FWC

Fan coil units
4PW64525-1B – 2014.03

Installation manual

6

Install the fan coil unit

3

Adjust the unit to the right position for installation.
Use the installation guide (delivered with the unit) for exact 
vertical positioning of the unit.

Q

Apply the short side of the installation guide in case of 

normal installation

 as illustrated below.

Fig. 4.2: Normal installation

Q

Apply the long side of the installation guide in case of 

installation with fresh air intake kit

 as illustrated below.

Fig. 4.3: Installation with fresh air intake

4

Check if the unit is horizontally levelled.

Q

Do not install the unit tilted. The unit is equipped with a built-
in drain pump and float switch. If the unit is tilted against the 
direction of the condensate flow (the drain piping side is 
raised), the float switch may malfunction and cause water to 
drip.

Q

Check if the unit is levelled at all four corners with a water 
level or a water-filled vinyl tube as illustrated in the figure 
below.

Fig. 4.4: Check if unit is levelled

5

Remove the paper pattern for installation. (For new ceilings only.)

Install the fan coil unit

4.5.

Perform the water piping work

Install the fan coil unit

4.5.1. Connect the water pipes

The unit is equipped with water outlet and inlet connections. There is 
an air purge valve that is fitted along with the water inlets and outlets 
for air purging as illustrated in figure 6: “Water piping connection”.

Connect the water inlet and outlet connections of the fan coil unit to 
the water piping as illustrated in figure 5: “Connecting the water 
piping”. 

In case the optional valve is used, refer to the installation manual of 
the valve kit to install the field piping.

Install the fan coil unit

4.5.2. Insulate the water pipes

The complete water circuit, inclusive all piping, must be insulated to 
prevent condensation and reduction of the capacity. 

Fig. 4.5: Water piping insulation

If the temperature is higher than 30°C and the relative humidity is 
higher than 80%, then the thickness of the sealing materials shall be 
at least 20 mm in order to avoid condensation on the surface of the 
sealing.

Install the fan coil unit

a

Suspended ceiling

b

Fan coil unit

a

Suspended ceiling

b

Fan coil unit

a

Water level

b

Vinyl tube

a

b

a

b

b

b

a

a

Drain pipe connection

b

Power supply entry hole

c

Water inlet (3/4" female BSP)

d

Water outlet (3/4" female BSP)

e

Cold water inlet (3/4" female BSP)

f

Cold water outlet (3/4" female BSP)

g

Hot water inlet (3/4" female BSP)

h

Hot water outlet (3/4" female BSP)

i

Transmission wiring entry

j

Air purge valve

a

Water piping:

Q

3/4" male BSP in case of direct connection to 
the unit,

Q

3/4" female BSP in case of connection to an 
optional valve.

b

O-ring (delivered with the unit)

Notice

Do not use excessive force when connecting the piping. 
This could deform the unit piping.
Deformation of the piping can cause the unit to malfunction.

a

Water inlet

b

Water outlet

c

Sealing pad for piping connections (delivered with 
the unit)

d

Insulation tube (delivered with the unit)

b

a

d

c

c

d

Summary of Contents for FWC06B7FV1B

Page 1: ...INSTALLATION MANUAL Fan coil units Cover Cover Type numbers FWC06B7TV1B FWC07B7TV1B FWC08B7TV1B FWC09B7TV1B FWC06B7FV1B FWC07B7FV1B FWC08B7FV1B FWC09B7FV1B...

Page 2: ...mm F1 F2 P1 P2 T1 T2 k i j j i g 1x 1x 8x 4x 1x 1x 1x 1x 1x 1x 1x FWC_T 2x FWC_F 4x FWC_T 2x FWC_F 4x FWC_T 2x FWC_F 4x a b c d e h i j k l m f g n a f b d c e 4 mm c e b A A A A a a a b 2500 1500 29...

Page 3: ...em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt...

Page 4: ...o install and operate the associated products and or optional equipment refer to the relevant catalogues technical literature or product manuals for those products The original documentation is writte...

Page 5: ...r scalding Danger electric shock Switch off all power supply before removing the control box cover or before making any connections or touching electrical parts To avoid electric shock be sure to disc...

Page 6: ...mperature is 5 C Q the maximum water temperature is 50 C 2 pipe fan coil units and 70 C 4 pipe fan coil units Q be sure to install components in the field piping that can withstand the water pressure...

Page 7: ...directions Select the air flow directions best suited for the room and point of installation For air discharge in 2 or 3 directions it is necessary to make field settings by means of the remote contr...

Page 8: ...he hanger bracket as illustrated in figure 15 Securing the hanger bracket 2 Fix the paper pattern for installation delivered with the unit For new ceilings only Q The paper pattern for installation co...

Page 9: ...onnection Connect the water inlet and outlet connections of the fan coil unit to the water piping as illustrated in figure 5 Connecting the water piping In case the optional valve is used refer to the...

Page 10: ...transmission wiring and other wiring Failure to observe this guideline may result in malfunction due to electrical noise Q For the remote controller wiring refer to the installation manual of the remo...

Page 11: ...Pull the cables i j inside through the remote controller and unit transmission cables intake h 3 Strip the wires to the recommended length 4 Connect the remote controller wires to P1 P2 terminals of t...

Page 12: ...ment refer to the installation manual which is delivered with the optional equipment and take into account the remarks mentioned in the table below a Ceiling slab b Hanger bracket c Drain raising pipe...

Page 13: ...n manual delivered with the option EKRP1C11 but refer to the installation manual of options EKMV2 and EKMV3 instead EKFCMBCB7 Optional PCB for Modbus connection Option Description Remark Danger electr...

Page 14: ...N dealer Test operation before installing decoration panel 1 Open the water inlet valve s 2 Open the water outlet valve s 3 Set to cooling operation with the remote controller and start operation by p...

Page 15: ...t brush and neutral detergent and dry thoroughly See figure 21 Cleaning the suction grill 6 Attach the air filter to the suction grill by hanging it to the projected portion above the suction grill Pr...