![background image](http://html.mh-extra.com/html/daikin/fxaq-pvju/fxaq-pvju_engineeiring-data_2459646003.webp)
Specifications
EDUS391100-F6
2
FXAQ-PVJU
1. Specifications
Wall Mounted Type
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB (27°CDB /19.4°CWB)
Outdoor temperature: 95°FDB (35°CDB)
Equivalent ref. piping length: 25ft (7.5 m) (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB (21°CDB).
Outdoor temperature: 47°FDB, 43°FWB (8.3°CDB / 6°CWB)
Equivalent ref. piping length: 25ft (7.5 m) (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4
Sound levels are measured under JIS conditions.
5 Refer to page 9 for Power Input.
Model
FXAQ07PVJU
FXAQ09PVJU
FXAQ12PVJU
Power Supply
1 phase, 208/230V, 60Hz
1,
3 Cooling Capacity
Btu/h
7,500
9,500
12,000
2,
3 Heating Capacity
Btu/h
8,500
10,500
13,500
Casing Color
White (3.0Y8.5/0.5)
White (3.0Y8.5/0.5)
White (3.0Y8.5/0.5)
Dimensions: (H×W×D)
in (mm)
11–3/8 × 31–1/4 × 9–1/4
(289 x 794 x 235)
11–3/8 × 31–1/4 × 9–1/4
(289 x 794 x 235)
11–3/8 × 31–1/4 × 9–1/4
(289 x 794 x 235)
Coil (Cross
Fin Coil)
Rows×Stages×FPI
2×14×17
2×14×17
2×14×17
Face Area
ft² (m²)
1.73
1.73
1.73
Fan
Model
QCL9661M
QCL9661M
QCL9661M
Type
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
Motor Output
W
40
40
40
Air Flow Rate (H/L)
cfm (m
3
/min)
260/160 (79/49)
280/175 (85/53)
290/180 (88/55)
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for Cooling
and Heating
Microprocessor Thermostat for Cooling
and Heating
Microprocessor Thermostat for Cooling
and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Air Filter
Resin Net (Washable)
Resin Net (Washable)
Resin Net (Washable)
Machine Weight (Mass)
Lbs (kg)
26 (12)
26 (12)
26 (12)
Piping
Connections
Liquid Pipes
in (mm)
1/4 (6.4) (Flare Connection)
1/4 (6.4) (Flare Connection)
1/4 (6.4) (Flare Connection)
Gas Pipes
in (mm)
1/2 (12.7) (Flare Connection)
1/2 (12.7) (Flare Connection)
1/2 (12.7) (Flare Connection)
Drain Pipe
in (mm)
VP13
(External Dia. 11/16 (17.5) Internal
Dia. 1/2 (12.7))
VP13
(External Dia. 11/16 (17.5) Internal
Dia. 1/2 (12.7))
VP13
(External Dia. 11/16 (17.5) Internal Dia.
1/2 (12.7))
4 Sound Level (H/L)
dB(A)
36/31
37/31
38/31
Safety Devices
Fuse
Fuse
Fuse
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R-410A VRV Series
R-410A VRV Series
R-410A VRV Series
Standard Accessories
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tape, Insulation
Tube, Clamps, Screws.
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tape, Insulation
Tube, Clamps, Screws.
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tape, Insulation
Tube, Clamps, Screws.
Drawing No.
C: 3D075572A