• Power supply wire

Holding the control box lid, loosen the 2 securing screws, 
remove the control box lid, match up the phases on the power 
supply terminal block inside (2P), and make the connections.
After this is done, use the attached clamp (4) to bind wire 
between units to the anchor point.

 (Refer to Fig. 28)

• Remote controller wire and transmission wire

Holding the control box lid, loosen the 2 securing screws, 
remove the control box lid.
Thread the remote controller wire and transmission wire 
through the insulating tube (11) and secure with the clamp 
(4), and cut off the insulating tube (11) to suitable length. The 
insulating tube (11) can let the wire pass to 2. If there are 3 or 
more wires, use another insulating tube (11). Pull the wires 
inside through resin bush and connect the wires to the trans-
mission terminal block (6P) inside the control box. After con-
necting, use the clamp (4) to bind the remote controller wire 
together with the transmission wire to the anchor. 

(Refer to 

Fig. 27, 28, 29)

• In the insulating tube (11), it can let the remote controller wire 

and transmission wire pass to 2.

WARNING

• Never connect power supply wiring to the terminal block for 

remote controller wiring as this could damage the entire system.

• Use only specified wire and connect wires to the terminal 

tightly. Be careful wires do not place external stress on termi-
nals. Keep wires in neat order so as to not obstruct other 
equipment. Make sure that the electric box lid fits tightly. 
Incomplete connections could result in overheating and, in 
worse case, result in electric shock or fire.

CAUTION

• To avoid a short circuit in the electric parts box, be sure to 

apply sealing material or putty (not included) to the wiring 
hole to prevent the infiltration of water as well as insects or 
other small creatures.

NOTE

1. Use round crimp-style terminals for connecting wires to the 

power supply terminal block.

If unavailable, observe the following points when wiring.
• Do not connect wires of different gauge to the same 

power supply terminal.
(Looseness in the connection may cause overheating.)

• Use the specified electric wire. Connect the wire securely to 

the terminal. Lock the wire down without applying excessive 
force to the terminal. (Tightening torque : 0.97 ft.lbf ±10%)

Resin bush (10)

Lock nut

Conduit

Conduit hole

Fig. 26

L

 1

POWER  SUPPLY

L

 2

power supply

How to connect power supply
terminal block (2P)

Control box

Transmission
terminal block (6P)

Power supply
teminal block (2P)

Remote controller wire
and transmission wire

Refer to Fig. 28

Ground terminal

Power supply wire

Gas pipe

Liquid pipe

Drain pipe

Conduit

Corking or Putty

Resin bush (10)

Control box 
lid secuing screw (2 pcs.)

Control box lid

Insulating tube (11)

Clamp (4)

Fig. 27

Fastener

Clamp (4)

Clamp (4)

Ground wire

After securing the 
cramp material 
to the bracket, 
cut off any extra 
material.

Remote controller wire and 
transmission wire

Fastener

Power supply wire

Fig. 28

P

1 P2 F1 F2 T1 T2

REMOTE

CNTRL

FORCED

OFF

TRANSMISSION

WIRING

Clamp (4)

Remote controller wire

Transmission
terminal block (6P)

Transmission wire

Insulating
tube (11)

1 in.

Fig. 29

Electric wire

Round crimp-style terminal

Attach insulation sleeve

Connect wires of the 
same gauge to both side.

Summary of Contents for FXHQ12MVJU

Page 1: ...U FXHQ24MVJU FXHQ36MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual sh...

Page 2: ...ly Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan heater stove or cooking device Exposure to this gas could result in severe injury or death After completing...

Page 3: ...ng distance can result shorter than expected in rooms with elec tronic fluorescent lamps inverter or rapid start types Install the indoor unit as far away from fluorescent lamps as possible In a domes...

Page 4: ...lammable materials are present due to risk of explosion resulting in serious injury or death WARNING If the supporting structural members are not strong enough to take the unit s weight the unit could...

Page 5: ...unit 3 1 Detach the suction grille Slide the locking knobs 2 on the suction grille inward direction of arrows and lift upwards Refer to Fig 1 With the suction grille open remove the suction grille for...

Page 6: ...e sure to use the provided accessories and specified parts designated by our company 1 Secure the hanger brackets to the suspension bolts Refer to Fig 10 NOTE To ensure they are safely secured use the...

Page 7: ...oximately 250 F so use insulation pipe cover which is sufficiently resistant Also in cases where the temperature and humidity of the refrigerant pipe sections might exceed 86 F or RH 80 reinforce the...

Page 8: ...asten both ends with the clamps 4 Refer to Fig 16 Wrap the small sealing pad 9 only around the insulation for the joints on the gas piping side Refer to Fig 16 1 For piping facing back Remove the rear...

Page 9: ...the drain socket and securely attach the metal clamp bracket inside the gray tape area on the inserted tip of the drain pipe Refer to Fig 22 Screw the screws on the metal clamp bracket until there is...

Page 10: ...sion wire between indoor out door units and between the indoor unit and the remote con troller wire are as follows 1 Outdoor unit Indoor unit Max 3280 ft Total wire length 6560 ft 2 Indoor unit Remote...

Page 11: ...result in overheating and in worse case result in electric shock or fire CAUTION To avoid a short circuit in the electric parts box be sure to apply sealing material or putty not included to the wiri...

Page 12: ...TION GRILLE THE DECORATION PANELS AND THE PROTECTION NET Once wiring is complete firmly attach the control box lid the suction grille the decoration panels and the protection net in the order opposite...

Page 13: ...the upper part The remote controller PC board is attached to the upper part of remote controller Refer to Fig 35 2 Turn the MAIN SUB changeover switch on one of the 2 remote controllers PC boards to...

Page 14: ...ill be displayed for a few seconds on the remote controller immediately after the power is turned on This display indicates that the remote controller is being checked to see whether it is ok or not a...

Page 15: ...s fault The remote controller thermistor does not function but the system thermo run is possible E3 High pressure abnormal outdoor unit E4 Low pressure abnormal outdoor unit ON OFF TEST SWING TEST E5...