14 Electrical installation

Installation and operation manual

21

FXUA50~100AVEB
VRV system air conditioner
3P668115-2C – 2022.01

1

Turn up the seams of the insulation pieces.

2

Attach to the base of the unit.

3

Tighten the tie wrap on the insulation pieces.

4

Wrap the sealing pad from the base of the unit to the top
of the flare nut.

For 

upward

 and 

right 

piping, use the attached L-shaped piping, and

insulate on both ends of the L-shaped piping.

a

b

d

b

e

c

a

Piping insulation material (field supply)

b

Tie wrap (accessory)

c

Flare nut connection

d

Insulation piece: Large (gas pipe) (accessory)

e

L-shaped piping (accessory)

INFORMATION

In  addition,  bend  the  liquid  piping  with  a  radius  ≤40  mm
using  a  pipe  bender.  If  the  attached  L-shaped  piping  is
NOT  used  or  if  the  bending  radius  is  >40  mm,  this  may
interfere with other piping or the drain hose.

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

14

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

14.1

Specifications of standard wiring
components

Component

Class

50

71

100

Power
supply cable

MCA

(a)

0.5 A

0.6 A

1.1 A

Voltage

220~240 V/220 V

Phase

1~

Frequency

50/60 Hz

Wire sizes

1.5 mm

(3‑core wire)

H07RN-F (60245 IEC 66)

Transmission wiring

For specifications, refer to the installation

manual of the outdoor unit

Component

Class

50

71

100

User interface cable

0.75 to 1.25 mm

2

 (2‑core wire)

H05RN-F (60245 IEC 57)

Length ≤500 m

Recommended circuit
breaker

6 A

Residual current device

Must comply with applicable legislation

(a)

MCA=Minimum circuit ampacity. Stated values are maximum
values (see electrical data of indoor unit for exact values).

14.2

To connect the electrical wiring to
the indoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located at the inside of the service cover).

▪ For  instructions  on  how  to  connect  the  optional

equipment,  see  the  installation  manual  delivered  with
the optional equipment.

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

It is important to keep the power supply and the transmission wiring
separated  from  each  other.  In  order  to  avoid  any  electrical
interference  the  distance  between  both  wirings  should  ALWAYS  be
at least 50 mm.

NOTICE

Be sure to keep the power line and transmission line apart
from  each  other.  Transmission  wiring  and  power  supply
wiring may cross, but may NOT run parallel.

1

Remove the service cover. Remove the 2 screws and slide the
service cover out.

a

b

a

Service cover

b

Screw

2

User  interface  cable

:  Route  the  cable  through  the  frame  and

connect it to the terminal block (P1, P2).

3

Transmission  cable

:  Route  the  cable  through  the  frame  and

connect it to the terminal block (make sure the symbols F1 and
F2 match with the symbols on the outdoor unit).

4

Power  supply  cable

:  Route  the  cable  through  the  frame  and

connect it to the terminal block (L, N, earth).

a

b

a

Circuit breaker

b

Residual current device

5

Fix  the  user  interface  cable  and  transmission  cable  with  a  tie
wrap.

Summary of Contents for FXHA-A

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXUA50AVEB FXUA71AVEB FXUA100AVEB...

Page 2: ...mi laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokl...

Page 3: ...in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN...

Page 4: ...the electrical wiring to the indoor unit 21 15 Finishing the indoor unit installation 22 15 1 To mount the corner cover 22 15 2 To close the suction grille 23 16 Commissioning 23 16 1 Checklist befor...

Page 5: ...cal installation 421 WARNING ALWAYS use multicore cable for power supply cables WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the applicable legislation Make e...

Page 6: ...e vibration or pulsation to refrigeration piping Protection devices piping and fittings shall be protected as far as possible against adverse environmental effects Provision shall be made for expansio...

Page 7: ...or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed beneath the symbol this c...

Page 8: ...of obstructions Maintenance and service see 7 Maintenance and service 411 CAUTION Pay attention to the fan It is dangerous to inspect the unit while the fan is running Make sure to turn OFF the main s...

Page 9: ...r must be replaced after every detection or at the end of its lifetime ONLY authorised persons may replace the sensor Troubleshooting see 8 Troubleshooting 414 WARNING Stop operation and shut OFF the...

Page 10: ...operation manual of the installed user interface 6 Operation 6 1 Operation range INFORMATION For the operation limits see the technical data of the connected outdoor unit 6 2 About operation modes INF...

Page 11: ...nits run in Continuous operation and the airflow direction is downward When starting operation When the room temperature is higher than the controller s setpoint for heating operation including auto o...

Page 12: ...t exterior air filter and suction grille CAUTION Turn off the unit before cleaning the unit exterior air filter and suction grille NOTICE Do NOT use gasoline benzene thinner polishing powder or liquid...

Page 13: ...eater WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer Be aware that t...

Page 14: ...unit Stop operation The operation switch does NOT function properly Turn OFF the power supply If the user interface displays Notify your installer and report the error code To display an error code se...

Page 15: ...ion in such locations CAUTION Appliance NOT accessible to the general public install it in a secured area protected from easy access This unit both indoor and outdoor is suitable for installation in a...

Page 16: ...e is a risk reinforce the ceiling before installing the unit For existing ceilings use anchors For new ceilings use sunken inserts sunken anchors or other field supplied parts 50 100 c b mm a d e a Ce...

Page 17: ...ng a 1 2 3 4 b a Piping part b Level NOTICE Do NOT install the unit tilted Possible consequence If the unit is tilted against the direction of the condensate flow the drain piping side is raised the f...

Page 18: ...ny remaining space may cause air leakage and condensation 12 2 2 Guidelines when installing the drain piping Make sure condensation water can be evacuated properly This involves General guidelines Con...

Page 19: ...se and fix it with tie wraps Start wrapping from the tightened part of the metal clamp so that the end of the metal clamp is wrapped twice 6 Connect the drain piping to the drain hose To check for wat...

Page 20: ...m 1 4 8 10 mm 10 mm 9 5 mm 3 8 12 15 mm 13 mm 12 7 mm 1 2 14 16 mm 13 mm 15 9 mm 5 8 17 20 mm 13 mm i i t p p If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness...

Page 21: ...F 60245 IEC 66 Transmission wiring For specifications refer to the installation manual of the outdoor unit Component Class 50 71 100 User interface cable 0 75 to 1 25 mm2 2 core wire H05RN F 60245 IE...

Page 22: ...N L N L N L TO OUT D TO IN D a a Outdoor unit b Indoor unit c User interface d Most downstream indoor unit NOTICE Group control connection is NOT allowed CAUTION Each indoor unit has to be connected t...

Page 23: ...arthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the...

Page 24: ...angeover if remote sensor is used If the system contains a remote sensor set the increase decrease increments If you want to change increments to Then 1 M SW 1 C 12 22 2 01 0 5 C 02 Setting Automatic...

Page 25: ...s Portal authentication required 18 1 Wiring diagram 18 1 1 Unified wiring diagram legend For applied parts and numbering refer to the wiring diagram on the unit Part numbering is by Arabic numbers in...

Page 26: ...tor Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure senso...

Page 27: ......

Page 28: ...3P668115 2C 2022 01 Copyright 2021 Daikin Verantwortung f r Energie und Umwelt...

Reviews: