14 Electrical installation

Installation and operation manual

21

FXHA32~100AVEB
VRV system air conditioner
3P668115-1C – 2022.01

a

c

b

a

Screw

b

Reinforcing plate

c

Decoration side panel

Pipe length

. Keep refrigerant piping as short as possible.

Flare  connections

.  Connect  refrigerant  piping  to  the  unit  using

flare connections.

Insulation

.  Insulate  the  refrigerant  piping  on  the  indoor  unit  as

follows:

A

B

a

d

c

e f

b

b

a

d

c

e f

b

b

2

4

3

g

1

2

3

1

B

A

A

Gas piping

B

Liquid piping

a

Insulation material (field supply)

b

Tie wrap (accessory)

c

Insulation pieces: Large (gas pipe), small (liquid pipe)
(accessory)

d

Flare nut (attached to the unit)

e

Refrigerant pipe connection (attached to the unit)

f

Unit

g

Small sealing pad (accessory)

1

Turn up the seams of the insulation pieces.

2

Attach to the base of the unit.

3

Tighten the tie wrap on the insulation pieces.

4

Wrap the sealing pad from the base of the unit to the top
of the flare nut.

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

14

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

14.1

Specifications of standard wiring
components

Component

Class

32

50

63

100

Power
supply cable

MCA

(a)

0.5 A

0.6 A

0.7 A

1.3 A

Voltage

220~240 V/220 V

Phase

1~

Frequency

50/60 Hz

Wire sizes

1.5 mm

(3‑core wire)

H07RN-F (60245 IEC 66)

Transmission wiring

For specifications, refer to the installation

manual of the outdoor unit

User interface cable

0.75 to 1.25 mm

2

 (2‑core wire)

H05RN-F (60245 IEC 57)

Length ≤500 m

Recommended circuit
breaker

6 A

Residual current device

Must comply with applicable legislation

(a)

MCA=Minimum circuit ampacity. Stated values are maximum
values (see electrical data of indoor unit for exact values).

14.2

To connect the electrical wiring to
the indoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located at the inside of the service cover).

▪ For  instructions  on  how  to  connect  the  optional

equipment,  see  the  installation  manual  delivered  with
the optional equipment.

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

It is important to keep the power supply and the transmission wiring
separated  from  each  other.  In  order  to  avoid  any  electrical
interference  the  distance  between  both  wirings  should  ALWAYS  be
at least 50 mm.

NOTICE

Be sure to keep the power line and transmission line apart
from  each  other.  Transmission  wiring  and  power  supply
wiring may cross, but may NOT run parallel.

1

Remove the service cover.

2

Open  the  knockout  hole  and  install  the  resin  bushing
(accessory).  Refer  to: 

"To  mount  the  indoor  unit"

  [

4

  17].  The

location  depends  on  the  power  supply  wiring  route.  For
transmission and user interface cable, choosing the same route
as the refrigerant piping is recommended.

50 mm

b c

a

d

c

a

Power supply wiring

b

Resin bushing (accessory)

c

Sealing material for gaps around pipes and cables
(accessory)

Summary of Contents for FXHA100AVEB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXHA32AVEB FXHA50AVEB FXHA63AVEB FXHA100AVEB...

Page 2: ...atuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za pr...

Page 3: ...e used in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of...

Page 4: ...inishing the indoor unit installation 22 15 1 To mount the suction grille and decoration side panel 22 16 Commissioning 23 16 1 Checklist before commissioning 23 16 2 To perform a test run 23 17 Confi...

Page 5: ...see 14 Electrical installation 421 WARNING ALWAYS use multicore cable for power supply cables WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the applicable leg...

Page 6: ...e vibration or pulsation to refrigeration piping Protection devices piping and fittings shall be protected as far as possible against adverse environmental effects Provision shall be made for expansio...

Page 7: ...or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed beneath the symbol this c...

Page 8: ...of obstructions Maintenance and service see 7 Maintenance and service 411 CAUTION Pay attention to the fan It is dangerous to inspect the unit while the fan is running Make sure to turn OFF the main s...

Page 9: ...r must be replaced after every detection or at the end of its lifetime ONLY authorised persons may replace the sensor Troubleshooting see 8 Troubleshooting 414 WARNING Stop operation and shut OFF the...

Page 10: ...operation manual of the installed user interface 6 Operation 6 1 Operation range INFORMATION For the operation limits see the technical data of the connected outdoor unit 6 2 About operation modes INF...

Page 11: ...ically The following airflow directions can be set Direction Display Fixed position The indoor unit blows air in 1 of 5 fixed positions Swing The indoor unit alternates between the 5 positions Note Th...

Page 12: ...nts and result in burnout of these components DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes and measure the voltage at the terminals of main circuit capacitors or e...

Page 13: ...for 10 min then wash it with water 5 Reattach the air filter Refer to 7 2 2 To clean the air filter 412 6 Reattach the suction grille and close it steps 2 and 1 in reverse order INFORMATION When clos...

Page 14: ...ur dealer immediately For more information see the installation manual of the outdoor unit In case of detection when the unit is turned on 1 The user interface displays error A0 11 emits an alarm soun...

Page 15: ...inimum floor area of the smallest room that is served For minimum floor area requirements for indoor units see the installation and operation manual of the outdoor unit INFORMATION The sound pressure...

Page 16: ...n Attach the hanger bracket to the suspension bolt Fix it securely using a nut and washer on the top and bottom of the hanger bracket Front view 5 175 200 c b a G H J mm Top ceiling view mm F 210 D B...

Page 17: ...order to remove it a c b b b d c 10 mm a Hanger bracket fixing screw M5 b Hanger bracket installation bolt M8 c Hanger bracket d Indoor unit CAUTION Do NOT remove the milky white tape from the exterio...

Page 18: ...rews 50 63 class 11 screws 100 class 10 screws a a a a b a Fixing screw for protective grille b Protective grille 2 Remove the cap from the drain socket and remove the insulation material from the lef...

Page 19: ...ping installation 13 1 Preparing refrigerant piping 13 1 1 Refrigerant piping requirements CAUTION Piping MUST be installed according to instructions given in 13 Piping installation 419 Only mechanica...

Page 20: ...to avoid the knob part of the cover a b a Rear refrigerant piping b Rear piping pipe port cover 2 Run the field supply pipes through the cut out holes 3 After the drain and refrigerant piping is finis...

Page 21: ...s 32 50 63 100 Power supply cable MCA a 0 5 A 0 6 A 0 7 A 1 3 A Voltage 220 240 V 220 V Phase 1 Frequency 50 60 Hz Wire sizes 1 5 mm2 3 core wire H07RN F 60245 IEC 66 Transmission wiring For specifica...

Page 22: ...s with sealing material accessory to prevent small animals from entering the system 8 Reattach the service cover Complete system example 1 user interface controls 1 indoor unit L N L N L N P1 P2 P1 P2...

Page 23: ...oor and outdoor units The stop valves gas and liquid on the outdoor unit are fully open 16 2 To perform a test run INFORMATION Perform the test run according to the instructions in the outdoor unit ma...

Page 24: ...e cooling setpoint minus the heating setpoint If you want to set Then 1 Example M SW 0 C 12 22 4 01 cooling 24 C heating 24 C 1 C 02 cooling 24 C heating 23 C 2 C 03 cooling 24 C heating 22 C 3 C 04 c...

Page 25: ...sidual current device Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink BRN Brown PRP PPL Purple GRN Green RED Red GRY Grey WHT White SKY BLU Sky blue YLW Yellow Symbol Meaning A P Pr...

Page 26: ...h low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmit...

Page 27: ......

Page 28: ...3P668115 1C 2022 01 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Reviews: