Instructions for equipment using
R32 refrigerant

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (example:  open  flames,  an
operating  gas  appliance  or  an  operating  electric  heater)
and have a room size as specified below.

WARNING

Make  sure  installation,  servicing,  maintenance  and  repair
comply  with  instructions  from  Daikin  and  with  applicable
legislation and are executed ONLY by authorised persons.

WARNING

If  one  or  more  rooms  are  connected  to  the  unit  using  a
duct system, make sure:

▪ there are no operating ignition sources (example: open

flames,  an  operating  gas  appliance  or  an  operating
electric  heater)  in  case  the  floor  area  is  less  than  the
minimum floor area A (m²).

▪ no  auxiliary  devices,  which  may  be  a  potential  ignition

source,  are  installed  in  the  duct  work  (example:  hot
surfaces  with  a  temperature  exceeding  700°C  and
electric switching device);

▪ only  auxiliary  devices  approved  by  the  manufacturer

are used in the duct work;

▪ air inlet AND outlet are connected directly to the same

room  by  ducting.  Do  NOT  use  spaces  such  as  a  false
ceiling as a duct for the air inlet or outlet.

NOTICE

▪ Precautions shall be taken to avoid excessive vibration

or pulsation to refrigeration piping.

▪ Protection  devices,  piping  and  fittings  shall  be

protected  as  far  as  possible  against  adverse
environmental effects.

▪ Provision shall be made for expansion and contraction

of long runs of piping.

▪ Piping  in  refrigerating  systems  shall  be  designed  and

installed such as to minimise the likelihood of hydraulic
shock damaging the system.

▪ The  indoor  equipment  and  pipes  shall  be  securely

mounted  and  guarded  such  that  accidental  rupture  of
equipment  or  pipes  cannot  occur  from  events  such  as
moving furniture or reconstruction activities.

CAUTION

Do  NOT  use  potential  sources  of  ignition  in  searching  for
or detection of refrigerant leaks.

NOTICE

▪ Do  NOT  re-use  joints  and  copper  gaskets  which  have

been used already.

▪ Joints  made  in  installation  between  parts  of  refrigerant

system shall be accessible for maintenance purposes.

NOTICE

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

2.1.1

Installation space requirements

CAUTION

The  total  refrigerant  charge  in  the  system  cannot  exceed
the  requirements  for  minimum  floor  area  of  the  smallest
room that is served. For minimum floor area requirements
for  indoor  units,  see  the  installation  and  operation  manual
of the outdoor unit.

WARNING

This  appliance  contains  R32  refrigerant.  For  the  minimum
floor area of the room in which the appliance is stored refer
to installation and operation manual of the outdoor unit.

NOTICE

▪ Pipework shall be protected from physical damage.

▪ Installation of pipework shall be kept to a minimum.

For the user

3

User safety instructions

Always observe the following safety instructions and regulations.

3.1

General

WARNING

If you are NOT sure how to operate the
unit, contact your installer.

Summary of Contents for FXHA100AVEB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXHA32AVEB FXHA50AVEB FXHA63AVEB FXHA100AVEB...

Page 2: ...atuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za pr...

Page 3: ...e used in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of...

Page 4: ...inishing the indoor unit installation 22 15 1 To mount the suction grille and decoration side panel 22 16 Commissioning 23 16 1 Checklist before commissioning 23 16 2 To perform a test run 23 17 Confi...

Page 5: ...see 14 Electrical installation 421 WARNING ALWAYS use multicore cable for power supply cables WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the applicable leg...

Page 6: ...e vibration or pulsation to refrigeration piping Protection devices piping and fittings shall be protected as far as possible against adverse environmental effects Provision shall be made for expansio...

Page 7: ...or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed beneath the symbol this c...

Page 8: ...of obstructions Maintenance and service see 7 Maintenance and service 411 CAUTION Pay attention to the fan It is dangerous to inspect the unit while the fan is running Make sure to turn OFF the main s...

Page 9: ...r must be replaced after every detection or at the end of its lifetime ONLY authorised persons may replace the sensor Troubleshooting see 8 Troubleshooting 414 WARNING Stop operation and shut OFF the...

Page 10: ...operation manual of the installed user interface 6 Operation 6 1 Operation range INFORMATION For the operation limits see the technical data of the connected outdoor unit 6 2 About operation modes INF...

Page 11: ...ically The following airflow directions can be set Direction Display Fixed position The indoor unit blows air in 1 of 5 fixed positions Swing The indoor unit alternates between the 5 positions Note Th...

Page 12: ...nts and result in burnout of these components DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes and measure the voltage at the terminals of main circuit capacitors or e...

Page 13: ...for 10 min then wash it with water 5 Reattach the air filter Refer to 7 2 2 To clean the air filter 412 6 Reattach the suction grille and close it steps 2 and 1 in reverse order INFORMATION When clos...

Page 14: ...ur dealer immediately For more information see the installation manual of the outdoor unit In case of detection when the unit is turned on 1 The user interface displays error A0 11 emits an alarm soun...

Page 15: ...inimum floor area of the smallest room that is served For minimum floor area requirements for indoor units see the installation and operation manual of the outdoor unit INFORMATION The sound pressure...

Page 16: ...n Attach the hanger bracket to the suspension bolt Fix it securely using a nut and washer on the top and bottom of the hanger bracket Front view 5 175 200 c b a G H J mm Top ceiling view mm F 210 D B...

Page 17: ...order to remove it a c b b b d c 10 mm a Hanger bracket fixing screw M5 b Hanger bracket installation bolt M8 c Hanger bracket d Indoor unit CAUTION Do NOT remove the milky white tape from the exterio...

Page 18: ...rews 50 63 class 11 screws 100 class 10 screws a a a a b a Fixing screw for protective grille b Protective grille 2 Remove the cap from the drain socket and remove the insulation material from the lef...

Page 19: ...ping installation 13 1 Preparing refrigerant piping 13 1 1 Refrigerant piping requirements CAUTION Piping MUST be installed according to instructions given in 13 Piping installation 419 Only mechanica...

Page 20: ...to avoid the knob part of the cover a b a Rear refrigerant piping b Rear piping pipe port cover 2 Run the field supply pipes through the cut out holes 3 After the drain and refrigerant piping is finis...

Page 21: ...s 32 50 63 100 Power supply cable MCA a 0 5 A 0 6 A 0 7 A 1 3 A Voltage 220 240 V 220 V Phase 1 Frequency 50 60 Hz Wire sizes 1 5 mm2 3 core wire H07RN F 60245 IEC 66 Transmission wiring For specifica...

Page 22: ...s with sealing material accessory to prevent small animals from entering the system 8 Reattach the service cover Complete system example 1 user interface controls 1 indoor unit L N L N L N P1 P2 P1 P2...

Page 23: ...oor and outdoor units The stop valves gas and liquid on the outdoor unit are fully open 16 2 To perform a test run INFORMATION Perform the test run according to the instructions in the outdoor unit ma...

Page 24: ...e cooling setpoint minus the heating setpoint If you want to set Then 1 Example M SW 0 C 12 22 4 01 cooling 24 C heating 24 C 1 C 02 cooling 24 C heating 23 C 2 C 03 cooling 24 C heating 22 C 3 C 04 c...

Page 25: ...sidual current device Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink BRN Brown PRP PPL Purple GRN Green RED Red GRY Grey WHT White SKY BLU Sky blue YLW Yellow Symbol Meaning A P Pr...

Page 26: ...h low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmit...

Page 27: ......

Page 28: ...3P668115 1C 2022 01 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Reviews: