NOTICE

Disposal requirements

Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not
be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refriger-
ant, of oil and of other parts must be done by a qualified installer in accordance with relevant local and national
legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this
product is disposed of correctly, you will help to prevent potential negative consequences for the environment and
human health. Please contact the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local
and national legislation.

2. Unit Installation

• Measure and mark the position for the hanging rod. Drill the

hole for the angle nut on the ceiling and fix the hanging rod.

• The installation template is extended according to tempera-

ture and humidity. Check on dimensions in use.

• The dimensions of the installation template are the same as

those of the ceiling opening dimensions.

• Before ceiling laminating work is completed, be sure to fit

the installation template to the indoor unit.

Note:

 Be sure to discuss the ceiling drilling work with the in-

stallers concerned.

3. Unit Hanging

• Confirm the pitch of the hanging rod.
• Hold the unit and hang it on the hanging rod with the nut and

washer.

• Adjust the unit height to 35.0 mm between the indoor unit

bottom surface and the ceiling surface.

• Confirm with a level gauge that the unit is installed horizon-

tally and tighten the nut and bolt to prevent unit failing and
vibration.

• Open the ceiling board along the outer edge of the paper

installation template.

Indoor Unit

Ceiling
Board

35.0 mm

35.0 mm

Indoor Unit

Ceiling

Board

580.0 ~ 610.0 mm (

Ceiling

Board Opening)

15.0

538.0

529.0

19.0

18.0

580.0 ~ 610.0 mm (Ceiling Board Opening)

32.0

38.0

505.0

448.0

88.0

INSTALLATION OF THE INDOOR UNIT

• Electrical supply and installation is to conform to local authority’s (e.g. National Electrical Board) codes and regulations.
• Voltage supply fluctuation must not exceed ±10% of rated voltage. Electricity supply lines must be independent of welding

transformers which can cause high supply fluctuation.

• Ensure that the location is convenient for wiring, piping and drainage.
• The indoor unit must be installed in such that is free from any obstacles in path of cool air discharge and warm air return, and

must allow spreading of air throughout the room (near the center of the room).

• Provide clearance for the indoor unit from the wall and obstacles as shown in the figure.
• The installation place must be strong enough to support a load 4 times the indoor unit weight to avoid amplifying noise and

vibration.

• The installation place (hanging ceiling surface) must levelled and the height in the ceiling is 350mm or more.
• The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).

1. Preliminary Site Survey

Max. 0.3 m

Min. 0.5 m

Min. 0.5 m

Min. 0.5 m

Min. 1.0 m

Max. 3.0 m

Floor

Obstacle

Beam

Obstacle

Min. 1.0 m

Min. 2.5m ~ Max 3.0m

Floor

Min. 0.5 m

Min. 0.5 m

Min. 0.5 m

Max. 0.3 m

Beam

Summary of Contents for FWF02AATNMV1

Page 1: ...INSTALLATION MANUAL Models FWF02AATNMV1 FWF03AATNMV1 FWF04AATNMV1 English Installation Manual Chilled Water Fan Coil Units...

Page 2: ......

Page 3: ...THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM WARNING Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation and experienced with this type...

Page 4: ...washer Adjust the unit height to 35 0 mm between the indoor unit bottom surface and the ceiling surface Confirm with a level gauge that the unit is installed horizon tally and tighten the nut and bolt...

Page 5: ...r vent that is fitted along with the connection for air purging 3 ways valve is required for cycling off or bypass the chilled water Black steel pipe polyethrene pipe and copper tube are recommended i...

Page 6: ...elay 220 240V 10A Model FWF02AATNMV1 FWF03AATNMV1 FWF04AATNMV1 PART NUMBER 08024091944 INDOOR COIL SENSOR RETURN AIR SENSOR LCD WIRELESS CONTROLLER AC LC MC BLACK PURPLE RED WHITE RED YELLOW FH BROWN...

Page 7: ...appropriate voltage range should be checked with label data on the unit A main switch or other means for disconnection having a contact separation in all poles must be incorpo rated in the fixed wiri...

Page 8: ...possible to seal one of the four air discharge outlet Sealing two or more air discharge outlet could cause a malfunction Remove the front panel and insert the sealing material into the air discharge...

Page 9: ...Is there any abnormal vibration on the unit itself or piping d Is the drainage of water smooth Note The installation guide above covers only the fan coil unit For installation of outdoor mini chiller...

Page 10: ...or the compressor to start operating Power failure or the fuse need to be replaced The power plug is disconnected It is possible that your delay timer has been set incorrectly If the fault persist aft...

Page 11: ......

Page 12: ...t 300 B 8400 Oostende Belgium Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo office JR Shinagawa East Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com g...

Reviews: