7 Electrical installation

Installation manual

11

FTXTP-M_FTXTP-N
Daikin room air conditioner
3P650253-16U – 2023.03

(a)

Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.

6.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

10~14 mm

≥13 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

6.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

6.2.1

To connect the refrigerant piping to the
indoor unit

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

Pipe length

. Keep refrigerant piping as short as possible.

1

Connect refrigerant piping to the unit using 

flare connections

.

2

Wrap  the  refrigerant  piping  connection  using  vinyl  tape,
overlapping  at  least  half  the  width  of  the  tape  with  each  turn.
Keep  the  slit  of  the  heat  insulation  pipe  cover  up.  Avoid
wrapping the tape too tight.

b

a

c d

e

f

e

a

Heat insulation pipe cover (on the indoor unit side)

b

Flare connections

c

Liquid pipe (with insulation) (field supply)

d

Gas pipe (with insulation) (field supply)

e

Slit on heat insulation pipe cover facing up

f

Vinyl tape (field supply)

3

Insulate 

the  refrigerant  piping,  interconnection  cable  and  drain

hose  on  the  indoor  unit:  See 

"8.1  To  insulate  the  drain  piping,

refrigerant piping and interconnection cable"

 [

4

 12].

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

6.2.2

To check refrigerant piping joints for leaks
after charging refrigerant

1

Perform  the  leak  tests  according  to  instructions  in  the  outdoor
unit installation manual.

2

Charge refrigerant.

3

Check for refrigerant leaks after charging (see below).

Tightness test of field-made refrigerant joints indoors

1

Use a leakage test method with a minimum sensitivity of 5 g of
refrigerant/year.  Test  leaks  using  a  pressure  of  at  least  0.25
times  the  maximum  working  pressure  (see  "PS  High"  on  the
unit nameplate).

If a leak is detected

1

Recover the refrigerant, repair the joint, and repeat the test.

7

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provides  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

7.1

Specifications of standard wiring
components

NOTICE

We recommend using solid (single-core) wires. If stranded
wires are used, slightly twist the strands to consolidate the
end  of  the  conductor  for  either  direct  use  in  the  terminal
clamp  or  insertion  in  a  round  crimp-style  terminal.  Details
are described in "Guidelines when connecting the electrical
wiring" in the installer reference guide.

Summary of Contents for FTXTP25N5V1B

Page 1: ...Installation manual Daikin room air conditioner English Installation manual Daikin room air conditioner FTXTP25M5V1B FTXTP35M5V1B FTXTP25N5V1B FTXTP35N5V1B...

Page 2: ...antis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e s...

Page 3: ...h our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulatio...

Page 4: ...nstrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e sa v robky p...

Page 5: ...tions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 follo...

Page 6: ...commissioning 15 11 2 To perform a test run 15 11 2 1 To perform a test run in winter season 15 12 Disposal 15 13 Technical data 15 13 1 Wiring diagram 15 13 1 1 Unified wiring diagram legend 15 1 Abo...

Page 7: ...UST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge...

Page 8: ...rol equipment E g automatic doors or fire alarm equipment This product may cause faulty behaviour of the equipment Microwave oven It may affect wireless LAN communications 4 1 2 Basic parameters What...

Page 9: ...ipe end d Through the wall hole 65 mm e Drain hose position 5 2 2 To drill a wall hole CAUTION For walls containing a metal frame or a metal board use a wall embedded pipe and wall cover in the feed t...

Page 10: ...kage from the plug 3 Insert the drain hose on the left side and do not forget to tighten it with the fixing screw otherwise water leakage may occur a b a b a Insulation fixing screw b Drain hose 4 Att...

Page 11: ...t piping and interconnection cable 412 NOTICE Make sure to insulate all refrigerant piping Any exposed piping might cause condensation 6 2 2 To check refrigerant piping joints for leaks after charging...

Page 12: ...About the documentation 46 3 Pass the interconnection cable from the outdoor unit through the feed through wall hole through the back of the indoor unit and through the front side Note In case the in...

Page 13: ...3 Press the bottom edge of the indoor unit with both hands until it is firmly caught by the mounting plate hooks 4 Secure the indoor unit to the mounting plate using 2 indoor unit fixing screws M4 12L...

Page 14: ...ONECTA application 9 2 1 To install the ONECTA app 1 Go to Google Play for Android devices or the App Store for iOS devices and search for ONECTA 2 Follow the directions on the screen to install the...

Page 15: ...that all functions and parts are working properly 1 In cooling mode select the lowest programmable temperature In heating mode select the highest programmable temperature Test run can be disabled if...

Page 16: ...Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude m...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P650253 16U 2023 03 Copyright 2...

Reviews: