background image

9

• When piping is complete, cut the removed penetration lid into 

the shape of the pipe using scissors and attach.
As when before removing the top penetration lid, secure the 
lead lines for the swing motor and thermistor by passing them 
through the clamp section on the top penetration lid.

(Refer to Fig. 18, 20)

• When doing this, block any gaps between the pipe penetra-

tion lid and the pipes using putty to prevent dust from enter-
ing the indoor unit.

7.

DRAIN PIPING WORK

(1) Carry out the drain piping.

• Make sure piping provides proper drainage.
• You can select whether to bring the drain piping out from the 

rear right or right. For rear right-facing and right-facing situa-
tions, refer to “6. REFRIGERANT PIPING WORK” on page 7.

• Make sure the pipe diameter is the same or bigger than the 

branch piping. (vinyl-chloride piping, nominal diameter 1 in., 
external diameter 1 1/4 in.)

• Make sure the piping is short, has at least a 1/100 slope, and 

can prevent air pockets from forming. 

(Refer to Fig. 21)

• Do not allow any slack to gather in the drain pipe inside the 

indoor unit.
(Slack in the drain pipe can cause the suction grille to break.

)

CAUTION

• Water accumulating in the drain piping can cause the drain to 

clog.

• Be sure to use the drain pipe (1) and metal clamp (2).

Also, insert the drain pipe completely into the drain socket, and 
securely attach the metal clamp bracket inside the gray tape 
area on the inserted tip of the drain pipe. 

(Refer to Fig. 22)

Screw the screws on the metal clamp bracket until there is 5/
32 in. left. (Pay attention to the direction of the attachment to 
prevent the metal clamp bracket from coming into contact 
with the suction grille.)

 (Refer to Fig. 23)

• Insulate the metal clamp bracket and drain pipe from the bot-

tom using the large sealing pad (8). 

(Refer to Fig. 23)

• Be sure to insulate all drain piping running indoors.

NOTE

• To ensure no excessive pressure is applied to the drain pipe 

(1), do not bend or twist when installing. (This may cause 
leakage.)

• If converging multiple drain pipes, install according to the pro-

cedure shown below.

Select converging drain pipes whose gauge is suitable for the 
operating capacity of the unit.

Top plate

Top penetration lid

Cut out

Fig. 18

 (A figure from an inside bottom)

This hole not using it.

Fig. 19

Upward-facing 
refrigerant pipe 
L-shaped branch pipe 
kit (Optional accessories)

Top penetration 
lid clamp section

Thermistor lead line

Swing motor 
lead line

Fig. 20

 (A figure from an inside bottom)

Tilt down

Do not lift Make sure there 

is no slack

Make sure it is 
not in the water

Good

Wrong

Fig. 21

Taping area (Gray)

Drain pipe (1)

Metal clamp (2)

Fig. 22

Large sealing pad (8)

Metal clamp (2)

< Facing rear right or right >

5/32 or less

Fig. 23

(Length : in.)

3 7/8 or more

T-joint converging drain pipes

Slope downwards at a gradient 
of at least 1/100

(Length : in.)

Summary of Contents for FXHQ12MVJU

Page 1: ...U FXHQ24MVJU FXHQ36MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual sh...

Page 2: ...ly Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could result in severe injury or death After completing...

Page 3: ...ng distance can result shorter than expected in rooms with elec tronic fluorescent lamps inverter or rapid start types Install the indoor unit as far away from fluorescent lamps as possible In a domes...

Page 4: ...lammable materials are present due to risk of explosion resulting in serious injury or death WARNING If the supporting structural members are not strong enough to take the unit s weight the unit could...

Page 5: ...unit 3 1 Detach the suction grille Slide the locking knobs 2 on the suction grille inward direction of arrows and lift upwards Refer to Fig 1 With the suction grille open remove the suction grille for...

Page 6: ...e sure to use the provided accessories and specified parts designated by our company 1 Secure the hanger brackets to the suspension bolts Refer to Fig 10 NOTE To ensure they are safely secured use the...

Page 7: ...oximately 250 F so use insulation pipe cover which is sufficiently resistant Also in cases where the temperature and humidity of the refrigerant pipe sections might exceed 86 F or RH 80 reinforce the...

Page 8: ...asten both ends with the clamps 4 Refer to Fig 16 Wrap the small sealing pad 9 only around the insulation for the joints on the gas piping side Refer to Fig 16 1 For piping facing back Remove the rear...

Page 9: ...the drain socket and securely attach the metal clamp bracket inside the gray tape area on the inserted tip of the drain pipe Refer to Fig 22 Screw the screws on the metal clamp bracket until there is...

Page 10: ...sion wire between indoor out door units and between the indoor unit and the remote con troller wire are as follows 1 Outdoor unit Indoor unit Max 3280 ft Total wire length 6560 ft 2 Indoor unit Remote...

Page 11: ...result in overheating and in worse case result in electric shock or fire CAUTION To avoid a short circuit in the electric parts box be sure to apply sealing material or putty not included to the wiri...

Page 12: ...TION GRILLE THE DECORATION PANELS AND THE PROTECTION NET Once wiring is complete firmly attach the control box lid the suction grille the decoration panels and the protection net in the order opposite...

Page 13: ...the upper part The remote controller PC board is attached to the upper part of remote controller Refer to Fig 35 2 Turn the MAIN SUB changeover switch on one of the 2 remote controllers PC boards to...

Page 14: ...ill be displayed for a few seconds on the remote controller immediately after the power is turned on This display indicates that the remote controller is being checked to see whether it is ok or not a...

Page 15: ...s fault The remote controller thermistor does not function but the system thermo run is possible E3 High pressure abnormal outdoor unit E4 Low pressure abnormal outdoor unit ON OFF TEST SWING TEST E5...

Page 16: ...0510 FS 3PN06240 1E EM04A049B...

Reviews: