background image

Terminal for remote 

controller wiring (P1, P2)

No polarity

Remote 

controller 2

(Sub)

Remote 

controller 1

(Main)

Terminal block 

(X1M)

< Caution >

• 

When using the group control and the 2 remote control-
lers control at the same time, connect the remote control-
ler 2 (Sub) to the indoor unit at the end of the crossover 
wiring (the largest No.). 

(Refer to Fig. 25)

Indoor unit 1

Indoor unit 2

Indoor unit 

largest No.

Remote 

controller 2 

(Sub)

Crossover 

wiring (Remote 

controller)

Remote 

controller 1 

(Main)

Fig. 25

8-7  FOR CENTRALIZED CONTROL

• 

When centralized equipment (such as centralized controller) 
is used for control, it is required to set the group No. on the 
remote controller. 
For details, refer to the manuals attached to the centralized 
equipment.

• 

Connect the centralized equipment to the indoor unit 
connected to the remote controller.

8-8  FOR REMOTE CONTROL (FORCE OFF OR ON / 

OFF OPERATION) 

(1)  Wiring method and specification

• 

Remote control is available by connecting the external 
input to the terminal T1 and T2 on the terminal block for 
remote controller and transmission wiring (X1M).

F2 T1 T2

FORCED

OFF

Input A

Wiring  

specification

Sheathed vinyl 
cord or 2 core 
cable

Wiring size

0.75-1.25 mm

2

Wiring length

Max. 100 m

External  
contact spec

Contact that can 
make and break 
the min. load of 
DC 15 V · 1 mA

(2)  Actuation

• 

Input A of FORCED OFF and ON/OFF OPERATION will 
be as the table shown below.

Input A = ON

Input A = OFF

In case of FORCED 
OFF

Remote controller 

prohibited

Remote controller 

permitted

In case of ON/OFF 
OPERATION

Operation

Stop

(3)  How to choose FORCED OFF or ON/OFF OPERATION 

• 

For choosing FORCED OFF or ON/OFF OPERATION, 
setting by remote controller is required.
(Refer to “

10. FIELD SETTING AND TEST OPERATION”)

9.  MOUNTING DECORATION PANEL

<<If test operation is required before mounting the 

decoration panel, “10. FIELD SETTING AND TEST 

OPERATION” can be carried out before “9. MOUNTING 

DECORATION PANEL”.>>

 CAUTION

In case of a wireless remote controller, unless the decoration 
panel is mounted, field setting and test opera tion cannot be 
carried out.

Refer to the installation manual attached to the decoration 
panel.

• 

After the decoration panel is mounted, check if no clearance 
exists between the panel and the unit.

• 

If test operation is carried out before mounting the decoration 
panel, check the swing blade action after the panel is 
mounted.

10. FIELD SETTING AND TEST OPERATION

<<Refer to also the installation manual attached to the 

outdoor unit.>>

 CAUTION

Before carrying out field setting, check the items mentioned in 
the clause 2 “

1. Items to be checked after the installation 

work is completed” on page 3.

• 

Check if all the installation and piping works for the air 
conditioner are completed.

• 

Check if the control box lids of the air conditioner are closed.

< FIELD SETTING >

<<After turn on the power supply, carry out field setting 

from the remote controller according to the installation 

state.>>

• 

Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.” 
and “SECOND CODE No.”. 
The settings shown by “ 

 ” in the table indicate those 

when shipped from the factory.

• 

The method of setting procedure and operation is shown in 
the installation manual attached to the remote controller.
(Note)  Though setting of “Mode No.” is carried out as a group, 

if you intend to carry out individual setting by each 
indoor unit or confirmation after setting, carry out 
setting with the Mode No. shown in the paren thesis ( ). 

• 

In case of remote control, for changeover of input to 
FORCED OFF or to ON/OFF OPERATION. 
[1] Enter into the field setting mode with the remote controller. 
[2] Select Mode No. “12”. 
[3] Set the FIRST CODE No. to “1”. 
[4-1] For FORCE OFF, set the SECOND CODE No. to “01”. 
[4-2] For ON/OFF OPERATION, set the SECOND CODE No. to “02”. 
(It is set to FORCE OFF when shipped from the factory.)

• 

Ask your customer to keep the manual attached to the remote 
controller together with the operation manual.

• 

Do not carry out settings other than those shown in the table.

15 

3P335596-2D        English

Summary of Contents for FXFQ25SVM

Page 1: ...ensing FXFQ25SVM FXFQ63SVM FXFQ32SVM FXFQ80SVM FXFQ40SVM FXFQ100SVM FXFQ50SVM FXFQ125SVM INSTALLATION MANUAL CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR...

Page 2: ...h may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleasant chattering noise Carry out the specified installation work...

Page 3: ...ance that the refrigerant to be used for installation work is R410A The air conditioner will not properly operate if a wrong refrigerant is used For installation of the outdoor unit refer to the insta...

Page 4: ...ing operation and the warm air discharge during the heating operation Does the indoor unit makes unpleasant sound of air discharge Have you explained how to operate the air conditioner showing the ope...

Page 5: ...perature heat generating equipment is in stalled Each sensor has been set so that the center of the sensing area is located in the center of the product 800 mm above the floor in case of the infrared...

Page 6: ...to reinforce the ceiling framework to keep the level of the ceiling and prevent vibration of the ceiling For details consult with the builder and interior designer 3 Install the hanging bolts Use M8...

Page 7: ...n piping side gets high it may cause malfunction of a float switch and results in water leakage Attach nuts on the upper and lower side of hanger If there is no upper nut and the lower nut is over tig...

Page 8: ...rench use Table 3 as a rule of thumb When tightening a flare nut with a spanner harder and harder there is a point where the tightening torque sud denly increases From that position tighten the nut ad...

Page 9: ...nitrogen flow through the piping is approximately 0 02 MPa a pressure that makes one feel like breeze and can be obtained through a pres sure reducing valve 2 Do not use flux when brazing refrigerant...

Page 10: ...the tip of the metal clamp 2 inward as shown Refer to Fig 16 In case of sticking vinyl tape Tightened part approx 90 Stick vinyl tape without tearing the sealing material Large 10 Vinyl tape In case...

Page 11: ...ng the drainage of water refer to Fig 20 and attach the sealing material 14 to perform the thermal insulation of the drain socket Sealing material 14 accessory Fig 20 When the electric wiring work is...

Page 12: ...nit always wiring the indoor unit to the terminal indicated with the same symbol on the terminal block If the wiring and the piping are connected to the different indoor units and operated it will res...

Page 13: ...ning cannot be car ried out If a terminal is over tightened it may be damaged Refer to the table shown below for tightening torque of terminals Tightening torque N m Terminal block for remote controll...

Page 14: ...supply wiring high voltage R10 or more R10 or more Strand the wirings after sheath is peeled off After the wirings are clamped cut off the extra part After the wirings are clamped cut off the extra pa...

Page 15: ...L Remote controller option Remote controller option Remote controller option L N L N L N P1P2 F1 F2 T1 T2 P1P2 P1P2 F1 F2 T1 T2 P1P2 P1P2 F1 F2 T1 T2 P1P2 No 2 system When carrying out group control o...

Page 16: ...ore 9 MOUNTING DECORATION PANEL CAUTION In case of a wireless remote controller unless the decoration panel is mounted field setting and test opera tion cannot be carried out Refer to the installation...

Page 17: ...cleaning indication is not necessary such as the case of periodical clean ing being carried out TEST OPERATION After cleaning the indoor unit inside carry out test operation according to installation...

Page 18: ......

Page 19: ......

Page 20: ...1310 FS 3P335596 2D EM13A007...

Reviews: