English

Main Drain Pipe

Feed Water

Flexible Drain Hose

5. Drain Test

• Connect the main drain pipe to the flexible drain.
• Feed water from flexible drain hose to check the piping for leak-

age.

• When the test is completed, connect the flexible drain hose to the

drain connector on the indoor unit.

Note:

This Indoor Unit uses a drain pump for condensed water
drainage. Install the unit horizontally to prevent water leak-
age or condensation around the air outlet.

• Drain pipe must be in downward gradient for smooth drain-

age.

• Avoid installing the drain pipe in up and down slope to pre-

vent reversed water flow.

• During the drain pipe connection, be careful not to exert extra

force on the drain connector at indoor unit.

• The outside diameter of the drain connection at the flexible

drain hose is 20mm.

• Be sure to execute heat insulation (polyethylene foam with

thickness more than 8.0mm) on the drain piping to avoid the
condensed water dripping inside the room.

4. Drain Pump Work

Indoor Unit

Pipe Clamp

Good

Bad

6.

 

Water Piping Connection

• The indoor unit is equipped with water outlet and inlet connection. There is an air-vent that is fitted along with the connection

for air purging.

• 3 ways valve is required for cycling off or bypass the chilled water.
• Black steel pipe, polyethrene pipe and copper tube are recommended in the field installation. All types of piping and connec-

tion must be insulated with polyethrene (ARMAFLEX type or equivalent) to avoid condensation.

• Do not used contaminated or damaged pipe and fitting for installation.
• Some main fitting components are needed in the system to enhance the capacity and ease the service, such as gate valve,

balancing valve, 2 ways or 3 ways valve, filter, strainer and etc.

7. Panel Installation

• Be sure to remove the installation template before installing the

front panel.

• Open the air intake grille by pulling back the catchers and re-

moving it together with filter from panel.

• Install the front frame panel onto the indoor unit by 4 screws and

tighten it completely to prevent cool air leakage.

• Connect the LED wire and air swing wire to the indoor unit.

Note:

Install the front panel firmly to prevent cool air leakage which
will cause condensation and water dripping.

OPEN

Screw

From
Front
Panel

LED Wire

Air Swing Wire

From
Control
Box

Gate Valve

Gate Valve

Gate Valve

Gate Valve

Gate Valve

Gate Valve

FCU

FCU

FCU

3 Way Valve

2 Way Valve

Good Control

Bad Control

Worst Control

Chiller

Summary of Contents for FWF02AATNMV1

Page 1: ...INSTALLATION MANUAL Models FWF02AATNMV1 FWF03AATNMV1 FWF04AATNMV1 English Installation Manual Chilled Water Fan Coil Units...

Page 2: ......

Page 3: ...THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM WARNING Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation and experienced with this type...

Page 4: ...washer Adjust the unit height to 35 0 mm between the indoor unit bottom surface and the ceiling surface Confirm with a level gauge that the unit is installed horizon tally and tighten the nut and bolt...

Page 5: ...r vent that is fitted along with the connection for air purging 3 ways valve is required for cycling off or bypass the chilled water Black steel pipe polyethrene pipe and copper tube are recommended i...

Page 6: ...elay 220 240V 10A Model FWF02AATNMV1 FWF03AATNMV1 FWF04AATNMV1 PART NUMBER 08024091944 INDOOR COIL SENSOR RETURN AIR SENSOR LCD WIRELESS CONTROLLER AC LC MC BLACK PURPLE RED WHITE RED YELLOW FH BROWN...

Page 7: ...appropriate voltage range should be checked with label data on the unit A main switch or other means for disconnection having a contact separation in all poles must be incorpo rated in the fixed wiri...

Page 8: ...possible to seal one of the four air discharge outlet Sealing two or more air discharge outlet could cause a malfunction Remove the front panel and insert the sealing material into the air discharge...

Page 9: ...Is there any abnormal vibration on the unit itself or piping d Is the drainage of water smooth Note The installation guide above covers only the fan coil unit For installation of outdoor mini chiller...

Page 10: ...or the compressor to start operating Power failure or the fuse need to be replaced The power plug is disconnected It is possible that your delay timer has been set incorrectly If the fault persist aft...

Page 11: ......

Page 12: ...t 300 B 8400 Oostende Belgium Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo office JR Shinagawa East Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com g...

Reviews: