Specific installer safety
instructions

Always observe the following safety instructions and regulations.

General

WARNING

Make  sure  installation,  servicing,  maintenance,  repair  and
applied materials follow the instructions from Daikin and, in
addition,  comply  with  applicable  legislation  and  are
performed  by  qualified  persons  only.  In  Europe  and  areas
where  IEC  standards  apply,  EN/IEC  60335-2-40  is  the
applicable standard.

Unit installation (see 

"12 Unit installation"

 [

4

 15])

For 

additional 

installation 

site 

requirements, 

read 

also

"2.1 Instructions for equipment using R32 refrigerant"

 [

4

 6].

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

CAUTION

Appliance NOT accessible to the general public, install it in
a secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

WARNING

Keep  any  required  ventilation  openings  clear  of
obstructions.

CAUTION

This  equipment  is  NOT  intended  for  use  in  residential
locations  and  will  NOT  guarantee  to  provide  adequate
protection to radio reception in such locations.

Refrigerant piping installation (see 

"13 Piping

installation"

 [

4

 20])

CAUTION

Piping MUST be installed according to instructions given in

"13  Piping  installation"

  [

4

  20].  Only  mechanical  joints  (e.g.

braze+flare connections) that are compliant with the latest
version of ISO14903 can be used.

CAUTION

Install  the  refrigerant  piping  or  components  in  a  position
where  they  are  unlikely  to  be  exposed  to  any  substance
which  may  corrode  components  containing  refrigerant,
unless  the  components  are  constructed  of  materials  that
are  inherently  resistant  to  corrosion  or  are  suitably
protected against corrosion.

Electrical installation (see 

"14 Electrical installation"

 [

4

 21])

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  stranded  conductor  wires,

extension  cords,  or  connections  from  a  star  system.
They can cause overheating, electrical shock or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

CAUTION

▪ Each  indoor  unit  has  to  be  connected  to  a  separate

user interface. Only a safety system compatible remote
controller  can  be  used  as  the  user  interface.  See
technical  data  sheet  for  remote  controller  compatibility
(e.g. BRC1H52/82*).

▪ The  user  interface  has  to  be  put  in  the  same  room  as

the  indoor  unit.  For  details,  please  refer  to  the
installation and operation manual of the user interface.

CAUTION

In case shielded wire is used, connect the shielding to the
outdoor unit side only.

Configuration (see 

"17 Configuration"

 [

4

 23])

WARNING

In case of R32 refrigerant, terminal connections T1/T2 are
for  fire  alarm  input  ONLY.  Fire  alarm  has  a  higher  priority
than R32 safety and shuts the entire system down.

T1

T2

X1M

a

a

 Fire alarm input signal (potential free contact)

Summary of Contents for FXHA-A

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXUA50AVEB FXUA71AVEB FXUA100AVEB...

Page 2: ...mi laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokl...

Page 3: ...in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN...

Page 4: ...the electrical wiring to the indoor unit 21 15 Finishing the indoor unit installation 22 15 1 To mount the corner cover 22 15 2 To close the suction grille 23 16 Commissioning 23 16 1 Checklist befor...

Page 5: ...cal installation 421 WARNING ALWAYS use multicore cable for power supply cables WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the applicable legislation Make e...

Page 6: ...e vibration or pulsation to refrigeration piping Protection devices piping and fittings shall be protected as far as possible against adverse environmental effects Provision shall be made for expansio...

Page 7: ...or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed beneath the symbol this c...

Page 8: ...of obstructions Maintenance and service see 7 Maintenance and service 411 CAUTION Pay attention to the fan It is dangerous to inspect the unit while the fan is running Make sure to turn OFF the main s...

Page 9: ...r must be replaced after every detection or at the end of its lifetime ONLY authorised persons may replace the sensor Troubleshooting see 8 Troubleshooting 414 WARNING Stop operation and shut OFF the...

Page 10: ...operation manual of the installed user interface 6 Operation 6 1 Operation range INFORMATION For the operation limits see the technical data of the connected outdoor unit 6 2 About operation modes INF...

Page 11: ...nits run in Continuous operation and the airflow direction is downward When starting operation When the room temperature is higher than the controller s setpoint for heating operation including auto o...

Page 12: ...t exterior air filter and suction grille CAUTION Turn off the unit before cleaning the unit exterior air filter and suction grille NOTICE Do NOT use gasoline benzene thinner polishing powder or liquid...

Page 13: ...eater WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer Be aware that t...

Page 14: ...unit Stop operation The operation switch does NOT function properly Turn OFF the power supply If the user interface displays Notify your installer and report the error code To display an error code se...

Page 15: ...ion in such locations CAUTION Appliance NOT accessible to the general public install it in a secured area protected from easy access This unit both indoor and outdoor is suitable for installation in a...

Page 16: ...e is a risk reinforce the ceiling before installing the unit For existing ceilings use anchors For new ceilings use sunken inserts sunken anchors or other field supplied parts 50 100 c b mm a d e a Ce...

Page 17: ...ng a 1 2 3 4 b a Piping part b Level NOTICE Do NOT install the unit tilted Possible consequence If the unit is tilted against the direction of the condensate flow the drain piping side is raised the f...

Page 18: ...ny remaining space may cause air leakage and condensation 12 2 2 Guidelines when installing the drain piping Make sure condensation water can be evacuated properly This involves General guidelines Con...

Page 19: ...se and fix it with tie wraps Start wrapping from the tightened part of the metal clamp so that the end of the metal clamp is wrapped twice 6 Connect the drain piping to the drain hose To check for wat...

Page 20: ...m 1 4 8 10 mm 10 mm 9 5 mm 3 8 12 15 mm 13 mm 12 7 mm 1 2 14 16 mm 13 mm 15 9 mm 5 8 17 20 mm 13 mm i i t p p If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness...

Page 21: ...F 60245 IEC 66 Transmission wiring For specifications refer to the installation manual of the outdoor unit Component Class 50 71 100 User interface cable 0 75 to 1 25 mm2 2 core wire H05RN F 60245 IE...

Page 22: ...N L N L N L TO OUT D TO IN D a a Outdoor unit b Indoor unit c User interface d Most downstream indoor unit NOTICE Group control connection is NOT allowed CAUTION Each indoor unit has to be connected t...

Page 23: ...arthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the...

Page 24: ...angeover if remote sensor is used If the system contains a remote sensor set the increase decrease increments If you want to change increments to Then 1 M SW 1 C 12 22 2 01 0 5 C 02 Setting Automatic...

Page 25: ...s Portal authentication required 18 1 Wiring diagram 18 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring diagram on the unit Part numbering is by Arabic numbers in...

Page 26: ...tor Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure senso...

Page 27: ......

Page 28: ...3P668115 2C 2022 01 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Reviews: