37
NOTE
1. A single switch can be used to supply power to units on the same system. Branch switches and branch circuit
breakers must be selected carefully.
2. Do not ground the equipment on gas pipes, water pipes, lightning rods or telephone ground wires. Improper
grounding could result in electric shock.
8-3
CONTROL BY 2 REMOTE CONTROLLERS (CONTROLLING 1 INDOOR UNIT BY 2 REMOTE
CONTROLLERS)
•
When using 2 remote controllers, one must be set to
MAIN
and the other to
SUB
.
MAIN/SUB CHANGEOVER
(1)
Insert a
screwdriver into the recesses between the
upper and lower part of remote controller, and
working from the 2 positions, pry off the upper part.
The remote controller PC board is attached to the upper
part of the remote controller.
(Refer to Fig. 28)
(2)
Turn the
MAIN/SUB changeover
switch on one of the
two remote controller PC boards to
S
.
(Leave the switch of the other remote controller set to
M
.)
Refer to Fig. 29
Wiring Method:
See Section 7: ELECTRICAL WIRING
WORK
(3)
Remove the service lid.
(4)
Add second remote controller (slave) to the terminal
block (6P in Figure 22) for remote controller (P
1
, P
2
) in
the electric parts box. There is no polarity. Refer to Fig.
26 and Section 7-3 for the wiring size.
8-4
COMPUTERIZED CONTROL (FORCED OFF AND ON/OFF OPERATION)
1. Wire specifications and how to perform wiring:
•
Connect the input from outside to terminals T1 and T2 of the terminal block (6P).
(2)
Actuation
•
The following table explains
FORCED OFF
and
ON/OFF OPERATIONS
in response to Input A:
Wire specification
2 conductor, stranded copper, non-shielded, PVC or vinyl
jacket
Gauge
AWG18
Length
Max. 328 ft. (100 m)
External terminal
Contact must ensure the minimum
applicable load of 15V DC, 10 mA.
FORCED OFF
ON/OFF OPERATION
Input “ON” stops operation (impossible by remote controllers).
Input OFF
→
ON turns ON unit.
Upper part of
remote controller
Lower part of
remote controller
Insert the screwdriver here
and gently work off the
upper part of the remote controller.
Fig. 28
S
M
S
S
M
Remote
controller
PC board
(Factory setting)
(Only one remote
controller needs
to be changed if
factory settings
have remained
untouched.)
Fig. 29
Input A
Fig. 30
F2
T1
T2
FORCED
OFF
Summary of Contents for FXAQ-M Series
Page 1: ...EDUS 39 600 F6 AMERICAS FXAQ M Wall Mounted Type...
Page 6: ...EDUS39 600 F6 Dimensions FXAQ M 5 3 Dimensions FXAQ07 09 12MVJU 3D046040A...
Page 7: ...Dimensions EDUS39 600 F6 6 FXAQ M FXAQ18MVJU 3D046041...
Page 8: ...EDUS39 600 F6 Dimensions FXAQ M 7 FXAQ24MVJU 3D046042...
Page 10: ...EDUS39 600 F6 Wiring Diagrams FXAQ M 9 5 Wiring Diagrams FXAQ07M 09M 12M 18M 24MVJU 3D046039C...
Page 11: ...Electric Characteristics EDUS39 600 F6 10 FXAQ M 6 Electric Characteristics 4D046466A...
Page 20: ...EDUS39 600 F6 Installation FXAQ M 19 10 Installation Installation Example...