before accessing terminal devices make sure to interrupt all power supply DANGER RISK OF ELECTROCUTION To clean the air conditioner or air filter be sure to stop operation and turn all power...

Page 8: ...frigerant piping transmission cable g Drain pipe h Suction grille and air filter 5 User interface CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts insi...

Page 9: ...w direction The following airflow directions can be set Up and down direction horizontal blades Using user interface fixed position or swing Left and right direction vertical blades Manually fixed pos...

Page 10: ...r air filter be sure to stop operation and turn all power supplies OFF Otherwise an electrical shock and injury may result WARNING Be careful with ladders when working in high places NOTICE When clean...

Page 11: ...ilter 410 4 Clean the suction grille Wash with a soft bristle brush and water or neutral detergent If the suction grille is very dirty use a typical kitchen cleaner leave it on for 10 min then wash it...

Page 12: ...arranty card 9 Relocation Contact your dealer to remove and reinstall the entire unit Moving units requires technical expertise 10 Disposal NOTICE Do NOT try to dismantle the system yourself dismantli...

Page 13: ...lation Attach the hanger bracket to the suspension bolt Fix it securely using a nut and washer on the top and bottom of the hanger bracket Front view 5 175 200 c b a G H J mm Top ceiling view mm F 210...

Page 14: ...r to remove it a c b b b d c 10 mm a Hanger bracket fixing screw M5 b Hanger bracket installation bolt M8 c Hanger bracket d Indoor unit CAUTION Do NOT remove the milky white tape from the exterior of...

Page 15: ...ws 63 class 11 screws 100 class 10 screws a a a a b a Fixing screw for protective grille b Protective grille 2 Remove the cap from the drain socket and remove the insulation material from the left sid...

Page 16: ...ng installation 13 1 Preparing refrigerant piping 13 1 1 Refrigerant piping requirements CAUTION Piping MUST be installed according to instructions given in 13 Piping installation 416 Only mechanical...

Page 17: ...Clamp of the pipe port cover b Cables except cable of expansion valve Upward piping INFORMATION L shaped connection piping kit optional accessory is required 1 Remove the top pipe port cover and cut o...

Page 18: ...60 Hz Phase 1 Current FXHQ32 63 0 8 A FXHQ100 1 6 A Components Power supply cable MUST comply with national wiring regulation 3 core cable Wire size based on the current but not less than 1 5 mm2 Tra...

Page 19: ...User interface cable and transmission cable i Rear piping cover j Large cut out hole k Connection of user interface cable and transmission cable l Connection of power supply cable m Wiring fixture fi...

Page 20: ...indoor unit is properly mounted The outdoor unit is properly mounted The drain piping is properly installed and insulated and drainage flows smoothly Check for water leaks Possible consequence condens...

Page 21: ...at sensor selection This setting must correspond with how if the user interface thermostat sensor is used When the user interface thermostat sensor is Then 1 M SW Used in combination with indoor unit...

Page 22: ...d OFF 12 22 1 01 ON OFF Operation 02 Emergency recommended for alarm operation 03 Forced OFF multi tenant 04 18 Technical data A subset of the latest technical data is available on the regional Daikin...

Page 23: ...PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R T The...

Page 24: ...3P668115 3E 2022 11 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: