Installation
EDUS391100-F6
24
FXAQ-PVJU
Where piping between indoor and outdoor units is possible within the allowable limit.
•
(Refer to the installation manual of the outdoor unit.)
Install the indoor and outdoor units, power supply wiring and connecting wires at least 3.5ft. away
•
from televisions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 3.5ft. may not be suffi cient enough to eliminate the
noise.)
Where the cool (warm) air reaches all across the room.
•
Fig. 1
q
2
q
2
[ Space required for installation (in.) ]
q
3-5/8
q
1-1/4
Floor
Fig. 2
Obstruction
a
4-3/4
q
100 (from floor)
For installation
in high places.
Consider whether the place where the unit will be installed can support the full weight of the
(2)
unit, and reinforce it with boards and beams, etc. if needed before proceeding with the installa-
tion. Also, reinforce the place to prevent vibration and noise before installing.
(The installation pitch can be found on the paper pattern for installation (3), so refer to it when
considering the necessity for reinforcing the location.)
The indoor unit may not be directly installed on the wall. Use the attached installation panel (1)
(3)
before installing the unit.
DANGER
Do not install unit in an area where fl ammable materials are present due to risk of explosion resulting in
•
serious injury or death.
WARNING
If the supporting structural members are not strong enough to take the unit’s weight, the unit could fall
•
out of place and cause serious injury.