Install the fan coil unit

Q

Keep piping as short as possible and slope it downwards at a 
gradient of at least 1/100 so that air does not remain trapped 
inside the pipe. Refer to 

“Drain pipe installation” on page 8

.

If the drain hose cannot be sufficiently set on a slope, fit the drain 
hose with a drain raising piping (field supply) as illustrated in 
figure 7: “How to perform drain piping”.

Q

Keep pipe size equal to or greater than that of the connecting 
pipe (25 mm inner diameter).

Q

Install the drain raising pipes at a height of less than 675 mm.

Q

Install the drain raising pipes at a right angle to unit and no more 
than 300 mm from the unit.

Q

To prevent air bubbles, install the drain hose level or slightly tilted 
up (

75 mm).

Q

Insulate the complete drain piping inside the building.

Install the fan coil unit

4.7.2. Connect the drain piping to the unit

1

Push the drain hose (delivered with the unit) as far as possible 
over the drain socket as illustrated in the figure below.

Fig. 4.8: Connecting the drain hose

2

Tighten the metal clamp until the screw head is less than 4 mm 
from the metal clamp part as illustrated in figure 8: “Wrap sealing 
pad”.

3

Wrap the large sealing pad (as illustrated in figure 8: “Wrap 
sealing pad”) over the metal clamp and drain hose and fix it with 
clamps.

Install the fan coil unit

4.7.3. Test the drain piping

After the drain piping work is finished, check if drainage flows 
smoothly.
1

Add approximately 1 l of water gradually through the air outlet 
(See figure 10: “Method of adding water”).

2

Check the drainage flow.

3

After the testing of drain piping is finished, attach the drain 
sealing pad (delivered with the unit) over the uncovered part of 
the drain socket (between drain hose (delivered with the unit) and 
unit body) as illustrated in figure 8: “Wrap sealing pad”.

Install the fan coil unit

4.8.

Install optional equipment

For the installation of optional equipment, refer to the installation 
manual which is delivered with the optional equipment and take into 
account the remarks mentioned in the table below.

a

Ceiling slab

b

Hanger bracket

c

Drain raising pipe (nominal diameter = 25 mm)

d

Drain hose (delivered with the unit)

e

Metal clamp (delivered with the unit)

Information

When unifying multiple drain pipes, install the pipes as 
illustrated in figure 17: “Unifying multiple drain pipes”. 
Select converging drain pipes whose size is suitable for the 
operating capacity of the unit. 

a

T-joint converging drain pipes

a

Drain socket (fixed to the unit)

b

Drain hose (delivered with the unit)

a

Drain socket (fixed to the unit)

b

Drain hose (delivered with the unit)

c

Metal clamp (delivered with the unit)

d

Drain sealing pad (delivered with the unit)

e

Large sealing pad (delivered with the unit)

f

Drain piping (field supply)

b

a

a

Plastic watering can (tube should be about 
100 mm long)

b

Service drain outlet (with rubber plug) (Use this 
outlet to drain water from the drain pan)

c

Drain pump location

d

Drain pipe

e

Drain socket

Q

In case the electric wiring work is finished

Check drainage flow during COOL running, explained in 

“Test 

the installation” on page 11

.

Q

In case electric wiring work is not finished

1

Remove the control box cover. Connect the power 
supply (50 Hz, 220-240 V) to connections L and N on 
the power supply terminal block and connect the 
ground wire firmly. 

2

Close the control box cover and turn on the power.

Danger: electric shock

Do not touch the drain pump.

3

Confirm the drain operation looking at the drain 
socket.

4

After checking the drainage flow, turn off power, 
remove the control box cover and disconnect the 
power supply from the power supply terminal block 
again. Fit the control box cover back in place.

Option

Description

Remark

BYCQ140CW1

Decoration panel - 
standard

BYCQ140CW1W

Decoration panel - 
white

KAFP551K160

Long life replacement 
filter

KDDQ55C140

Fresh air intake kit

Installation: refer to
FXFQ125P.

KDBHQ55C140

Sealing member of 
air discharge outlet

Settings: refer to type 
Y.

BRC7F532F

Remote controller - 
wireless (cooling and 
heating)

Not all functions are 
available for the FWC 
models.

Summary of Contents for FWC06B7TV1B

Page 1: ...INSTALLATION MANUAL Fan coil units Cover Cover Type numbers FWC06B7TV1B FWC07B7TV1B FWC08B7TV1B FWC09B7TV1B FWC06B7FV1B FWC07B7FV1B FWC08B7FV1B FWC09B7FV1B...

Page 2: ...mm F1 F2 P1 P2 T1 T2 k i j j i g 1x 1x 8x 4x 1x 1x 1x 1x 1x 1x 1x FWC_T 2x FWC_F 4x FWC_T 2x FWC_F 4x FWC_T 2x FWC_F 4x a b c d e h i j k l m f g n a f b d c e 4 mm c e b A A A A a a a b 2500 1500 29...

Page 3: ...em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt...

Page 4: ...o install and operate the associated products and or optional equipment refer to the relevant catalogues technical literature or product manuals for those products The original documentation is writte...

Page 5: ...r scalding Danger electric shock Switch off all power supply before removing the control box cover or before making any connections or touching electrical parts To avoid electric shock be sure to disc...

Page 6: ...mperature is 5 C Q the maximum water temperature is 50 C 2 pipe fan coil units and 70 C 4 pipe fan coil units Q be sure to install components in the field piping that can withstand the water pressure...

Page 7: ...directions Select the air flow directions best suited for the room and point of installation For air discharge in 2 or 3 directions it is necessary to make field settings by means of the remote contr...

Page 8: ...he hanger bracket as illustrated in figure 15 Securing the hanger bracket 2 Fix the paper pattern for installation delivered with the unit For new ceilings only Q The paper pattern for installation co...

Page 9: ...onnection Connect the water inlet and outlet connections of the fan coil unit to the water piping as illustrated in figure 5 Connecting the water piping In case the optional valve is used refer to the...

Page 10: ...transmission wiring and other wiring Failure to observe this guideline may result in malfunction due to electrical noise Q For the remote controller wiring refer to the installation manual of the remo...

Page 11: ...Pull the cables i j inside through the remote controller and unit transmission cables intake h 3 Strip the wires to the recommended length 4 Connect the remote controller wires to P1 P2 terminals of t...

Page 12: ...ment refer to the installation manual which is delivered with the optional equipment and take into account the remarks mentioned in the table below a Ceiling slab b Hanger bracket c Drain raising pipe...

Page 13: ...n manual delivered with the option EKRP1C11 but refer to the installation manual of options EKMV2 and EKMV3 instead EKFCMBCB7 Optional PCB for Modbus connection Option Description Remark Danger electr...

Page 14: ...N dealer Test operation before installing decoration panel 1 Open the water inlet valve s 2 Open the water outlet valve s 3 Set to cooling operation with the remote controller and start operation by p...

Page 15: ...t brush and neutral detergent and dry thoroughly See figure 21 Cleaning the suction grill 6 Attach the air filter to the suction grill by hanging it to the projected portion above the suction grill Pr...

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ...P1 L N L a N P2 F1 F2 T1 T2 P1 L N L N P2 F1 F2 T1 T2 P1 L N L N P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 L N L N P2 F1 F2 T1 T2 c b 100 0 675 a a a a 710 840 860 910 860 860 910 950 20 35 20 35 780...

Page 20: ...Copyright 2010 Daikin 4PW64525 1B 2014 03 Cover Rear Cover Rear...

Reviews: