background image

15

(3) Press the OPERATION MODE SELECTOR button and 

upper figure of the malfunction code flashes.

(4) Continue pressing the PROGRAMMING TIME button 

unit it makes 2 short beeps and find the upper code.

(5) Press the OPERATION MODE SELECTOR button and 

lower figure of the malfunction code flashes.

(6) Continue pressing the PROGRAMMING TIME button 

unit it makes a long beep and find the lower code.

• A long beep indicate the malfunction code.

NOTE

1. In case wired remote controller. Press the INSPECTION /

TEST OPERATION button on remote controller, “ 

 ” 

starts flashing.

2. Keep down the ON/OFF button for 5 seconds or longer in 

the inspection mode and the above trouble history disap-
pears, after the trouble code goes on and off twice, followed 

by the code “

”(normal).

The display changes from the inspection mode to the nor-
mal mode.

12-2 MALFUNCTION CODE

• For places where the malfunction code is left blank, the “

” 

indication is not displayed. Though the system continues 
operating, be sure to inspect the system and make repairs as 
necessary.

• Depending on the type of indoor or outdoor unit, the malfunc-

tion code may or may not be displayed.

Order

Operation

(1)

Open gas side stop valve. 

(2)

Open liquid side stop valve.

(3)

Electrify crank case heater for 6 hours.

(4)

Set to cooling with the remote controller and push “

” 

button to start operation.

(5)

Push“

”button twice and operate in TEST OPERA-

TION MODE for 3 minutes.

(6)

Push“

”button and confirm its operation.

(7)

Push“

”button and operate normally.

(8)

Confirm its function according to the operation manual.

Code

Malfunction/Remarks

A1

Indoor unit’s PC board faulty

A3

Condensate level abnormal

A6

Indoor fan motor overloaded, overcurrent or locked.

A7

Air flow direction adjust motor is fault.

A9

Drive for electronic expansion valve is fault.

AJ

Type set improper

Capacity data is wrongly preset. Or there is nothing pro-
grammed in the data hold IC.

C4

Sensor R2T for heat exchanger temperature is fault.

C5

Sensor R3T for heat exchanger temperature is fault.

C9

Sensor R1T for suction air temperature is fault.

CJ

Sensor for remote controller is fault.

The remote controller thermistor does not function, but 
the system thermo run is possible.

E3

High pressure abnormal (outdoor unit)

E4

Low pressure abnormal (outdoor unit)

ON/OFF

TEST

SWING

TEST

E5

Compressor motor lock malfunction

E7

Outdoor fan motor lock malfunction
Outdoor fan instantaneous overcurrent malfunction

E9

Electronic expansion valve faulty (outdoor unit)

F3

Discharge pipe temperature abnormal (outdoor unit)

F6

The refrigerant is overcharged.

H9

Outdoor air thermistor faulty (outdoor unit)

J3

Discharge pipe thermistor faulty (outdoor unit)

J5

Suction pipe thermistor faulty (outdoor unit)

J6

Heat exchanger thermistor faulty (outdoor unit)

J9

Sensor for heat exchanger is fault.

JA

Sensor for high pressure is fault.

JC

Sensor for low pressure is fault.

L4

Overheated heat-radiating fin (outdoor)

Inverter cooling defect.

L5

Instantaneous overcurrent (outdoor)

Possible earth fault or short circuit in the compressor 
motor.

L8

Electric thermal (outdoor)

Possible electrical overload in the compressor or cut line 
in the compressor motor.

L9

Stall prevention (outdoor)

Compressor possibly locked.

LC

Transmission malfunction between the outdoor control 
units’ inverters (outdoor)

P1

Open-phase (outdoor)

P3

PC board temperature sensor malfunction (outdoor)

P4

Heat-radiating fin temperature sensor malfunction
(outdoor)

PJ

Type set improper (outdoor unit)

Capacity data is wrongly preset. Or there is nothing pro-
grammed in the data hold IC.

U0

Suction pipe temperature abnormal

U2

Power source voltage malfunction

Includes the defect in K1M.

U3

The check operation has not performed.

U4
UF

Transmission error (indoor unit – outdoor unit)

Miswiring between indoor and outdoor units or malfunc-
tion of the PC board mounted on the indoor and the out-
door units.
If UF is shown, the wire between the indoor and outdoor 
units is not properly wired. Therefore, immediately dis-
connect the power supply and correct the wire. (The 
compressor and the fan mounted on the outdoor unit 
may start operation independent of the remote controller 
operation.) The power is not supplied to outdoor unit.

U9

Same transmission for in / outdoor unit is fault.

UA

Miss setting for multi system

Setting is wrong for selector switch of multi-system. (see 
switch SS2 on the main unit’s PC board)

Summary of Contents for FXHQ12MVJU

Page 1: ...U FXHQ24MVJU FXHQ36MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual sh...

Page 2: ...ly Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could result in severe injury or death After completing...

Page 3: ...ng distance can result shorter than expected in rooms with elec tronic fluorescent lamps inverter or rapid start types Install the indoor unit as far away from fluorescent lamps as possible In a domes...

Page 4: ...lammable materials are present due to risk of explosion resulting in serious injury or death WARNING If the supporting structural members are not strong enough to take the unit s weight the unit could...

Page 5: ...unit 3 1 Detach the suction grille Slide the locking knobs 2 on the suction grille inward direction of arrows and lift upwards Refer to Fig 1 With the suction grille open remove the suction grille for...

Page 6: ...e sure to use the provided accessories and specified parts designated by our company 1 Secure the hanger brackets to the suspension bolts Refer to Fig 10 NOTE To ensure they are safely secured use the...

Page 7: ...oximately 250 F so use insulation pipe cover which is sufficiently resistant Also in cases where the temperature and humidity of the refrigerant pipe sections might exceed 86 F or RH 80 reinforce the...

Page 8: ...asten both ends with the clamps 4 Refer to Fig 16 Wrap the small sealing pad 9 only around the insulation for the joints on the gas piping side Refer to Fig 16 1 For piping facing back Remove the rear...

Page 9: ...the drain socket and securely attach the metal clamp bracket inside the gray tape area on the inserted tip of the drain pipe Refer to Fig 22 Screw the screws on the metal clamp bracket until there is...

Page 10: ...sion wire between indoor out door units and between the indoor unit and the remote con troller wire are as follows 1 Outdoor unit Indoor unit Max 3280 ft Total wire length 6560 ft 2 Indoor unit Remote...

Page 11: ...result in overheating and in worse case result in electric shock or fire CAUTION To avoid a short circuit in the electric parts box be sure to apply sealing material or putty not included to the wiri...

Page 12: ...TION GRILLE THE DECORATION PANELS AND THE PROTECTION NET Once wiring is complete firmly attach the control box lid the suction grille the decoration panels and the protection net in the order opposite...

Page 13: ...the upper part The remote controller PC board is attached to the upper part of remote controller Refer to Fig 35 2 Turn the MAIN SUB changeover switch on one of the 2 remote controllers PC boards to...

Page 14: ...ill be displayed for a few seconds on the remote controller immediately after the power is turned on This display indicates that the remote controller is being checked to see whether it is ok or not a...

Page 15: ...s fault The remote controller thermistor does not function but the system thermo run is possible E3 High pressure abnormal outdoor unit E4 Low pressure abnormal outdoor unit ON OFF TEST SWING TEST E5...

Page 16: ...0510 FS 3PN06240 1E EM04A049B...

Reviews: