background image

Downward

inclination of 

1/100 or more

1~1.5 m

Support

Good

Wrong

Fig. 14

 CAUTION

If drain stagnates in the drain piping, the piping may be 
clogged.

• 

If sufficient downward inclination cannot be ensured, 

carry out upward drain piping.

• 

Install supports at a distance of 1 to 1.5 m so that the pip-

ing may not deflect. 

(Refer to Fig. 14)

• 

Make sure to use the attached drain hose (1) and the 
metal clamp (2). 
Insert the drain hose (1) into the drain socket up to the 
point where the socket diameter becomes larger.  

  Put the metal clamp (2) to the taped hose end and 

tighten the metal clamp (2) with torque 1.35±0.15 N·m 

(135±15 N·cm).

Metal clamp (2)

(accessory)

Drain socket

Tape

VP20 side VP25 side

Hose end

Drain hose (1)

(accessory)

Fig. 15

 CAUTION

• 

Do not tighten the metal clamp (2) with the torque more 

than the specified value.

 

The drain hose (1), the socket or the metal clamp (2) may 
be damaged.

• 

Wrap the vinyl tape around the end of the metal clamp 
(2) so that the sealing material (Large) (10) to be used at 
the next process may not be damaged with the clamp 
end or bend the tip of the metal clamp (2) inward as 
shown. 

(Refer to Fig. 16)

<In case of sticking vinyl tape>

Tightened part

appro

x.

 90°

Stick vinyl tape without 

tearing the sealing 

material (Large) (10) .

Vinyl tape

<In case of bending the tip>

Bend the tip without tearing the 
sealing material (Large) (10).

Tightened part

appro

x.

 90°

Fig. 16

< Caution to be taken when carrying out upward drain 

piping (Refer to Fig. 17) >

• 

The maximum height of the drain riser is 675 mm. Since 
the drain pump mounted on this indoor unit is a high 
head type, from the characteristic point of view, the 
higher the drain riser the lower the draining noise. 
Therefore, the drain riser of 300 mm or higher is recom-
mended.

• 

For upward drain piping, keep the horizontal piping dis-
tance of 300 mm or less between the drain socket root 
to the drain riser.

Ceiling slab

300 or less

1~1.5 m

Support

Metal clamp (2) (accessory)

Drain hose (1) (accessory)

Upward drain piping

Drain riser

Adjustable

(675 or less)

(850 or less)

Drain hose (1) 

(accessory)

Level or upward 

inclination

Keep the drain hose level or make a slight up-grade so 

that air may not stagnate in the drain hose.

If air stagnates, the drain may flow oppositely when 

the drain pump stops and generate abnormal sound.   

(unit  [mm])

Fig. 17

3P335596-2D        English

Summary of Contents for FXFQ25SVM

Page 1: ...ensing FXFQ25SVM FXFQ63SVM FXFQ32SVM FXFQ80SVM FXFQ40SVM FXFQ100SVM FXFQ50SVM FXFQ125SVM INSTALLATION MANUAL CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR...

Page 2: ...h may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleasant chattering noise Carry out the specified installation work...

Page 3: ...ance that the refrigerant to be used for installation work is R410A The air conditioner will not properly operate if a wrong refrigerant is used For installation of the outdoor unit refer to the insta...

Page 4: ...ing operation and the warm air discharge during the heating operation Does the indoor unit makes unpleasant sound of air discharge Have you explained how to operate the air conditioner showing the ope...

Page 5: ...perature heat generating equipment is in stalled Each sensor has been set so that the center of the sensing area is located in the center of the product 800 mm above the floor in case of the infrared...

Page 6: ...to reinforce the ceiling framework to keep the level of the ceiling and prevent vibration of the ceiling For details consult with the builder and interior designer 3 Install the hanging bolts Use M8...

Page 7: ...n piping side gets high it may cause malfunction of a float switch and results in water leakage Attach nuts on the upper and lower side of hanger If there is no upper nut and the lower nut is over tig...

Page 8: ...rench use Table 3 as a rule of thumb When tightening a flare nut with a spanner harder and harder there is a point where the tightening torque sud denly increases From that position tighten the nut ad...

Page 9: ...nitrogen flow through the piping is approximately 0 02 MPa a pressure that makes one feel like breeze and can be obtained through a pres sure reducing valve 2 Do not use flux when brazing refrigerant...

Page 10: ...the tip of the metal clamp 2 inward as shown Refer to Fig 16 In case of sticking vinyl tape Tightened part approx 90 Stick vinyl tape without tearing the sealing material Large 10 Vinyl tape In case...

Page 11: ...ng the drainage of water refer to Fig 20 and attach the sealing material 14 to perform the thermal insulation of the drain socket Sealing material 14 accessory Fig 20 When the electric wiring work is...

Page 12: ...nit always wiring the indoor unit to the terminal indicated with the same symbol on the terminal block If the wiring and the piping are connected to the different indoor units and operated it will res...

Page 13: ...ning cannot be car ried out If a terminal is over tightened it may be damaged Refer to the table shown below for tightening torque of terminals Tightening torque N m Terminal block for remote controll...

Page 14: ...supply wiring high voltage R10 or more R10 or more Strand the wirings after sheath is peeled off After the wirings are clamped cut off the extra part After the wirings are clamped cut off the extra pa...

Page 15: ...L Remote controller option Remote controller option Remote controller option L N L N L N P1P2 F1 F2 T1 T2 P1P2 P1P2 F1 F2 T1 T2 P1P2 P1P2 F1 F2 T1 T2 P1P2 No 2 system When carrying out group control o...

Page 16: ...ore 9 MOUNTING DECORATION PANEL CAUTION In case of a wireless remote controller unless the decoration panel is mounted field setting and test opera tion cannot be carried out Refer to the installation...

Page 17: ...cleaning indication is not necessary such as the case of periodical clean ing being carried out TEST OPERATION After cleaning the indoor unit inside carry out test operation according to installation...

Page 18: ......

Page 19: ......

Page 20: ...1310 FS 3P335596 2D EM13A007...

Reviews: