Installation manual

11

FWC

Fan coil units

4PW64525-1B – 2014.03

Commission the fan coil unit

5.2.

Configure the unit

It is important that all information in this chapter is read sequentially by 
the installer and that the unit is configured as applicable.
Configuration of the unit is done trough the controller in accordance 
with the installation condition.

Q

Setting can be made by changing the “Mode No.”, “First code 
No.” and “Second code No.”.

Q

For setting and operation, refer to “Field setting” in the installation 
manual of the controller.

Setting ceiling height

Adjust the Second code No. according to the table below so that it 
corresponds to the ceiling height of your installation. (Second code 
No. is factory set to “01”)

Table 5.2: Ceiling height setting

Setting air discharge direction

For changing air discharge direction (2, 3 or 4 directions), refer to the 
option handbook of the optional blocking pad kit. (Second code No. is 
factory set to “01” for all-round air discharge)

Setting air filter sign

Remote controllers are equipped with liquid crystal air filter signs to 
display the time to clean the air filter. Change the Second code No. 
Depending on the amount of dirt or dust in the room. (Second code 
No. is factory set to “01” for air filter contamination-light)

Table 5.3: Air filter contamination

When using wireless remote controllers it is necessary to use address 
setting. Refer to the controller installation manual for the setting 
instructions.

Activating forced OFF and ON/OFF operation

The following table explains “forced OFF” and “ON/OFF operations” in 
response to the input signal. 

Table 5.4: Forced OFF and ON/OFF operation

1

Turn the power on and then use the remote controller to select 
operation.

2

Set the remote controller to the field set mode. 

Table 5.5: Forced OFF and ON/OFF selection

Commission the fan coil unit

5.3.

Test the installation

After installation, the installer is obliged to verify correct operation. 
In case something is wrong with the unit and it does not operate, 
contact your local DAIKIN dealer.

Test operation before installing decoration panel

1

Open the water inlet valve(s).

2

Open the water outlet valve(s).

3

Set to cooling operation with the remote controller and start 
operation by pushing 

ON/OFF

 button.

4

Press 

Inspection/Test Operation

 button 

 4 times and 

operate at 

Test Operation

 mode for 3 minutes.

5

Press 

Inspection/Test Operation

 button 

 and operate 

normally.

6

Confirm function of unit according to the operation manual.

7

Turn off the main power supply after operation.

Test operation after installing decoration panel

1

Open the water inlet valve(s).

2

Open the water outlet valve(s).

3

Set to cooling operation with the remote controller and start 
operation by pushing 

ON/OFF

 button.

4

Press

 Inspection/Test Operation

 button 

 4 times (2 

times for wireless remote controller) and operate at 

Test Opera-

tion

 mode for 3 minutes.

5

Push 

air flow direction adjust

 button 

 to make sure 

the unit is in operation.

6

Press 

Inspection/Test Operation

 button 

 and operate 

normally.

7

Confirm function of unit according to the operation manual.

Commission the fan coil unit

5.4.

Handover to the user

Once the test run is finished and the unit operates properly, fill in the 
sheet “Handover of the installation to the user” which is an annex of 
the user manual.

Service and maintenance

Service and maintenance

Ceiling height 
(m)

Mode No.

First code No.

Second code 

No.

3.2

13(23)

0

01

>3.2 or 

3.6

13(23)

0

02

>3.6 or 

4.2

13(23)

0

03

Setting

Display 
interval

Mode No.

First code 

No.

Second 

code No.

Light

±2500 hrs

10(20)

0

01

Heavy

±1250 hrs

10(20)

0

02

No display

10(20)

3

02

Forced OFF

ON/OFF operations Protective 

equipment input

Input “ON” stops 
operation

Input OFF

ON: 

turns on the unit 
(impossible by 
remote controllers)

Input ON: enables 
abnormal system 
stop (an error code 
will be displayed)

Input “OFF” enables 
control

Input ON

OFF: 

turns off the unit (by 
remote controller)

Input OFF: enables 
normal operation

Setting

Mode No.

First code 
No.

Second 
code No.

Forced OFF

12(22)

8

01

ON/OFF 
operation

12(22)

8

02

Protective 
equipment 
input

12(22)

8

03

Information

When using a wireless remote controller, conduct a test 
operation after installing the decoration panel.

Danger: electric shock

See 

“Precautions for installation” on page 2

.

Summary of Contents for FWC06B7FV1B

Page 1: ...INSTALLATION MANUAL Fan coil units Cover Cover Type numbers FWC06B7TV1B FWC07B7TV1B FWC08B7TV1B FWC09B7TV1B FWC06B7FV1B FWC07B7FV1B FWC08B7FV1B FWC09B7FV1B...

Page 2: ...mm F1 F2 P1 P2 T1 T2 k i j j i g 1x 1x 8x 4x 1x 1x 1x 1x 1x 1x 1x FWC_T 2x FWC_F 4x FWC_T 2x FWC_F 4x FWC_T 2x FWC_F 4x a b c d e h i j k l m f g n a f b d c e 4 mm c e b A A A A a a a b 2500 1500 29...

Page 3: ...em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt...

Page 4: ...o install and operate the associated products and or optional equipment refer to the relevant catalogues technical literature or product manuals for those products The original documentation is writte...

Page 5: ...r scalding Danger electric shock Switch off all power supply before removing the control box cover or before making any connections or touching electrical parts To avoid electric shock be sure to disc...

Page 6: ...mperature is 5 C Q the maximum water temperature is 50 C 2 pipe fan coil units and 70 C 4 pipe fan coil units Q be sure to install components in the field piping that can withstand the water pressure...

Page 7: ...directions Select the air flow directions best suited for the room and point of installation For air discharge in 2 or 3 directions it is necessary to make field settings by means of the remote contr...

Page 8: ...he hanger bracket as illustrated in figure 15 Securing the hanger bracket 2 Fix the paper pattern for installation delivered with the unit For new ceilings only Q The paper pattern for installation co...

Page 9: ...onnection Connect the water inlet and outlet connections of the fan coil unit to the water piping as illustrated in figure 5 Connecting the water piping In case the optional valve is used refer to the...

Page 10: ...transmission wiring and other wiring Failure to observe this guideline may result in malfunction due to electrical noise Q For the remote controller wiring refer to the installation manual of the remo...

Page 11: ...Pull the cables i j inside through the remote controller and unit transmission cables intake h 3 Strip the wires to the recommended length 4 Connect the remote controller wires to P1 P2 terminals of t...

Page 12: ...ment refer to the installation manual which is delivered with the optional equipment and take into account the remarks mentioned in the table below a Ceiling slab b Hanger bracket c Drain raising pipe...

Page 13: ...n manual delivered with the option EKRP1C11 but refer to the installation manual of options EKMV2 and EKMV3 instead EKFCMBCB7 Optional PCB for Modbus connection Option Description Remark Danger electr...

Page 14: ...N dealer Test operation before installing decoration panel 1 Open the water inlet valve s 2 Open the water outlet valve s 3 Set to cooling operation with the remote controller and start operation by p...

Page 15: ...t brush and neutral detergent and dry thoroughly See figure 21 Cleaning the suction grill 6 Attach the air filter to the suction grill by hanging it to the projected portion above the suction grill Pr...

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ...P1 L N L a N P2 F1 F2 T1 T2 P1 L N L N P2 F1 F2 T1 T2 P1 L N L N P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 L N L N P2 F1 F2 T1 T2 c b 100 0 675 a a a a 710 840 860 910 860 860 910 950 20 35 20 35 780...

Page 20: ...Copyright 2010 Daikin 4PW64525 1B 2014 03 Cover Rear Cover Rear...

Reviews: