background image

Do not mix substance other than the specified refriger

-

ant such as air into the refrigeration circuit. 

If the refrigerant leaks during the work, ventilate the 

room.

• 

The refrigerant is pre-charged in the outdoor unit.

• 

When connecting the pipings to the air conditioner, make 
sure to use a spanner and a torque wrench as shown in 
Fig. 10.

• 

For the dimension of flared part and the tightening torque, 

refer to the Table 2.

• 

When making a flare connection, coat the flared inner 

surface only with ether oil or ester oil.  
(Refer to Fig. 11) 

Then, turn the flare nut 3 to 4 times with your hand and 

screw in the nut.

 

Torque wrench

Spanner

Flare nut

Union joint

Fig. 10

Coat the flared inner surface 

only with ether oil or ester oil

Fig. 11

Table 2

Piping 

size 

(mm)

Tightening 

torque 

(N·m)

Dimension for 

processing flare 

A (mm)

Flare shape

f

 6.4

15.7 ± 1.5

8.9 ± 0.2

R0.4-0.8

90°±2°

A

45°±2°

f

 9.5

36.3 ± 3.6

13.0 ± 0.2

f

 12.7

54.9 ± 5.4

16.4 ± 0.2

f

 15.9

68.6 ± 6.8

19.5 ± 0.2

 CAUTION

Do not have oil adhere to the screw fixing part of resin 

parts.
If oil adheres, it may weaken the strength of screwed part.

Do not tighten flare nuts too tight.

If a flare nut cracks, the refrigerant may leak.

• 

If there is no torque wrench, use Table 3 as a rule of 
thumb. 

When tightening a flare nut with a spanner harder and 

harder, there is a point where the tightening torque sud-
denly increases. 
From that position, tighten the nut additionally the angle 
shown in Table 3. 

After the work is finished, check securely that there is no 

gas leak. 
If the nut is not tightened as instructed, it may cause slow 

refrigerant leak and result in malfunction (such as does 
not cool or heat).

Table 3

Piping size 

(mm)

Tightening 

angle

Recommended arm length of 

tool used

f

 6.4

60° - 90°

approx. 150 mm

f

 9.5

60° - 90°

approx. 200 mm

f

 12.7

30° - 60°

approx. 250 mm

f

 15.9

30° - 60°

approx. 300 mm

 CAUTION

Insulation of field piping must be carried out up to the 

connection inside the casing.
If the piping is exposed to the atmosphere, it may cause 
sweating, burn due to touching the piping, electric shocks or 
a fire due to the wiring touching the piping.

• 

After leak test, referring to 

Fig. 12, insulate both the gas 

and liquid piping connection with the attached joint in-
sulating material (8) and (9) to prevent the pipings from 
getting exposed. 
Then, tighten the both ends of insulating material with the 
clamp (4).

• 

Wrap the sealing material (Medium-1, 2) (11) (12) around 

the joint insulating material (8) and (9) (flare nut section), 

both the gas and liquid piping.

• 

Make sure to bring the seam of joint insulating material (8) 
and (9) to the top.

3P335596-2D        English

Summary of Contents for FXFQ25SVM

Page 1: ...ensing FXFQ25SVM FXFQ63SVM FXFQ32SVM FXFQ80SVM FXFQ40SVM FXFQ100SVM FXFQ50SVM FXFQ125SVM INSTALLATION MANUAL CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR...

Page 2: ...h may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleasant chattering noise Carry out the specified installation work...

Page 3: ...ance that the refrigerant to be used for installation work is R410A The air conditioner will not properly operate if a wrong refrigerant is used For installation of the outdoor unit refer to the insta...

Page 4: ...ing operation and the warm air discharge during the heating operation Does the indoor unit makes unpleasant sound of air discharge Have you explained how to operate the air conditioner showing the ope...

Page 5: ...perature heat generating equipment is in stalled Each sensor has been set so that the center of the sensing area is located in the center of the product 800 mm above the floor in case of the infrared...

Page 6: ...to reinforce the ceiling framework to keep the level of the ceiling and prevent vibration of the ceiling For details consult with the builder and interior designer 3 Install the hanging bolts Use M8...

Page 7: ...n piping side gets high it may cause malfunction of a float switch and results in water leakage Attach nuts on the upper and lower side of hanger If there is no upper nut and the lower nut is over tig...

Page 8: ...rench use Table 3 as a rule of thumb When tightening a flare nut with a spanner harder and harder there is a point where the tightening torque sud denly increases From that position tighten the nut ad...

Page 9: ...nitrogen flow through the piping is approximately 0 02 MPa a pressure that makes one feel like breeze and can be obtained through a pres sure reducing valve 2 Do not use flux when brazing refrigerant...

Page 10: ...the tip of the metal clamp 2 inward as shown Refer to Fig 16 In case of sticking vinyl tape Tightened part approx 90 Stick vinyl tape without tearing the sealing material Large 10 Vinyl tape In case...

Page 11: ...ng the drainage of water refer to Fig 20 and attach the sealing material 14 to perform the thermal insulation of the drain socket Sealing material 14 accessory Fig 20 When the electric wiring work is...

Page 12: ...nit always wiring the indoor unit to the terminal indicated with the same symbol on the terminal block If the wiring and the piping are connected to the different indoor units and operated it will res...

Page 13: ...ning cannot be car ried out If a terminal is over tightened it may be damaged Refer to the table shown below for tightening torque of terminals Tightening torque N m Terminal block for remote controll...

Page 14: ...supply wiring high voltage R10 or more R10 or more Strand the wirings after sheath is peeled off After the wirings are clamped cut off the extra part After the wirings are clamped cut off the extra pa...

Page 15: ...L Remote controller option Remote controller option Remote controller option L N L N L N P1P2 F1 F2 T1 T2 P1P2 P1P2 F1 F2 T1 T2 P1P2 P1P2 F1 F2 T1 T2 P1P2 No 2 system When carrying out group control o...

Page 16: ...ore 9 MOUNTING DECORATION PANEL CAUTION In case of a wireless remote controller unless the decoration panel is mounted field setting and test opera tion cannot be carried out Refer to the installation...

Page 17: ...cleaning indication is not necessary such as the case of periodical clean ing being carried out TEST OPERATION After cleaning the indoor unit inside carry out test operation according to installation...

Page 18: ......

Page 19: ......

Page 20: ...1310 FS 3P335596 2D EM13A007...

Reviews: