7 Electrical installation

Installation manual

10

C FVXM25~50A

Split system air conditioners

3P477070-2M – 2021.09

6.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

6.2.1

To connect the refrigerant piping to the
indoor unit

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

Pipe length

. Keep refrigerant piping as short as possible.

1

Connect refrigerant piping to the unit using 

flare connections

.

2

Insulate

 the refrigerant piping on the indoor unit as follows:

a

b

c

d

a

Gas pipe

b

Gas pipe insulation

c

Liquid pipe

d

Liquid pipe insulation

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

3

Close  the  slit  on  the  refrigerant  pipe  connection  and  secure  it
with a tape (field supply). Make sure there are no gaps.

4

Wrap  the  slit  and  the  end  of  the  insulation  of  the  connected
refrigerant  piping  with  insulation  piece  (accessory).  Make  sure
there are no gaps.

a

b

a

a

e

b

e

c

b

a

d

c

d

b

a

Refrigerant pipe connection

b

Refrigerant piping (field supply)

c

Slit

d

Tape

e

Insulation piece (accessory)

7

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

7.1

Specifications of standard wiring
components

Component

Interconnection cable
(indoor↔outdoor)

4-core cable

1.5 mm²~2.5 mm²
and applicable for

220~240 V

H05RN-F (60245 IEC 57)

7.2

To connect the electrical wiring to
the indoor unit

1

Open the terminal block. See 

"5.2 Opening the indoor unit"

 [

4

 4].

2

Strip the wire ends approximately 15 mm.

3

Match  wire  colours  with  terminal  numbers  on  indoor  and
outdoor  unit’s  terminal  blocks  and  firmly  screw  wires  to  the
corresponding terminals.

4

Connect the earth wires to the corresponding terminals.

a
b

c

a

Terminal block

b

Electrical component block

c

Cable clamp

5

Pull  the  wires  to  make  sure  that  they  are  securely  attached,
then retain the wires with the cable clamp.

6

Make sure that the wires do not come in contact with the metal
parts of the heat exchanger.

7

In  case  of  connecting  to  an  optional  adapter,  see 

"7.3  To

connect optional accessories (wired user interface, central user
interface, wireless adapter, etc.)"

 [

4

 11].

Summary of Contents for FVXM25A2V1B

Page 1: ...stallation manual Split system air conditioners English Installation manual Split system air conditioners CVXM20A2V1B CVXM20A3V1B FVXM25A2V1B FVXM35A2V1B FVXM50A2V1B FVXM25A3V1B FVXM35A3V1B FVXM50A3V1...

Page 2: ...iring diagram legend 12 1 About the documentation 1 1 About this document INFORMATION Make sure that the user has the printed documentation and ask him her to keep it for future reference Target audie...

Page 3: ...e in contact with sharp edges or piping particularly on the high pressure side Do NOT use taped wires stranded conductor wires extension cords or connections from a star system They can cause overheat...

Page 4: ...ed version of Android or iOS specified on app daikineurope com Internet line and communicating device such as modem router etc Wireless LAN access point Installed free Daikin Residential Controller ap...

Page 5: ...ck 1 Remove the front grille 2 Remove 1 lower screw 3 Lift the sensor securing plate 4 Move the metal plate cover down and then towards you to remove it c b c b a 1 2 3 a Screw b Sensor securing plate...

Page 6: ...n is finished attach the front panel and the front grille in their original position Wall mounted installation 82 166 0 6 mm 627 5 750 0 0 6 553 300 200 285 115 238 b b b b 75 0 6 75 45 65 65 45 d e 7...

Page 7: ...ng Half concealed installation A Front view B Side view C Top view a Extra filler board b Screw hole 6 c Hole d Left back piping hole location e Right back piping hole location f Right left piping hol...

Page 8: ...ame same of the other side d Slit portion for the bottom piping 1 Cut off the slit portion using nippers 2 Remove an burrs along the cut section using a half round needle file 5 3 4 To provide drainag...

Page 9: ...it 3MXM40N8 or 3MXM52N8 with the indoor units CVXM A and or FVXM A The total piping length MUST be 30 m Foreign materials inside pipes including oils for fabrication must be 30 mg 10 m Refrigerant pip...

Page 10: ...voltage category III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard WARNING Do NOT connect th...

Page 11: ...h each turn a b c d e f a Interconnection cable b Gas pipe c Gas pipe insulation d Insulation tape e Liquid pipe f Liquid pipe insulation 2 Pass the pipes through the wall hole and seal the gaps with...

Page 12: ...and other parts MUST comply with applicable legislation Units MUST be treated at a specialised treatment facility for reuse recycling and recovery 11 Technical data A subset of the latest technical da...

Page 13: ...verload protector Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL...

Page 14: ......

Page 15: ......

Page 16: ...3P477070 2M 2021 09 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: