background image

2 Specific installer safety instructions

Installation and operation manual

5

FXHA32~100AVEB
VRV system air conditioner
3P668115-1C – 2022.01

General

WARNING

Make  sure  installation,  servicing,  maintenance,  repair  and
applied materials follow the instructions from Daikin and, in
addition,  comply  with  applicable  legislation  and  are
performed  by  qualified  persons  only.  In  Europe  and  areas
where  IEC  standards  apply,  EN/IEC  60335-2-40  is  the
applicable standard.

Unit installation (see 

"12 Unit installation"

 [

4

 15])

For 

additional 

installation 

site 

requirements, 

read 

also

"2.1 Instructions for equipment using R32 refrigerant"

 [

4

 6].

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

CAUTION

Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

WARNING

Keep  any  required  ventilation  openings  clear  of
obstructions.

CAUTION

This  equipment  is  NOT  intended  for  use  in  residential
locations  and  will  NOT  guarantee  to  provide  adequate
protection to radio reception in such locations.

CAUTION

Do NOT remove the (milky white) tape from the exterior of
the  indoor  unit.  Removing  the  tape  may  cause  an  electric
shock or a fire.

Refrigerant piping installation (see 

"13 Piping

installation"

 [

4

 19])

CAUTION

Piping MUST be installed according to instructions given in

"13  Piping  installation"

  [

4

  19].  Only  mechanical  joints  (e.g.

braze+flare connections) that are compliant with the latest
version of ISO14903 can be used.

CAUTION

Install  the  refrigerant  piping  or  components  in  a  position
where  they  are  unlikely  to  be  exposed  to  any  substance
which  may  corrode  components  containing  refrigerant,
unless  the  components  are  constructed  of  materials  that
are  inherently  resistant  to  corrosion  or  are  suitably
protected against corrosion.

Electrical installation (see 

"14 Electrical installation"

 [

4

 21])

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  stranded  conductor  wires,

extension  cords,  or  connections  from  a  star  system.
They can cause overheating, electrical shock or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

CAUTION

▪ Each  indoor  unit  has  to  be  connected  to  a  separate

user interface. Only a safety system compatible remote
controller  can  be  used  as  the  user  interface.  See
technical  data  sheet  for  remote  controller  compatibility
(e.g. BRC1H52/82*).

▪ The  user  interface  has  to  be  put  in  the  same  room  as

the  indoor  unit.  For  details,  please  refer  to  the
installation and operation manual of the user interface.

CAUTION

In case shielded wire is used, connect the shielding to the
outdoor unit side only.

Configuration (see 

"17 Configuration"

 [

4

 23])

WARNING

In case of R32 refrigerant, terminal connections T1/T2 are
for  fire  alarm  input  ONLY.  Fire  alarm  has  a  higher  priority
than R32 safety and shuts the entire system down.

T1

T2

X1M

a

a

 Fire alarm input signal (potential free contact)

Summary of Contents for FXHA100AVEB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXHA32AVEB FXHA50AVEB FXHA63AVEB FXHA100AVEB...

Page 2: ...atuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za pr...

Page 3: ...e used in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of...

Page 4: ...inishing the indoor unit installation 22 15 1 To mount the suction grille and decoration side panel 22 16 Commissioning 23 16 1 Checklist before commissioning 23 16 2 To perform a test run 23 17 Confi...

Page 5: ...see 14 Electrical installation 421 WARNING ALWAYS use multicore cable for power supply cables WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the applicable leg...

Page 6: ...e vibration or pulsation to refrigeration piping Protection devices piping and fittings shall be protected as far as possible against adverse environmental effects Provision shall be made for expansio...

Page 7: ...or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed beneath the symbol this c...

Page 8: ...of obstructions Maintenance and service see 7 Maintenance and service 411 CAUTION Pay attention to the fan It is dangerous to inspect the unit while the fan is running Make sure to turn OFF the main s...

Page 9: ...r must be replaced after every detection or at the end of its lifetime ONLY authorised persons may replace the sensor Troubleshooting see 8 Troubleshooting 414 WARNING Stop operation and shut OFF the...

Page 10: ...operation manual of the installed user interface 6 Operation 6 1 Operation range INFORMATION For the operation limits see the technical data of the connected outdoor unit 6 2 About operation modes INF...

Page 11: ...ically The following airflow directions can be set Direction Display Fixed position The indoor unit blows air in 1 of 5 fixed positions Swing The indoor unit alternates between the 5 positions Note Th...

Page 12: ...nts and result in burnout of these components DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes and measure the voltage at the terminals of main circuit capacitors or e...

Page 13: ...for 10 min then wash it with water 5 Reattach the air filter Refer to 7 2 2 To clean the air filter 412 6 Reattach the suction grille and close it steps 2 and 1 in reverse order INFORMATION When clos...

Page 14: ...ur dealer immediately For more information see the installation manual of the outdoor unit In case of detection when the unit is turned on 1 The user interface displays error A0 11 emits an alarm soun...

Page 15: ...inimum floor area of the smallest room that is served For minimum floor area requirements for indoor units see the installation and operation manual of the outdoor unit INFORMATION The sound pressure...

Page 16: ...n Attach the hanger bracket to the suspension bolt Fix it securely using a nut and washer on the top and bottom of the hanger bracket Front view 5 175 200 c b a G H J mm Top ceiling view mm F 210 D B...

Page 17: ...order to remove it a c b b b d c 10 mm a Hanger bracket fixing screw M5 b Hanger bracket installation bolt M8 c Hanger bracket d Indoor unit CAUTION Do NOT remove the milky white tape from the exterio...

Page 18: ...rews 50 63 class 11 screws 100 class 10 screws a a a a b a Fixing screw for protective grille b Protective grille 2 Remove the cap from the drain socket and remove the insulation material from the lef...

Page 19: ...ping installation 13 1 Preparing refrigerant piping 13 1 1 Refrigerant piping requirements CAUTION Piping MUST be installed according to instructions given in 13 Piping installation 419 Only mechanica...

Page 20: ...to avoid the knob part of the cover a b a Rear refrigerant piping b Rear piping pipe port cover 2 Run the field supply pipes through the cut out holes 3 After the drain and refrigerant piping is finis...

Page 21: ...s 32 50 63 100 Power supply cable MCA a 0 5 A 0 6 A 0 7 A 1 3 A Voltage 220 240 V 220 V Phase 1 Frequency 50 60 Hz Wire sizes 1 5 mm2 3 core wire H07RN F 60245 IEC 66 Transmission wiring For specifica...

Page 22: ...s with sealing material accessory to prevent small animals from entering the system 8 Reattach the service cover Complete system example 1 user interface controls 1 indoor unit L N L N L N P1 P2 P1 P2...

Page 23: ...oor and outdoor units The stop valves gas and liquid on the outdoor unit are fully open 16 2 To perform a test run INFORMATION Perform the test run according to the instructions in the outdoor unit ma...

Page 24: ...e cooling setpoint minus the heating setpoint If you want to set Then 1 Example M SW 0 C 12 22 4 01 cooling 24 C heating 24 C 1 C 02 cooling 24 C heating 23 C 2 C 03 cooling 24 C heating 22 C 3 C 04 c...

Page 25: ...sidual current device Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink BRN Brown PRP PPL Purple GRN Green RED Red GRY Grey WHT White SKY BLU Sky blue YLW Yellow Symbol Meaning A P Pr...

Page 26: ...h low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmit...

Page 27: ......

Page 28: ...3P668115 1C 2022 01 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Reviews: