1-8
Dry Mode
When the air humidity is high, the unit can operate in dry
mode. Press <MODE> button and choose <DRY>.
If the room temperature is 2°C/3.6°F higher than the
set temperature, the air conditioner will operate under
cooling mode until it reaches within the 2°C/3.6°F range
of difference compared to the set temperature before it
converts to dry mode.
If the room temperature is within the 2°C/3.6°F range of
difference compared to the set temperature, it will directly
operate under dry mode.
The unit will operate at LOW speed under dry mode.
Heat Mode (for heat pump unit only)
When the unit at cold draft setting, the indoor fan will
start to operate only after the coil reaches the desired
temperature.
For fan mode setting, indoor fan will continuous running
once unit ON.
When the set temperature is achieved, the indoor fan will
operate until the coil cannot provide anymore additional
heat.
Air Flow Control
For more effective air circulation, you can manually adjust
the air discharge grille to the left or right.
During cool mode operation and dry mode operation, do
not direct the air discharge louver downwards for too long.
If operating continues in this way, condensation may occur
on the louver, thus resulting in drippings.
Fan Speed And Rated Cooling Capacity
The rated cooling capacity is provided at the HIGH fan
speed.
The cooling capacity is lower when the unit is operating at
MEDIUM and LOW fan speed.
•
•
•
•
•
•
•
•
•
•
•
Notes On Flaps And Louvers Angles
When “
SWING button
” is selected, the flaps swinging
range depends on the operation mode. (See the figure.)
ATTENTION
Always use a remote controller to adjust the flaps angle.
If you attempt to move it forcibly with hand when it is
swinging, the mechanism may be broken.
Be careful when adjusting the louvers. Inside the air outlet,
a fan is rotating at a high speed.
•
•
•
In COOL, DRY and FAN mode
When stop operation
Upper limit 55
˚
Lower limit 75
˚
AIR CONDITIONER UNIT OPERATION
In HEAT mode
When stop operation
Upper limit 70
˚
Lower limit 110
˚
OPERATING RANGE
Operating Limits:
Thermal carrier : Water
Water temperature : 4-10°C Cooling; 35-50°C Heating
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature
Ts °C/°F
Th °C/°F
Minimum indoor
temperature
19.0 / 66.2
14.0 / 57.2
Maximum indoor
temperature
32.0 / 89.6
23.0 / 73.4
Heating Mode
Ts: Dry bulb temperature.
Th: Wet bulb temperature.
Temperature
Ts °C/°F
Th °C/°F
Minimum indoor
temperature
15.0 / 59.0
-
Maximum indoor
temperature
27.0 / 80.6
-
1 IM-WMJW-0312(9)DKdenv_EN.indd 8
1/31/20 4:23:47 PM
Summary of Contents for FWT02GATNMV1
Page 2: ...CVR IM WMJW 0312 9 DKdenv_EN ind2 2 1 31 20 12 04 18 PM...
Page 14: ...MEMO 1 IM WMJW 0312 9 DKdenv_EN indd 12 1 31 20 4 23 48 PM...
Page 26: ...MITTEILUNG 2 IM WMJW 0312 9 DKdenv_DE indd 12 1 31 20 4 22 29 PM...
Page 38: ...LE M MO 3 IM WMJW 0312 9 DKdenv_FR indd 12 1 31 20 4 13 11 PM...
Page 50: ...MEMO 4 IM WMJW 0312 9 DKdenv_NL indd 12 1 31 20 4 20 31 PM...
Page 62: ...EL MEMOR NDUM 5 IM WMJW 0312 9 DKdenv_ES indd 12 1 31 20 4 13 51 PM...
Page 74: ...PROMEMORIA 6 IM WMJW 0312 9 DKdenv_IT indd 12 1 31 20 4 14 15 PM...
Page 75: ...7 1 A B C B ON OFF 7 IM WMJW 0312 9 DKdenv_GR indd 1 1 31 20 4 19 11 PM...
Page 77: ...7 3 1m 1m ON OFF OFF 7 IM WMJW 0312 9 DKdenv_GR indd 3 1 31 20 4 19 12 PM...
Page 78: ...7 4 50 50 55 2000 mm 7 IM WMJW 0312 9 DKdenv_GR indd 4 1 31 20 4 19 12 PM...
Page 84: ...7 10 1 2 3 4 5 2 30 C 86 F 7 IM WMJW 0312 9 DKdenv_GR indd 10 1 31 20 4 19 14 PM...
Page 86: ...7 IM WMJW 0312 9 DKdenv_GR indd 12 1 31 20 4 19 15 PM...
Page 98: ...MEMO 8 IM WMJW 0312 9 DKdenv_PT indd 12 1 31 20 4 30 38 PM...
Page 99: ...9 1 K A B C B XEMA A MEP 9 IM WMJW 0312 9 DKdenv_RU indd 1 1 31 20 5 40 38 PM...
Page 101: ...9 3 H MAH E CTOPO HO 1 1 OFF PE PE EH E 9 IM WMJW 0312 9 DKdenv_RU indd 3 1 31 20 4 32 12 PM...
Page 108: ...9 10 1 2 3 4 5 2 30 C 86 F 9 IM WMJW 0312 9 DKdenv_RU indd 10 1 31 20 4 32 14 PM...
Page 109: ...9 IM WMJW 0312 9 DKdenv_RU indd 11 1 31 20 4 32 14 PM...
Page 110: ...9 IM WMJW 0312 9 DKdenv_RU indd 12 1 31 20 4 32 14 PM...
Page 121: ...NOT 10 IM WMJW 0312 9 DKdenv_TR indd11 11 1 31 20 4 33 01 PM...
Page 122: ...NOT 10 IM WMJW 0312 9 DKdenv_TR indd12 12 1 31 20 4 33 01 PM...
Page 126: ...CVR IM WMJW 0312 9 DKdenv_AR ind3 3 1 31 20 4 51 06 PM...
Page 127: ...0 IM WMJW 0312 9 DKdenv_AR indd 12 1 31 20 4 49 09 PM...
Page 128: ...0 IM WMJW 0312 9 DKdenv_AR indd 11 1 31 20 4 49 12 PM...
Page 129: ...1 2 3 4 5 30 0 IM WMJW 0312 9 DKdenv_AR indd 10 1 31 20 4 49 12 PM...
Page 135: ...55 50 50 2000 0 IM WMJW 0312 9 DKdenv_AR indd 4 1 31 20 4 49 15 PM...
Page 136: ...OFF 1 1 ON OFF OFF 0 IM WMJW 0312 9 DKdenv_AR indd 3 1 31 20 4 49 15 PM...
Page 138: ...A B C B OFF ON 0 IM WMJW 0312 9 DKdenv_AR indd 1 1 31 20 4 49 16 PM...
Page 139: ...CVR IM WMJW 0312 9 DKdenv_AR ind2 2 1 31 20 4 51 06 PM...