5 Unit installation

Installation manual

8

C FVXM25~50A

Split system air conditioners

3P477070-2M – 2021.09

5.3.2

To drill a wall hole

CAUTION

For walls containing a metal frame or a metal board, use a
wall  embedded  pipe  and  wall  cover  in  the  feed-through
hole to prevent possible heat, electrical shock, or fire.

NOTICE

Be  sure  to  seal  the  gaps  around  the  pipes  with  sealing
material (field supply), in order to prevent water leakage.

1

Bore  a  65  mm  large  feed-through  hole  in  the  wall  with  a
downward slope towards the outside.

2

Insert a wall embedded pipe into the hole.

3

Insert a wall cover into the wall pipe.

Ø65

a b

c

a

Wall embedded pipe

b

Putty

c

Wall hole cover

4

After  completing  wiring,  refrigerant  piping  and  drain  piping,  do
NOT forget to seal the gap with putty.

5.3.3

To remove the slit portions

For  side  piping  (left/right)  and  bottom  piping  (left/right)  slit  portions
must  be  removed.  Remove  slit  portions  according  to  where  the
piping is taken out.

a

c

d

d

b

a

Bottom frame

b

Slit portion for side piping on the front grille (same on the
other side)

c

Slit portion for side piping on the bottom frame (same of
the other side)

d

Slit portion for the bottom piping

1

Cut off the slit portion using nippers.

2

Remove  an  burrs  along  the  cut  section  using  a  half  round
needle file.

5.3.4

To provide drainage

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe  size.

  Use  rigid  polyvinyl  chloride  pipe  with  20  mm  nominal

diameter and 26 mm outer diameter.

NOTICE

▪ Install the drain hose with a downward slope.

▪ Traps are NOT permitted.

▪ Do NOT put the end of the hose in water.

Drain  hose. 

Drain  hose  (accessory)  is  220  mm  long  and  with

18 mm outer diameter on the connecting side.

Extension  hose.

  Use  rigid  polyvinyl  chloride  pipe  (field  supply)

with  20  mm  nominal  diameter  as  extension  hose.  When
connecting an extension hose, use a polyvinyl adhesive agent for
glueing.

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

To connect the drain piping to the indoor unit

NOTICE

Incorrect  connection  of  the  drain  hose  might  cause  leaks,
and damage the installation space and surroundings.

1

Push  the  drain  hose  (accessory)  as  far  as  possible  over  the
drain socket and fix it with 1 screw (accessory).

Summary of Contents for FVXM25A2V1B

Page 1: ...stallation manual Split system air conditioners English Installation manual Split system air conditioners CVXM20A2V1B CVXM20A3V1B FVXM25A2V1B FVXM35A2V1B FVXM50A2V1B FVXM25A3V1B FVXM35A3V1B FVXM50A3V1...

Page 2: ...iring diagram legend 12 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask him her to keep it for future reference Target audie...

Page 3: ...e in contact with sharp edges or piping particularly on the high pressure side Do NOT use taped wires stranded conductor wires extension cords or connections from a star system They can cause overheat...

Page 4: ...ed version of Android or iOS specified on app daikineurope com Internet line and communicating device such as modem router etc Wireless LAN access point Installed free Daikin Residential Controller ap...

Page 5: ...ck 1 Remove the front grille 2 Remove 1 lower screw 3 Lift the sensor securing plate 4 Move the metal plate cover down and then towards you to remove it c b c b a 1 2 3 a Screw b Sensor securing plate...

Page 6: ...n is finished attach the front panel and the front grille in their original position Wall mounted installation 82 166 0 6 mm 627 5 750 0 0 6 553 300 200 285 115 238 b b b b 75 0 6 75 45 65 65 45 d e 7...

Page 7: ...ng Half concealed installation A Front view B Side view C Top view a Extra filler board b Screw hole 6 c Hole d Left back piping hole location e Right back piping hole location f Right left piping hol...

Page 8: ...ame same of the other side d Slit portion for the bottom piping 1 Cut off the slit portion using nippers 2 Remove an burrs along the cut section using a half round needle file 5 3 4 To provide drainag...

Page 9: ...it 3MXM40N8 or 3MXM52N8 with the indoor units CVXM A and or FVXM A The total piping length MUST be 30 m Foreign materials inside pipes including oils for fabrication must be 30 mg 10 m Refrigerant pip...

Page 10: ...voltage category III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard WARNING Do NOT connect th...

Page 11: ...h each turn a b c d e f a Interconnection cable b Gas pipe c Gas pipe insulation d Insulation tape e Liquid pipe f Liquid pipe insulation 2 Pass the pipes through the wall hole and seal the gaps with...

Page 12: ...and other parts MUST comply with applicable legislation Units MUST be treated at a specialised treatment facility for reuse recycling and recovery 11 Technical data A subset of the latest technical da...

Page 13: ...verload protector Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL...

Page 14: ......

Page 15: ......

Page 16: ...3P477070 2M 2021 09 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: