![background image](http://html1.mh-extra.com/html/daikin/fxaq-m-series/fxaq-m-series_engineering-data_2459642024.webp)
EDUS39-600-F6
Installation
FXAQ-M
23
2-1
ACCESSORIES
Check that the following accessories are included with your unit.
2-2
OPTIONAL ACCESSORIES
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER
INSTALLATION IS FINISHED.
1. Items to be checked after completion of work
2. Items to be checked at time of delivery:
2-3
NOTE TO THE INSTALLER
Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating different
functions, and adjusting the temperature) by having them carry out operations themselves while looking at the
Name
(1) Installation panel
(2) Attachment screws
for the installation panel
(3) Paper pattern for
installation
(4) Insulating tape
Quantity
1 set
8 pcs.
→
FXAQ07, 09, 12 type
9 pcs.
→
FXAQ18, 24 type
1 pc.
1 pc.
Shape
M4 × 25L
Name
(5) Clamp
(6) Securing screws
(7) Insulating tube
• Operation manual
• Installation manual
Quantity
1 large 4 small
2 pcs.
1 long 1 short
Shape
M4 × 12L
Remote controller type
Model
Wired type
BRC1D71
Wireless type
BRC7E818
Items to be checked
If not properly installed, the following malfunctions
can occur:
Check
Are the indoor and outdoor unit fixed firmly?
Unit drops, vibrates, or makes noise.
Is the gas leak test finished?
Insufficient cooling
Is the unit fully insulated?
Dripping condensate water
Does drainage flow smoothly?
Dripping condensate water
Does the power supply voltage correspond to that
shown on the name plate?
Unit malfunction or burned out components.
Are wiring and piping correct?
Unit malfunction or burned out components.
Is the unit safely grounded?
Danger of electric leakage
Is wiring size according to specifications?
Unit malfunction or burned out components.
Is something blocking the air outlet or inlet of either
the indoor or outdoor units?
Insufficient cooling
Are refrigerant piping length and additional refrigerant
charge noted down?
Refrigerant charge is not clear.
Review SAFETY CONSIDERATIONS
Check
Did you explain about operations while showing the operation manual to your customer?
Did you hand the operation manual over to your customer?
Summary of Contents for FXAQ-M Series
Page 1: ...EDUS 39 600 F6 AMERICAS FXAQ M Wall Mounted Type...
Page 6: ...EDUS39 600 F6 Dimensions FXAQ M 5 3 Dimensions FXAQ07 09 12MVJU 3D046040A...
Page 7: ...Dimensions EDUS39 600 F6 6 FXAQ M FXAQ18MVJU 3D046041...
Page 8: ...EDUS39 600 F6 Dimensions FXAQ M 7 FXAQ24MVJU 3D046042...
Page 10: ...EDUS39 600 F6 Wiring Diagrams FXAQ M 9 5 Wiring Diagrams FXAQ07M 09M 12M 18M 24MVJU 3D046039C...
Page 11: ...Electric Characteristics EDUS39 600 F6 10 FXAQ M 6 Electric Characteristics 4D046466A...
Page 20: ...EDUS39 600 F6 Installation FXAQ M 19 10 Installation Installation Example...