• Indoor Units • WALL MOUNTED UNIT • FXAQ-MAVE
1
Specifications
21
1-2 ELECTRICAL SPECIFICATIONS
FXAQ20MAVE
FXAQ25MAVE
FXAQ32MAVE
FXAQ40MAVE
FXAQ50MAVE
FXAQ63MAVE
Power Supply
Name
VE
Phase
1
1
1
1
1
1
Frequency
Hz
50
50
50
50
50
50
Voltage
V
220-240
Current
Minimum circuit amps
(MCA)
A
0.30
0.40
0.40
0.40
0.40
0.60
Maximum fuse amps (MFA) A
15.00
15.00
15.00
15.00
15.00
15.00
Full load amps (FLA)
A
0.20
0.30
0.30
0.30
0.30
0.50
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA<= 4 x FLA
next lower standard fuse rating minimum 15A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books”.
Finally, click on the document title of your choice.