5

English

Model

FWF02AATNMV1 FWF03AATNMV1 FWF04AATNMV1

Voltage range**

Recommended fuse*

A

2

2

2

Power supply cable size*

mm

2

1.5

1.5

1.5

Number of conductors

3

3

3

220V-240V/1Ph/50Hz+

!

• All wires must be firmly connected.
• All wires must not touch the water piping, or any moving parts of the fan motor.
• The power supply cord must be equivalent to H05VV-F (60227 IEC 52 or 60227 IEC 53) which is the minimum requirement,

and to be used in protective tube.

IMPORTANT :

* These values are for information only. They should be checked and selected to comply with local and/or

national codes and regulations. They are also subject to the type of installation and size of conductors.

** The appropriate voltage range should be checked with label data on the unit.

A main switch or other means for disconnection, having a contact separation in all poles, must be incorpo-
rated in the fixed wiring in accordance with relevant local and national legislation.

OPERATING RANGE

Operating Limits:

Thermal carrier : Water
Water temperature : 5 ~50°C
Maximum water pressure : 16 bar
Air temperature : (as below)

Heating Mode

Cooling Mode

Temperature

Ts °C/°F

Th °C/°F

Minimum indoor

16.0 / 60.8

11.0 / 51.8

temperature
Maximum indoor

32.0 / 89.6

23.0 / 73.4

temperature
Minimum outdoor

16.0 / 60.8

-

temperature
Maximum outdoor

46.0 / 114.8

-

temperature

Ts: Dry bulb temperature.           Th: Wet bulb temperature.

Temperature

Ts °C/°F

Th °C/°F

Minimum indoor

16.0 / 60.8

-

temperature
Maximum indoor

30.0 / 86.0

-

temperature
Minimum outdoor

-5.0 / 23.0

-6.0 / 21.2

temperature
Maximum outdoor

24.0 / 75.2

18.0 / 64.4

temperature

Summary of Contents for FWF02AATNMV1

Page 1: ...INSTALLATION MANUAL Models FWF02AATNMV1 FWF03AATNMV1 FWF04AATNMV1 English Installation Manual Chilled Water Fan Coil Units...

Page 2: ......

Page 3: ...THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM WARNING Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation and experienced with this type...

Page 4: ...washer Adjust the unit height to 35 0 mm between the indoor unit bottom surface and the ceiling surface Confirm with a level gauge that the unit is installed horizon tally and tighten the nut and bolt...

Page 5: ...r vent that is fitted along with the connection for air purging 3 ways valve is required for cycling off or bypass the chilled water Black steel pipe polyethrene pipe and copper tube are recommended i...

Page 6: ...elay 220 240V 10A Model FWF02AATNMV1 FWF03AATNMV1 FWF04AATNMV1 PART NUMBER 08024091944 INDOOR COIL SENSOR RETURN AIR SENSOR LCD WIRELESS CONTROLLER AC LC MC BLACK PURPLE RED WHITE RED YELLOW FH BROWN...

Page 7: ...appropriate voltage range should be checked with label data on the unit A main switch or other means for disconnection having a contact separation in all poles must be incorpo rated in the fixed wiri...

Page 8: ...possible to seal one of the four air discharge outlet Sealing two or more air discharge outlet could cause a malfunction Remove the front panel and insert the sealing material into the air discharge...

Page 9: ...Is there any abnormal vibration on the unit itself or piping d Is the drainage of water smooth Note The installation guide above covers only the fan coil unit For installation of outdoor mini chiller...

Page 10: ...or the compressor to start operating Power failure or the fuse need to be replaced The power plug is disconnected It is possible that your delay timer has been set incorrectly If the fault persist aft...

Page 11: ......

Page 12: ...t 300 B 8400 Oostende Belgium Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo office JR Shinagawa East Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com g...

Reviews: