13 Piping installation

Installation and operation manual

17

FXHQ-A
VRV system air conditioner
3P668115-3E – 2022.11

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

13.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

13.2.1

To connect the refrigerant piping to the
indoor unit

Refrigerant piping can be connected from following directions:

a

b

c

a

Rear right piping

b

Right piping

c

Upward piping

Rear right piping

1

Remove the rear piping pipe port cover and cut out the holes for
piping. When cutting out the holes, make sure to avoid the knob
part of the cover.

a

b

a

Rear refrigerant piping

b

Rear piping pipe port cover

2

Run the field supply pipes through the cut out holes.

3

After the drain and refrigerant piping is finished, install the pipe
port cover back. Run all the cables (except cable of expansion
valve) through the clamp of the pipe port cover and fix.

a b c

a

Clamp of the pipe port cover

b

Cables (except cable of expansion valve)

Upward piping

INFORMATION

L-shaped  connection  piping  kit  (optional  accessory)  is
required.

1

Remove the top pipe port cover and cut out the holes for piping.
When cutting out the holes, make sure to avoid the knob part of
the  cover.  Use  an  L-shaped  connection  piping  kit  (optional
accessory)  for  the  piping.  Run  the  pipes  through  the  cut  out
holes.

a

b

a

Upward refrigerant piping

b

Top pipe port cover

Right piping

1

Remove the reinforcing plate at the right side and put back the
screw in the original position on the indoor unit.

2

Remove the decoration side panel.

3

Remove the rectangular part of the decoration side panel.

a b

e

f

d

c

a

Round part

b

Rectangular part of the decoration side panel

c

Decoration side panel

d

Screw

e

Reinforcing plate

f

Right refrigerant piping

4

After  the  drain  and  refrigerant  piping  is  finished,  install  the
reinforcing  plate  (optional  step)  and  the  decoration  side  panel
back.

a

c

b

a

Screw

b

Reinforcing plate

c

Decoration side panel

Pipe length

. Keep refrigerant piping as short as possible.

Flare  connections

.  Connect  refrigerant  piping  to  the  unit  using

flare connections.

Insulation

.  Insulate  the  refrigerant  piping  on  the  indoor  unit  as

follows:

Summary of Contents for FXHQ32AVEB8

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXHQ32AVEB8 FXHQ63AVEB8 FXHQ100AVEB8...

Page 2: ...uojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za pred...

Page 3: ...used in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of B...

Page 4: ...ndard wiring components 18 14 2 To connect the electrical wiring to the indoor unit 18 15 Finishing the indoor unit installation 20 15 1 To mount the suction grille and decoration side panel 20 16 Com...

Page 5: ...s or circuit breakers Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping particularly on the high pressure side Do NOT use taped wires ex...

Page 6: ...alised treatment facility for reuse By ensuring waste batteries are disposed of correctly you will help to prevent potential negative consequences for the environment and human health 3 2 Instructions...

Page 7: ...CAUTION Before accessing terminal devices make sure to interrupt all power supply DANGER RISK OF ELECTROCUTION To clean the air conditioner or air filter be sure to stop operation and turn all power...

Page 8: ...frigerant piping transmission cable g Drain pipe h Suction grille and air filter 5 User interface CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts insi...

Page 9: ...w direction The following airflow directions can be set Up and down direction horizontal blades Using user interface fixed position or swing Left and right direction vertical blades Manually fixed pos...

Page 10: ...r air filter be sure to stop operation and turn all power supplies OFF Otherwise an electrical shock and injury may result WARNING Be careful with ladders when working in high places NOTICE When clean...

Page 11: ...ilter 410 4 Clean the suction grille Wash with a soft bristle brush and water or neutral detergent If the suction grille is very dirty use a typical kitchen cleaner leave it on for 10 min then wash it...

Page 12: ...arranty card 9 Relocation Contact your dealer to remove and reinstall the entire unit Moving units requires technical expertise 10 Disposal NOTICE Do NOT try to dismantle the system yourself dismantli...

Page 13: ...lation Attach the hanger bracket to the suspension bolt Fix it securely using a nut and washer on the top and bottom of the hanger bracket Front view 5 175 200 c b a G H J mm Top ceiling view mm F 210...

Page 14: ...r to remove it a c b b b d c 10 mm a Hanger bracket fixing screw M5 b Hanger bracket installation bolt M8 c Hanger bracket d Indoor unit CAUTION Do NOT remove the milky white tape from the exterior of...

Page 15: ...ws 63 class 11 screws 100 class 10 screws a a a a b a Fixing screw for protective grille b Protective grille 2 Remove the cap from the drain socket and remove the insulation material from the left sid...

Page 16: ...ng installation 13 1 Preparing refrigerant piping 13 1 1 Refrigerant piping requirements CAUTION Piping MUST be installed according to instructions given in 13 Piping installation 416 Only mechanical...

Page 17: ...Clamp of the pipe port cover b Cables except cable of expansion valve Upward piping INFORMATION L shaped connection piping kit optional accessory is required 1 Remove the top pipe port cover and cut o...

Page 18: ...60 Hz Phase 1 Current FXHQ32 63 0 8 A FXHQ100 1 6 A Components Power supply cable MUST comply with national wiring regulation 3 core cable Wire size based on the current but not less than 1 5 mm2 Tra...

Page 19: ...User interface cable and transmission cable i Rear piping cover j Large cut out hole k Connection of user interface cable and transmission cable l Connection of power supply cable m Wiring fixture fi...

Page 20: ...indoor unit is properly mounted The outdoor unit is properly mounted The drain piping is properly installed and insulated and drainage flows smoothly Check for water leaks Possible consequence condens...

Page 21: ...at sensor selection This setting must correspond with how if the user interface thermostat sensor is used When the user interface thermostat sensor is Then 1 M SW Used in combination with indoor unit...

Page 22: ...d OFF 12 22 1 01 ON OFF Operation 02 Emergency recommended for alarm operation 03 Forced OFF multi tenant 04 18 Technical data A subset of the latest technical data is available on the regional Daikin...

Page 23: ...PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R T The...

Page 24: ...3P668115 3E 2022 11 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: