9 Relocation

Installation and operation manual

13

FXFA20~125A2VEB
VRV system air conditioner
3P599604-1C – 2020.10

Malfunction

Measure

If a safety device such as a fuse, a
circuit breaker or a residual current
device frequently actuates or the ON/
OFF switch does NOT function properly.

Turn OFF all main power
supply switches to the
unit.

If water leaks from the unit.

Stop operation.

The operation switch does NOT function
properly.

Turn OFF the power
supply.

If the user interface displays 

.

Notify your installer and
report the error code. To
display an error code see
the reference guide of the
user interface.

If  the  system  does  NOT  operate  properly  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  in  accordance  with  the  following
procedures.

INFORMATION

Refer  to  the  reference  guide  located  on 

http://

www.daikineurope.com/support-and-manuals/product-
information/

 for more troubleshooting tips.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

9

Relocation

Contact  your  dealer  for  removing  and  reinstalling  the  total  unit.
Moving units requires technical expertise.

10

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

For the installer

11

About the box

11.1

Indoor unit

11.1.1

To remove the accessories from the
indoor unit

a

e

f

d

c

b

h

i

m

g

j

k

l

a

Paper pattern for installation (upper part of packing)

b

General safety precautions

c

Indoor unit installation and operation manual

d

Installation guide

e

Washers for hanger brackets

f

Screws (to temporarily attach the paper pattern for
installation to the indoor unit)

g

Tie wraps

h

Metal clamp

i

Sealing pads: Large (drain pipe), medium 1 (gas pipe),
medium 2 (liquid pipe), small (electrical wiring)

j

Drain hose

k

Insulation piece: Small (liquid pipe)

l

Insulation piece: Large (gas pipe)

m

Insulation piece (drain pipe)

12

Unit installation

12.1

Preparing the installation site

Avoid  installation  in  an  environment  with  a  lot  of  organic  solvents
such as ink and siloxane.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

12.1.1

Installation site requirements of the
indoor unit

INFORMATION

The sound pressure level is less than 70 dBA.

CAUTION

Appliance not accessible to the general public, install it in a
secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

Spacing

. Mind the following requirements:

(mm)

≥1500

≥2000

≥4000

≥1500

A

B

C

b

a

d

a

c

Summary of Contents for FXFA100A2VEB

Page 1: ...eration manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXFA20A2VEB FXFA25A2VEB FXFA32A2VEB FXFA40A2VEB FXFA50A2VEB FXFA63A2VEB FXFA80A2VEB FXFA100A2VEB FXFA125A2VEB ...

Page 2: ... fie utilizate în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно н...

Page 3: ... wiring components 18 14 2 To connect the electrical wiring to the indoor unit 18 15 Commissioning 19 15 1 Checklist before commissioning 19 15 2 To perform a test run 19 16 Configuration 19 16 1 Field setting 19 17 Technical data 21 17 1 Wiring diagram 21 17 1 1 Unified wiring diagram legend 21 1 About the documentation 1 1 About this document Target audience Authorised installers end users INFOR...

Page 4: ...per earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earthing may cause electrical shock Install the required fuses or circuit breakers Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping particularly on the high pressure side Do NOT use taped wires stranded conductor wires extension cords or...

Page 5: ...on piping Protection devices piping and fittings shall be protected as far as possible against adverse environmental effects Provision shall be made for expansion and contraction of long runs of piping Piping in refrigerating systems shall be designed and installed such as to minimise the likelihood of hydraulic shock damaging the system The indoor equipment and pipes shall be securely mounted and...

Page 6: ...bol means that the battery contains a heavy metal above a certain concentration Possible chemical symbols are Pb lead 0 004 Waste batteries must be treated at a specialized treatment facility for reuse By ensuring waste batteries are disposed of correctly you will help to prevent potential negative consequences for the environment and human health 3 2 Instructions for safe operation WARNING Do NOT...

Page 7: ...ting any maintenance task CAUTION Do NOT insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will cause injury WARNING NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check the unit stand and fit...

Page 8: ...he unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your dealer In case of accidental refrigerant leaks make sure there are no naked flames The refrigerant itself is entirely safe non toxic and mildly flammable but it will generate toxic gas when it accidentally leaks into a room where combustible air from fan heaters gas cookers etc is present Alw...

Page 9: ...ooling Heating and Auto operation modes Setback A function that keeps the room temperature in a specific range when the system is turned off by the user the schedule function or the OFF timer 6 2 1 Basic operation modes The indoor unit can operate in various operation modes Icon Operation mode Cooling In this mode cooling will be activated as required by the setpoint or by Setback operation Heatin...

Page 10: ...fan is rotating at high speed it will cause injury NOTICE NEVER inspect or service the unit by yourself Ask a qualified service person to perform this work However as end user you may clean the air filter suction grille air outlet and outside panels WARNING NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit ...

Page 11: ...er interface 7 2 2 To clean the suction grille NOTICE Do NOT use water of 50 C or higher Possible consequence Discoloration and deformation 1 Open the suction grille Standard panel 1 Design panel 1 1 2 2 2 Remove the suction grille Standard panel 45 1 2 Design panel 1 2 3 Remove the air filter 1 2 3 4 Clean the suction grille Wash with a soft bristle brush and water or neutral detergent If the suc...

Page 12: ...time Authorized person only MUST replace the sensor NOTICE Functionality of the safety measures are periodically automatically checked In case of malfunction error code will display on the user interface NOTICE The R32 refrigerant leakage sensor is a semiconductor detector which may incorrectly detect substances other than R32 refrigerant Avoid using chemical substances e g organic solvents hair s...

Page 13: ...ntling of the system treatment of the refrigerant oil and other parts MUST comply with applicable legislation Units MUST be treated at a specialised treatment facility for reuse recycling and recovery For the installer 11 About the box 11 1 Indoor unit 11 1 1 To remove the accessories from the indoor unit 1 1 1 8 4 1 1 1 a 4 1 1 7 e f d c b h i m g j k l a Paper pattern for installation upper part...

Page 14: ...tion before installation Minimum floor area requirements CAUTION The total refrigerant charge in the system cannot exceed the requirements for minimum floor area of the smallest room that is served For minimum floor area requirements for indoor units see the installation and operation manual of the outdoor unit 12 2 Mounting the indoor unit 12 2 1 Guidelines when installing the indoor unit INFORMA...

Page 15: ...ine the correct vertical position 2 1 2 1 2 1 2 1 A B 1 1 2 C a b c 2 1 2 D A In case of installation with standard decoration panel B In case of installation with fresh air intake kit C In case of installation with self cleaning decoration panel D In case of installation with design decoration panel a Suspended ceiling b Installation guide accessory c Unit Level Make sure the unit is level at all...

Page 16: ...is less than 4 mm from the metal clamp part 3 Check for water leaks see To check for water leaks 416 4 Install the insulation piece drain pipe 5 Wind the large sealing pad insulation around the metal clamp and drain hose and fix it with tie wraps 6 Connect the drain piping to the drain hose 4 mm A A A A A A f 6 5 2 c e 4 b a d b a d c 3 1 2 6 1 a Drain pipe connection attached to the unit b Drain ...

Page 17: ...rial Phosphoric acid deoxidised seamless copper Flare connections Only use annealed material Piping temper grade and thickness Outer diameter Ø Temper grade Thickness t a 6 4 mm 1 4 Annealed O 0 8 mm t Ø 9 5 mm 3 8 12 7 mm 1 2 15 9 mm 5 8 a Depending on the applicable legislation and the maximum working pressure of the unit see PS High on the unit name plate larger piping thickness might be requir...

Page 18: ...current device Must comply with applicable legislation a MCA Minimum circuit ampacity Stated values are maximum values see electrical data of indoor unit for exact values 14 2 To connect the electrical wiring to the indoor unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover For instructions on how to connect the optional equipment see the instal...

Page 19: ...e system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipe...

Page 20: ...tion in the room It determines the interval at which Time to clean filter notification is displayed on the user interface If you want an interval of air contamination Then 1 M SW 2500 h light 10 20 0 01 1250 h heavy 02 Notification ON 3 01 Notification OFF 02 Setting Thermostat sensor selection This setting must correspond with how if the remote controller thermostat sensor is used When the remote...

Page 21: ... earth Connection Protective earth screw Connector A Rectifier Earth Relay connector Field wiring Short circuit connector Fuse Terminal INDOOR Indoor unit Terminal strip Symbol Meaning Symbol Meaning OUTDOOR Outdoor unit Wire clamp Residual current device Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink BRN Brown PRP PPL Purple GRN Green RED Red GRY Grey WHT White YLW Yellow Symb...

Page 22: ...G Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Varistor V R Diode bridge Insulated gate bipolar transistor ...

Page 23: ......

Page 24: ...3P599604 1C 2020 10 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...

Reviews: