6 Piping installation

Installation manual

10

FTXTP-M_FTXTP-N

Daikin room air conditioner

3P650253-16U – 2023.03

NOTICE

Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.

5.3

Connecting the drain piping

5.3.1

To connect the piping on right side, right-
back, or right-bottom

INFORMATION

The factory default is right-side piping. For left-side piping,
remove  the  piping  from  the  right  side  and  install  it  on  the
left side.

1

Attach the drain hose with adhesive vinyl tape to the bottom of
the refrigerant pipes.

2

Wrap  the  drain  hose  and  the  refrigerant  pipes  together  using
insulation tape.

A

B

a b

A

Right-side piping

B

Right-bottom piping

C

Right-back piping

a

Remove the pipe port cover here for right side piping

b

Remove the pipe port cover here for right-bottom piping

5.3.2

To connect the piping on left side, left-
back, or left-bottom

INFORMATION

The factory default is right-side piping. For left-side piping,
remove  the  piping  from  the  right  side  and  install  it  on  the
left side.

1

Remove  the  insulation  fixing  screw  on  the  right  side  and
remove the drain hose.

2

Remove the drain plug on the left side and attach it to the right
side.

NOTICE

Do  NOT  apply  lubricating  oil  (refrigerant  oil)  to  the  drain
plug when inserting it. The drain plug may deteriorate and
cause drain leakage from the plug.

3

Insert the drain hose on the left side and do not forget to tighten
it with the fixing screw; otherwise water leakage may occur.

a

b

a

b

a

Insulation fixing screw

b

Drain hose

4

Attach the drain hose to the refrigerant piping bottom side using
adhesive vinyl tape.

A

B

b

a

A

Left-side piping

B

Left-back piping

C

Left-bottom piping

a

Remove the pipe port cover here for left-side piping

b

Remove the pipe port cover here for left-bottom piping

5.3.3

To check for water leaks

1

Remove the air filters.

2

Gradually pour approximately 1 l of water in the drain pan, and
check for water leaks.

6

Piping installation

6.1

Preparing refrigerant piping

6.1.1

Refrigerant piping requirements

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant piping.

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

Liquid piping

Gas piping

Ø6.4 mm

Ø9.5 mm

Refrigerant piping material

Piping material:

 phosphoric acid deoxidised seamless copper

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

Annealed (O)

Summary of Contents for FTXTP25N5V1B

Page 1: ...Installation manual Daikin room air conditioner English Installation manual Daikin room air conditioner FTXTP25M5V1B FTXTP35M5V1B FTXTP25N5V1B FTXTP35N5V1B...

Page 2: ...antis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e s...

Page 3: ...h our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulatio...

Page 4: ...nstrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e sa v robky p...

Page 5: ...tions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 follo...

Page 6: ...commissioning 15 11 2 To perform a test run 15 11 2 1 To perform a test run in winter season 15 12 Disposal 15 13 Technical data 15 13 1 Wiring diagram 15 13 1 1 Unified wiring diagram legend 15 1 Abo...

Page 7: ...UST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge...

Page 8: ...rol equipment E g automatic doors or fire alarm equipment This product may cause faulty behaviour of the equipment Microwave oven It may affect wireless LAN communications 4 1 2 Basic parameters What...

Page 9: ...ipe end d Through the wall hole 65 mm e Drain hose position 5 2 2 To drill a wall hole CAUTION For walls containing a metal frame or a metal board use a wall embedded pipe and wall cover in the feed t...

Page 10: ...kage from the plug 3 Insert the drain hose on the left side and do not forget to tighten it with the fixing screw otherwise water leakage may occur a b a b a Insulation fixing screw b Drain hose 4 Att...

Page 11: ...t piping and interconnection cable 412 NOTICE Make sure to insulate all refrigerant piping Any exposed piping might cause condensation 6 2 2 To check refrigerant piping joints for leaks after charging...

Page 12: ...About the documentation 46 3 Pass the interconnection cable from the outdoor unit through the feed through wall hole through the back of the indoor unit and through the front side Note In case the in...

Page 13: ...3 Press the bottom edge of the indoor unit with both hands until it is firmly caught by the mounting plate hooks 4 Secure the indoor unit to the mounting plate using 2 indoor unit fixing screws M4 12L...

Page 14: ...ONECTA application 9 2 1 To install the ONECTA app 1 Go to Google Play for Android devices or the App Store for iOS devices and search for ONECTA 2 Follow the directions on the screen to install the...

Page 15: ...that all functions and parts are working properly 1 In cooling mode select the lowest programmable temperature In heating mode select the highest programmable temperature Test run can be disabled if...

Page 16: ...Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude m...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P650253 16U 2023 03 Copyright 2...

Reviews: